TABLE 4. SUBSTITUTION OPERATION
N°
ORDER OF INTERVENTION OF
HEATING ELEMENTS
(when the set-
point is not achieved)
MODE
OPERATION
r10 r15
r12
r16
r23
r24
1
1)
Boiler
2) After r12 minutes,
auxiliary
electric heater of plant
HEAT /
HEAT+SAN
HEAT
0/1 0/1/2 Set up of
minutes
/
4/6
1/3
2 1)
Auxiliary electric heater of plant
2) After r12 minutes,
boiler
HEAT /
HEAT+SAN
HEAT
0/1 0/1/2 Set up of
minutes
/
1/3
1/3
3
1)
Boiler
2) After r12 minutes,
Auxiliary
electric heater of sanitary
HEAT+SAN
SANITARY
0/1 0/1/2
/
Set up of
minutes
5/6
2/3
4
1)
Auxiliary electric heater of
sanitary
2) After r12 minutes,
boiler
HEAT+SAN
SANITARY
0/1 0/1/2
/
Set up of
minutes
2/3
2/3
5
1)
Boiler
2) After r12 minutes,
auxiliary
electric heater of plant/sanitary
HEAT /
HEAT+SAN
IN HEAT OR IN
SANITARY
0/1 0/1/2 Set up of
minutes
Set up of
minutes
6
3
6
1)
Auxiliary electric heater of
plant/sanitary
2) After r12 minutes,
boiler
HEAT /
HEAT+SAN
IN HEAT OR IN
SANITARY
0/1 0/1/2 Set up of
minutes
Set up of
minutes
3
3
7 1)
Boiler
HEAT /
HEAT+SAN
HEAT
0/1 0/1/2 Set up of
minutes
/
1/3/4/6 0/2
8 1)
Auxiliary electric heater of plant
HEAT /
HEAT+SAN
HEAT
0/1 0/1/2 Set up of
minutes
/
0/2/5 1/3
9 1)
Boiler
HEAT+SAN
SANITARY
0/1 0/1/2
/
Set up of
minutes 2/3/5/6 0/1
10 1)
Auxiliary electric heater of
sanitary
HEAT+SAN
SANITARY
0/1 0/1/2
/
Set up of
minutes
0/1/4 2/3
11 1)
Boiler
HEAT /
HEAT+SAN
IN HEAT OR IN
SANITARY
0/1 0/1/2 Set up of
minutes
Set up of
minutes
3/6
0
12 1)
Auxiliary electric heater of
plant/sanitary
HEAT /
HEAT+SAN
IN HEAT OR IN
SANITARY
0/1 0/1/2 Set up of
minutes
Set up of
minutes
0
3
The below Table (5) shows the parameter to be set in order to enable the auxiliary electric heaters in "Summer and sanitary"
mode (in this case, the only available auxiliary electric heater is the one of sanitary side and the subdivision between
normal/joint/substitution operation is not valid).
TABLE 5. OPERATION IN COOL+SAN MODE (SANITARY MODE IS OPERATING)
N°
ORDER OF INTERVENTION OF AUXILIARY
ELECTRIC HEATERS
- when the set point is not achieved
after r16 minutes from the compressor
startup or
- when the set-point is not achieved and
the unit is in alarm condition.
MODE
OPERATION r10 r15 r12
r16
r23
r24
1 1)
Auxiliary electric heater of sanitary
COOL+SAN SANITARY 0/1 1
/
Set up of
minutes
0/1/2/3/4/5/6 2/3