i-MAX 

Industrial inverter air/water heat pump with axial fans 

17 

outlet water sensor exceeds 

r02+r06 

in heating mode or 

r03+r06 

in cooling mode and in shut off condition (the default value is 

r06=2,0°C). The heating cable placed on the basement of the appliance turns on when the outdoor air temperature decreases 

below 3°C and the unit starts the defrosting cycle (or if 

r19

=0 even if the unit is not in defrosting cycle, or in stand-by mode). It will 

be deactivated if the outdoor temperature exceeds 5°C or the last defrosting cycle is concluded after more than 

r19

  minutes 

(default 10 minutes) (with 

r19

≠0).

 

If you want to produce gelid water, it is necessary to modify the actions of antifreeze resistances, as well as the set of activation of 

the antifreeze alarm (

A08 = 

4°C by default) and its hysteresis (

A09 = 

3.0°C by default). 

7.9

 

Remote ON/OFF 

The ON/OFF function is already enabled by default. Remove the bridge of the terminal block then the unit will be placed in stand-

by mode (in such status the display of the on-board unit controller will show the "

E00

" code). When the contact is closed, the 

appliance exits from standby mode and the circulation pump will be activated for 2 minutes. 

To change this function, enter at the parameters PRG

PSS

PRG

(introduce the maintainer password)

PRG

PAr

PRG

CnF 

See paragraph 11.2. 

Note:

 In the case of a remote switch Off during the defrost cycle, the unit will terminate this process before stopping completely 

the cooperation. 

Parameter  Unit 

Value 

Description 

Terminals 

Note 

H46 

Num  2 (default)  Remote On/Off digital input 

ID2-ID2 

Non-voltage digital input 

If the domestic hot water is enabled and the parameter “

H10” 

is configured as below: 

 

If 

H10 =

 

1/3/5

,  the remote on-off function has no any effect on sanitary operation;  it only disenables the heating and 

cooling on the plant system side (in such case the "

SAN

" item will be shown on the display of the on-board unit controller). 

 

If H10 = 2/4/6

, the remote on-off function disenables the production of domestic hot water and the operation of the heat 

pump in heating and cooling mode on plant circuit side. 

8

 

ACTIVABLE SIGNALIZATIONS FOR 0466, 0475 AND 0485 SIZES 

As for the sizes indicated above, on the 

DO3 – DO3N 

terminals (Parameter 

H81

), it’s possible to configure a 230Vac signal output 

voltage by setting the following user parameters introducing the installer password in the control panel located on the front panel. 

Value 

Description 

21 

Signalization of defrosting period

 

 

The digital output is activated at the beginning of defrosting cycle, once the Pa d06 time period has terminated. 

 

The digital output is deactivated at the end of defrosting cycle, once the Pa d07 time period is terminated. 

24 

Signalization of heat pump alarm 

31 

Signalization of plant season. 

 

The output is active in COOLING operation 

 

The output is not active in heating operation 

 

The output is not active when the unit s OFF. 

During the DHW production and defrosting cycle, the output keeps the settings of the provenance season. 

47 

Signalization of appliance lockout 

9

 

ACTIVABLE LOGIC FUNCTIONS WITH GI- MODULE FOR PLANT MANAGEMENT (optional) 

The following functions can be activated by the on-board controller which is located on the front panel of the unit. 

9.1

 

DEFROSTING CYCLE SIGNALIZATION 

It is possible to configure a digital output for the signalization of the beginning of defrosting cycle. 

To enable this function, you should enter at  the page of parameters PRG

PSS

  PRG

(enter the maintainer password)

 

PRG

PAr

 PRG

CnF.

 

See paragraph 11.2.

 

Parameter  Unit  Value 

Description 

Terminals 

Notes 

H86 

num 

21 

Undervoltage output for defrost 

cycle warning 

DO1E(phase) 

DO1E N(neutral) 

Under-voltage output 230V ac, 50Hz, 5A resistive, 1A inductive. 

Should be connected to the relay coil in order to get a free contact.

 

9.2

 

PLANT SEASON SIGNALIZATION 

It is possible to configure a digital output for the signalization of the plant season mode of the unit. 

The output is 

ON

 during summer mode operation, however is 

OFF

 when the unit is not operating or in winter mode. 

The output keeps the configuration of last season operating mode during the DHW production or defrosting cycle. 

To enable this function, you should enter at the page of the parameters PRG

PSS

PRG

(introduce the maintainer 

password)

PRG

PAr

PRG

CnF.

 

See paragraph 11.2.

 

Parameter  Unit  Value 

Description 

Terminals 

Notes 

H87 

num 

31 

Under-voltage output for plant 

season signalization

 

DO2E(phase) 

DO2E N(neutral) 

Under voltage output single phase 230Vac, 50Hz, 2A (AC1), 

for connection to the relay coil for obtaining a free contact.

 

Содержание i-MAX 0466

Страница 1: ......

Страница 2: ...e Series Serie Serie S rie i MAX SSL 0466 06115 Industrial inverter air water heat pump with axial fans Possible wasted electrical or electronic devices products should not be located together with no...

Страница 3: ...12 7 2 3 OPERATION WITH ACTIVE ELECTRIC HEATER 12 7 2 4 CONTINUOUS OPERATION 12 7 2 5 LINEAR REGULATION OF THE CIRCULATOR DOUBLE TWater 12 7 2 6 AIR PURGING OF THE SYSTEM 13 7 3 COMPRESSORS CONTROL 1...

Страница 4: ...9 10 6 AUXILIARY SYSTEMS OFFSET MANAGEMENT 26 9 11 DOUBLE SET POINT MANAGEMENT 26 9 11 1 SETTINGS 26 9 11 2 ADJUSTABLE SETPOINTS 27 9 11 3 COMMUTATIONS 27 9 12 SECONDARY CIRCULATOR MANAGEMENT RELAUNC...

Страница 5: ...personnel and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectl...

Страница 6: ...nt under voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a...

Страница 7: ...djust the summer set point value UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In t...

Страница 8: ...cond setpoint in the summer C 18 0 Coo H03 He2 Second setpoint in the winter C 35 0 H02 Hea 5 2 2 Password menu Enter the password for the desired access level The controller will automatically open t...

Страница 9: ...sequence 6 Once the update is completed the board returns to normal operation and the appliance is ready to start operation 7 Turn off the unit by placing the main switch in OFF position 8 Remove the...

Страница 10: ...tion 24 Alarm signalization 31 Plant season signalization 47 Lockout signalization DO3 phase DO3N neutral Under voltage output 230Vac 50Hz 2A AC1 For the sizes of 0466 0475 and 0485 Wherever the GI op...

Страница 11: ...n Continuous operation The circulator will immediately switch off if You have a pump circulator locking alarm including the manual reset flow switch alarm The unit is in stand by mode or when it s swi...

Страница 12: ...it will be activated periodically for a duration given by the parameter P17 in seconds after a counting time set by the parameter P16 in minutes activated when the thermoregulation is fulfilled and th...

Страница 13: ...the expansion valve the reversing valve is commutated in the opposite direction to that required by the actual mode for 5 seconds in order to allow the equilibrium of the optimal pressures for startin...

Страница 14: ...15 b05 C 0 5 0 5 0 5 0 5 0 5 0 5 b25 C 2 5 2 5 2 5 2 0 2 0 2 0 7 3 5 INVERTER COMPRESSORS CONTROL IN HEATING MODE The compressors are active in heating mode if the heat pump is enabled H09 Configurati...

Страница 15: ...ee the paragraph related to auxiliary electric heaters 7 5 HEAT DISSIPATION FAN MOTOR CONTROL The control of the dissipation is as a function of the condensing pressure in chiller mode operation where...

Страница 16: ...rtant decreasing of the thermal efficiency of the unit it can lead also to the risk of damaging the unit itself The adjustable parameter d01 enables the defrost operation 1 enabled defrosting Please s...

Страница 17: ...ated above on the DO3 DO3N terminals Parameter H81 it s possible to configure a 230Vac signal output voltage by setting the following user parameters introducing the installer password in the control...

Страница 18: ...water production DHW 3 The function is active in heating mode The remote switching on off function doesn t deactivate the domestic hot water production DHW 4 The function is active in heating mode Th...

Страница 19: ...hole system Note It is possible to invert the polarity of the digital input to do that please contact our technical office 9 5 3 HEATING MODE ON DOMESTIC HOT WATER TANK If the following setting H83 1...

Страница 20: ...eater r24 Num 1 o 3 Type of utilization of the electric heaters 9 8 2 AUXILIARY ELECTRIC HEATER OF THE PLANT IN DEFROST CYCLE During defrost cycle see Paragraph 7 6 by setting r21 1 in addition to r10...

Страница 21: ...h DHW and plant sides no priority intervention for electric heaters Settings of the parameter r32 when the boiler is being installed r32 0 boiler without a circulating pump with thermoregulation to be...

Страница 22: ...his remote sensor is less than the setpoint Hea the boiler will be activated and then will be deactivated when the measured temperature by the remote sensor is greater than setpoint Hea The boiler wil...

Страница 23: ...0 1 0 1 2 2 3 5 6 0 1 7 1 Auxiliary electric heater of sanitary 2 After r15 minutes boiler HEAT SAN SANITARY 0 1 1 Set up of minutes 2 3 2 3 8 1 Boiler 2 After r15 minutes auxiliary electric heater o...

Страница 24: ...ter r12 minutes later heat pump HEAT HEAT SAN HEAT 1 0 1 2 Set up of minutes 1 3 1 3 3 1 Boiler 2 After r12 minutes heat pump 3 After r12 minutes later auxiliary electric heater of plant HEAT HEAT SAN...

Страница 25: ...AN HEAT 0 1 0 1 2 Set up of minutes 1 3 4 6 0 2 8 1 Auxiliary electric heater of plant HEAT HEAT SAN HEAT 0 1 0 1 2 Set up of minutes 0 2 5 1 3 9 1 Boiler HEAT SAN SANITARY 0 1 0 1 2 Set up of minutes...

Страница 26: ...to the open state the auxiliary electric heater of the plant will turned off It works as indicated in the TABLE 1 2 3 and 4 3 COOL SAN SANITARY Not available It works as indicated in the TABLE 5 4 COO...

Страница 27: ...ng pump for the plant circuit utilizations An ambient thermostat must be appropriately configured NC state connected on the terminals DI3E DI3E by the installer Thermostat contact normally open Active...

Страница 28: ...eeze alarm activation setting C 2 127 127 INSTALLER A09 Antifreeze alarm hysteresis C 3 0 0 0 25 5 INSTALLER A16 Low pressure set in cooling operation Bar Based on the model 4 0 80 0 INSTALLER A27 Low...

Страница 29: ...periodic mode min 20 0 600 INSTALLER P17 Time of operation of the pump in periodic mode sec 90 0 255 INSTALLER 0 deactivation of periodic mode P18 Enabling of unique pump operation in network 0 0 1 I...

Страница 30: ...activated function 1 enabled function 2 Operation of auxiliary plant side electric only if H83 1 r16 DHW auxiliary heater heat pump activation delay min 15 0 255 INSTALLER r19 Activation time of drain...

Страница 31: ...matically reset for the first 2 times and goes off after 5 seconds If the alarm occurs more than 3 times per hour the manual reset of the alarm is required The alarm is not active for 10 seconds after...

Страница 32: ...pump E041 Misfitted temperature alarm Heat pump E101 Communication Timeout GI module error Heat pump E611 Inlet water temp sensor error Heat pump E682 Plant water plant temperature remote sensor if e...

Страница 33: ...1 E913 Automatic All compressors are off for at least 180 sec E921 E923 Automatic All compressors are off for at least 180 sec E931 E933 Automatic All compressors are off for at least 180 sec E941 E94...

Страница 34: ...i MAX Industrial inverter air water heat pump with axial fans 34...

Страница 35: ......

Страница 36: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: