UL 325 2018 Standard - MAX 1500 PRO/2200 PRO/F18 PRO Matrix III Install Version 7

d

ul 325 compliant installation 

requirements continued

g) The Stop and/or Reset button must be located in the lineof-sight of the gate. Activation of the reset control shall not cause the operator to

start.

g) Le bouton d’arrêt, le bouton de réenclenchement ou ces deux boutons doivent être situés dans le champ de visibilité de la barrière.

L’activation des commandes de réenclenchement ne doit pas mettre en marche l’ouvrebarrière.

h) A minimum of two (2) WARNING SIGNS shall be installed, in the area of the gate. Each placard is to be visible by persons located on the

side of the gate on which the placard is installed. Also see 62.1.1.

h) Au moins deux panneaux de mise en garde doivent être installés dans la zone de la barrière. Chaque étiquette doit être visible des

personnes situées de chaque côté de la barrière sur laquelle l’étiquette est installée. Voir aussi la clause 62.1.1.

i) For gate operators utilizing a non-contact sensor in accordance with 32.1.1:

i) Pour les ouvre-barrières qui fonctionnent avec des capteurs sans contact conformément à la clause 32.1.1 :

1) See instructions on the placement of non-contact sensors for each Type of application,

1) Voir les instructions sur le positionnement des capteurs sans contact pour chaque type d’utilisation.

2) Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle, trips the sensor while the gate is still moving, and

2) Des précautions doivent être prises pour réduire les risques de déclenchement inutile, comme lorsqu’un véhicule déclenche le capteur alors

que la barrière est encore en mouvement.

3) One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a

moving gate or barrier.

3) Un capteur sans contact ou plus doit être situé où il existe un risque de coincement ou d’obstruction, comme dans l’espace que peut

occuper la barrière lorsqu’elle est en mouvement.

j) For a gate operator utilizing a contact sensor in accordance with 32.1.1:

j) Pour les ouvre-barrières qui fonctionnent avec des capteurs de contact conformément à la clause 32.1.1 :

1) One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as at the leading edge, trailing edge,

and postmounted both inside and outside of a vehicular horizontal slide gate.

1) Au moins un capteur de contact doit être situé où il existe un risque de coincement ou d’obstruction, comme sur le bord d’ouverture, sur le

bord de fermeture et sur les poteaux montés sur l’intérieur ou l’extérieur d’une barrière coulissante pour véhicules.

2) One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.

2) Au moins un capteur de contact doit être situé sur le bord inférieur d’une barrière levante pour véhicules.

3) One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.

3) Au moins un capteur de contact doit être situé au point de pincement d’une barrière à pivot vertical pour véhicules.

4) A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is

not subjected to mechanical damage.

4) Un capteur de contact doit être installé et câblé de sorte à éviter que la communication entre le capteur et l’ouvrebarrière soit gênée par des

dommages mécaniques.

5) A wireless device such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be

located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruc-

tion. A wireless device shall function under the intended end-use conditions.

5) Un dispositif sans fil, comme un appareil qui transmet des signaux de radiofréquence (RF) à l’ouvre-barrière pour prévenir le coincement,

doit être situé à un endroit où la transmission des signaux ne sera pas obstruée ou gênée par des structures, des arbres ou d’autres obstacles

similaires. Un dispositif sans fil doit fonctionner selon les conditions d’utilisation finale prévues.

6) One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a

swing gate is greater than 152 mm (6 inches) but less than 406 mm (16 inches) above the ground at any point in its arc of travel, one or more

contact sensors shall be located on the bottom edge.

6) Au moins un capteur de contact doit être situé sur les bords d’ouverture intérieur et extérieur d’une barrière battante. De plus, si le dessous

d’une barrière battante est situé à plus de 152 mm (6 po) mais à moins de 406 mm (16 po) du sol à l’un des points de sa trajectoire, au moins

un capteur de contact doit être situé sur le bord inférieur.

7) One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).

7) Au moins un capteur de contact doit être situé sur le bord inférieur d’une barrière verticale (bras).

Safety-2

Содержание MAX 1500 PRO

Страница 1: ...TO UL STD 325 MAX 1500 PRO 2200 PRO UL CLASS I II III IV MAX F18 PRO UL CLASS III IV ONLY CERTIFIED TO CAN CSA STD C22 2 NO 247 SAFETY SENSORS REQUIRED CONFORMS TO UL STD 325 Installation Guide for MA...

Страница 2: ...t lors de l ouverture et de la fermeture la barri re doit tre install e dans un endroit o la barri re et les structures avoisinantes sont suffisamment loign es l une de l autre Les barriers battantes...

Страница 3: ...s un capteur de contact doit tre situ o il existe un risque de coincement ou d obstruction comme sur le bord d ouverture sur le bord de fermeture et sur les poteaux mont s sur l int rieur ou l ext rie...

Страница 4: ...etest the gate operator properly can increase the risk of injury or death 4 V rifiez le fonctionnement de l ouvre barri re une fois par mois Le sens de la course DOIT s inverser lorsque la barri re en...

Страница 5: ...ONLY ul 325 model classifications A Inherent entrapment protection system B1 Provision for connection of a non contact sensor photoelectric sensor or the equivalent B2 Provision for connection of a c...

Страница 6: ...stalled where entrapment or pinch point exist A minimum of TWO entrapment protection sensors MUST be installed ONE in EACH direction of gate travel or operator will NOT function Physical Stops Install...

Страница 7: ...ssing through the openings anywhere in the gate and in that portion of the adjacent fence that the gate covers in the open position all exposed pinch points are eliminated or guarded and guarding is s...

Страница 8: ...325 Class of Operation MAX 1500 PRO 2200 PRO Class I II III IV MAX F18 PRO Class III IV ONLY Gate Type Vehicular Slide Gate Max Gate Length MAX 1500 PRO 25ft MAX 2200 PRO MAX F18 PRO 50ft Max Gate Wei...

Страница 9: ...round to avoid flooding Concrete Depth Note The heavier the gate the deeper the concrete pad should be At least two feet recommended for heavier gate Secure gate operator to concrete pad with four 4 1...

Страница 10: ...or is NOT parallel to gate Chain is NOT parallel to gate DO NOT mount chain bracket too high on gate NO NO YES YES YES YES Drive Gear NOTE The chain should sag no more than one 1 inch per 10 feet of t...

Страница 11: ...75 7 5 7 5 6 75 Cover 1 5 4 5 6 5 8 625 12 75 Conduit Area Outside Property Inside Property Input Power Physical Stop Conduit Run Operator MUST be level Concrete Pad Check local building codes in your...

Страница 12: ...heel Approx 1 5 Pulley Wheel Safety Cover Gate YES YES Modify Cover for Rear Mounting Position 16 5 Cut out cover between new hole and existing chain exit slot Make sure cuts are plumb with existing c...

Страница 13: ...SLIDER AC IN FUSE 7 Amp POWER On Off www Max US com MAX Toroid 15 Amp Select Input Voltage 115VAC or 230VAC 1 1 5 V MAX Toroid Box DANGER HIGH VOLTAGE Additional Gang Box 2 ac input power Choose eithe...

Страница 14: ...n ing pro te ction L I M I T S E N S O R E 1 2 Re pla ce Bat ter y ON OF F Bat ter y TES T Bat ter y Bat ter y IN Err or F Bat ter y Mo dul e THREE DO NOT 1 2 3 OPEN RIGHT OPEN LEFT MAX 1500 PRO MAX 2...

Страница 15: ...TAMPER NO COM CLS ONLY 10K OPEN CLS 10K 12VDC OUT NO COM NC LEFT RIGHT OFF 2 5 sec 1 5 sec UL SENSOR N C UL SENSOR 10K entrapment protection wiring 5 Entrapment Protection Device Options and Locations...

Страница 16: ...S NC GND 12VDC OUT GND CLS ONLY 10K OPEN CLS 10K 12VDC OUT UL SENSOR N C UL SENSOR 10K P NSOR N P NSOR P SOR P SOR SOR SOR OR OR OR O N C N N R R R R R R O N C N N N N R R R R O N C N N N N N R R R O...

Страница 17: ...TS CLOSE TIMER MAGLOCK DELAY JOG BATTERY TEST INPUT ERROR BATTERY IN USE REPLACE BATTERY LEAVE CLOSED LEAVE OPEN OPEN 1 TIME BATTERY VOLTAGE E F 1 2 RESET MANUAL RELEASE ID PLUG LINK OK MODULE PORT MO...

Страница 18: ...ter clockwise to reduce gate sensitivity while testing ERD until desired results is attained LED remains OFF for all but position 1 IMPORTANT When satisfied with ERD adjustment cycle the gate 3 or 4 t...

Страница 19: ...Rack SAFETY CENTER EXIT In Ground Loops loops loop detectors 9 matrix III settings 10 Maglock Delay Set to OFF Close Timer 1st click clockwise Knob at MIN 8 Plug In Loop Detectors NOTE DO NOT HIGH NO...

Страница 20: ...ly release slide gate Safety Open Device Dry Contact N O N O Telephone Entry Dry Contact N O Normal Opening Devices Dry Contact EXIT PWR ALARM POWER SOLAR IN BATTERY INPUT OPENING CLOSING CLOSING OPEN...

Страница 21: ...ITION INPUTS SLIDER LIMIT SWING LIMIT OPEN ONLY NC OPEN ONLY 10K CLS ONLY NC OPEN CLS NC GND 12VDC OUT GND GND GND GND GND GND JOG RIGHT JOG LEFT TAMPER IN TAMPER NO GATE DISABLE MANUAL RELEASE KEYPAD...

Страница 22: ...servicing the operator to prevent the switch from accidentally being turned ON during normal operation Plug the wire back in and turn ON the switch only while servicing the operator This can prevent...

Страница 23: ...E TIMER MAGLOCK DELAY JOG BATTERY TEST INPUT ERROR BATTERY BATTERY IN USE REPLACE BATTERY LEAVE CLOSED LEAVE OPEN OPEN 1 TIME BATTERY VOLTAGE E 2 1 F RESET MANUAL RELEASE ID PLUG LINK OK MODULE PORT M...

Страница 24: ...proper authorities BEFORE dropping the chain IMPROPER Dropping of Chain Vandalize Manual Disconnect switch is NOT turned ON When the chain is improperly dropped Vandalized the OPERATOR ALARM and GATE...

Страница 25: ...E PORT MOTOR POSITION INPUTS SLIDER LIMIT SWING LIMIT GND OPEN ONLY NC OPEN ONLY 10K PHOTO CLS NC OPEN CLS NC GND 12VDC OUT GND GND GND GND GND GND JOG RIGHT JOG LEFT TAMPER IN TAMPER NO GATE DISABLE...

Страница 26: ...RELEASE KEYPAD CARD GND GND GND MAX OPEN FIRE DEPT RADIO GND RADIO SIGNAL STRIKE CLOSE COM COM CLS ONLY 10K OPEN CLS 10K 12VDC OUT NO COM NC ERROR 24VDC OUTPUT 12VDC OUTPUT GND GND GND LOOP PWR OFF P...

Страница 27: ...OWER MODE A MODE B EXIT LOOP LOOP LOOP CENTER SAFETY GATE OPEN COM GATE CLOSED MIN MATRIX III SWING SLIDE This page and the next 3 pages can help troubleshoot problems that might occur after installat...

Страница 28: ...TERY IN USE LED is ON and BATTERY BACK UP MODE switch is set to Leave Open then battery may be too low and gate is kept OPEN If BATTERY IN USE LED is ON and BATTERY BACK UP MODE switch is set to OPEN...

Страница 29: ...is ON CLS ONLY 10K LED is ON PHOTO CLS LED is flashing CLS ONLY 10K LED is flashing OPEN ONLY LED is ON OPEN ONLY LED is FLASHING MAX SENSE LED is ON MANUAL RELEASE RESET LED is ON but manual release...

Страница 30: ...flashing Loop fault condition check if SAFETY loop wires are connected into to loop input connector properly Check if SAFETY loops are wired in series Check if loop detector is inserted properly in L...

Страница 31: ...itored 4 5 6 C 1 NO1 NC1 LIGHT ON SENSITIVITY Min Max DARK ON Power Set switch to LIGHT ON 24 to 240 VAC VDC 24 to 240 1 2 N02 C2 3 Sensitivity Adjustment If the photocell does not respond to an obstr...

Страница 32: ...otocell does not respond to an obstruction lower the sensitivity by turning adjustment counter clockwise OK to use 12VDC GND Installation Steps DO NOT connect to NC1 3 OPEN ONLY NC OPEN ONLY 10K OPEN...

Страница 33: ...device MUST be MONITORED by the gate operator Installation Steps 1 Set switch to LIGHT ON 2 Wire 12V power to photocell 3 Wire OPEN ONLY 10K to photocell NC1 Wire GND to photocell C 1 4 Align photocel...

Страница 34: ...GND OPEN ONLY NC OPEN ONLY 10K PHOTO CLS NC OPEN CLS NC GND 12VDC OUT GND GND GND GND GND GND JOG RIGHT JOG LEFT TAMPER IN TAMPER NO GATE DISABLE MANUAL RELEASE KEYPAD CARD GND GND GND MAX OPEN FIRE D...

Страница 35: ...own the desired channel assignment switch until all four channel LEDs activate and the system status LED begins flashing rapidly then release the switch On the transmitter hold down the connection swi...

Страница 36: ...tion device MUST be MONITORED by the gate operator Installation Steps 1 Set DIP switches 2 Remove jumper JP 5 3 Insert jumper on 4W JP 6 4 Wire 12V power to photocell VRX 5 Wire DSP board PHOTO CLS NC...

Страница 37: ...protection device MUST be MONITORED by the gate operator Installation Steps 1 Set DIP switches on receiver 2 Install jumper on receiver 3 Wire Matrix III 12VDC OUT power to receiver 4 Wire PHOTO CLS...

Страница 38: ...nd to an obstruction lower the sensitivity by turning adjustment counter clockwise Transmitter TX Secondary Matrix III Receiver RX Normally Closed PHOTO CLS NC Common GND Green LED Green LED NOComNC J...

Страница 39: ...CK CS1 C1 BS1 BS2 NO3 C3 ATEST Com CS2 C2 C Channel 1 2 transmitters MUST be programmed by RBAND receiver See below or Miller Edge Wireless RBAND instruction sheet to program transmitters to receiver...

Страница 40: ...NO NC Power NC Jog Left Jog Right External Alarm Reset Button Dry Contact Security Device PRESS to RESET ID Plug Specific for operator type REQUIRED Maglock Solenoid Lock Motion Sensor External Jog L...

Страница 41: ...UTS CLOSE TIMER MAGLOCK DELAY JOG ACE ERY LEAVE CLOSED LEAVE OPEN OPEN 1 TIME LINK OK MOTOR POSITION INPUTS SLIDER LIMIT SWING LIMIT GND OPEN ONLY NC OPEN ONLY 10K PHOTO CLS NC OPEN CLS NC GND 12VDC O...

Страница 42: ...Regulator 24V 10A Morning Star Handle AGM Battery Absorbant Glass Material 24V 35A Hr 2 x 12V Batteries YUASA SOLAR PACK Max Solar Pack Available for ALL SLIDE OPERATORS PRO SERIES UL325 Compliant UL...

Страница 43: ...RROR 24VDC OUTPUT 12VDC OUTPUT GND GND GND LOOP LOOP PWR LOOP CENTER SAFETY OFF SINGLE OPEN ON OFF BATTERY CLOSE DUAL ON ANTI TAILGATE PUSH OPEN PULL OPEN GATE OFF 1 2 3 4 5 6 7 8 9 10 OFF 1 2 3 4 5 6...

Страница 44: ...ent Loop Fault PW R LED Flashing Previous Loop Fault EDI Tel 480 968 6407 DEF LE CTO MET ER SENS RESET POWER DETECT EDI SENS LMA1800 LP OPTIONS 1 2 3 4 5 6 7 8 O N ON 1 2 3 4 5 6 7 8 5 Optim um Sen s...

Страница 45: ...ATER THAN 1000 LBS LESS THAN MAX WEIGHT SWING PRO OPERATORS 33Ah 33Ah 50Ah 33Ah 50Ah 50Ah 92 97 90 59 Select proper solar panel and battery size 1 33Ah 33Ah batteries 50Ah 33Ah 50Ah 50Ah batteries bat...

Страница 46: ...NOTES 38 UL 325 2018 Standard MAX 1500 PRO 2200 PRO F18 PRO Matrix III Install Version 7d...

Страница 47: ...NOTES 39 UL 325 2018 Standard MAX 1500 PRO 2200 PRO F18 PRO Matrix III Install Version 7d...

Страница 48: ...ETY SENSORS REQUIRED CONFORMS TO UL STD 325 MAX 1500 PRO 2200 PRO UL CLASS I II III IV MAX F18 PRO UL CLASS III IV ONLY CERTIFIED TO CAN CSA STD C22 2 NO 247 Maximum Controls LLC 10530 Lawson River Av...