7–1
TROUBLESHOOTING
www.maxcessintl.com
MAGPOWR DLCA
MI 850A348 1 E
Fault description
Probable cause
Solution
Reference
Er 10 at power-up
Sensor White (S+) or
Black (S-) wire
disconnected
Check sensor wiring.
Figure 2. DLCA wiring
Er 11 at powr-up
Sensor Red (P+) wire
disconnected
Check sensor wiring.
Figure 2. DLCA wiring
Er 12 at power-up
Sensor Green (P-) wire
disconnected
Check sensor wiring.
Figure 2. DLCA wiring
Er 13 at power-up
Sensor Failure or other
mis-wiring error
Example: Green and
White wire swapped, etc.
Check sensor wiring.
Figure 2. DLCA wiring
Display not lighted
No power
Check power wiring
Figure 2. DLCA wiring
Fuse blown
Check fuse in DLCA.
Fuse ratings in
Specifications; p. 8-1
Fuse Replacement; p. 6-1
Analog outputs not
changing with the
displayed tension
Analog output shorted
Check Analog output
wiring.
Figure 2. DLCA wiring
Analog output range
misconfigured
Check parameters P.06
through P0.11.
––
Analog output not
calibrated
Perform output
calibration CAL0.
––
Alarm output not
working
Alarm not wired
correctly
Check alarm wiring.
Figure 2, DLCA wiring
Alarm not configured
correctly
Check parameters P.13
through P.18
––
Remote zero not
zeroing tension
Remote zero input not
wired correctly
Check remote zero
wiring.
2, DLCA wiring
Digital input threshold
level not set correctly
Check parameter P.12
––
Displayed tension is
reading negative
value with increasing
tension.
Tension polarity is
wrong
Check parameter P.20.
––
Cannot change
parameters or
perform calibration.
Password protection is
active
Enter the password into
P.00 to unlock the DLCA.
The master unlock
password is 6195.
––