i-MAX 

Industrial inverter air/water heat pump with axial fans 

25 

TABLE 4. SUBSTITUTION OPERATION

 

N° 

ORDER OF INTERVENTION  OF 

HEATING ELEMENTS 

(when the set-

point is not achieved)

 

MODE 

OPERATION 

r10  r15 

r12 

r16 

r23 

r24 

1) 

Boiler

 

2) After r12 minutes, 

auxiliary 

electric heater of plant

 

HEAT / 

HEAT+SAN 

HEAT 

0/1  0/1/2  Set up of 

minutes 

4/6 

1/3 

2  1) 

Auxiliary electric heater of plant

 

2) After r12 minutes, 

boiler

 

HEAT / 

HEAT+SAN 

HEAT 

0/1  0/1/2  Set up of 

minutes 

1/3 

1/3 

1) 

Boiler

 

2) After r12 minutes, 

Auxiliary 

electric heater of sanitary

 

HEAT+SAN 

SANITARY 

0/1  0/1/2 

Set up of 

minutes 

5/6 

2/3 

1) 

Auxiliary electric heater of 

sanitary

 

2) After r12 minutes, 

boiler

 

HEAT+SAN 

SANITARY 

0/1  0/1/2 

Set up of 

minutes 

2/3 

2/3 

1) 

Boiler

 

2) After r12 minutes, 

auxiliary 

electric heater of plant/sanitary

 

HEAT / 

HEAT+SAN 

IN HEAT OR IN 

SANITARY 

0/1  0/1/2  Set up of 

minutes 

Set up of 

minutes 

1) 

Auxiliary electric heater of 

plant/sanitary

 

2) After r12 minutes, 

boiler

 

HEAT / 

HEAT+SAN 

IN HEAT OR IN 

SANITARY 

0/1  0/1/2  Set up of 

minutes 

Set up of 

minutes 

7  1)

 Boiler

 

HEAT / 

HEAT+SAN 

HEAT 

0/1  0/1/2  Set up of 

minutes 

1/3/4/6  0/2 

8  1) 

Auxiliary electric heater of plant

 

HEAT / 

HEAT+SAN 

HEAT 

0/1  0/1/2  Set up of 

minutes 

0/2/5  1/3 

9  1) 

Boiler

 

HEAT+SAN 

SANITARY 

0/1  0/1/2 

Set up of 

minutes  2/3/5/6  0/1 

10  1) 

Auxiliary electric heater of 

sanitary

 

HEAT+SAN 

SANITARY 

0/1  0/1/2 

Set up of 

minutes 

0/1/4  2/3 

11  1) 

Boiler

 

HEAT / 

HEAT+SAN 

IN HEAT OR IN 

SANITARY 

0/1  0/1/2  Set up of 

minutes 

Set up of 

minutes 

3/6 

12  1) 

Auxiliary electric heater of 

plant/sanitary

 

HEAT / 

HEAT+SAN 

IN HEAT OR IN 

SANITARY 

0/1  0/1/2  Set up of 

minutes 

Set up of 

minutes 

The below Table (5) shows the parameter to be set in order to enable the auxiliary electric heaters in "Summer and sanitary" 

mode (in this case, the only available auxiliary electric heater is the one of sanitary side and the subdivision between 

normal/joint/substitution operation is not valid). 

TABLE 5. OPERATION IN COOL+SAN MODE (SANITARY MODE IS OPERATING) 

N° 

ORDER OF INTERVENTION OF AUXILIARY 

ELECTRIC HEATERS 

-  when the set point is not achieved 

after r16 minutes from the compressor 

startup or 

- when the set-point is not achieved and 

the unit is in alarm condition. 

MODE 

OPERATION  r10  r15  r12 

r16 

r23 

r24 

1  1) 

Auxiliary electric heater of sanitary

 

COOL+SAN  SANITARY  0/1  1 

Set up of 

minutes 

0/1/2/3/4/5/6  2/3 

 

Содержание i-MAX 0466

Страница 1: ......

Страница 2: ...e Series Serie Serie S rie i MAX SSL 0466 06115 Industrial inverter air water heat pump with axial fans Possible wasted electrical or electronic devices products should not be located together with no...

Страница 3: ...12 7 2 3 OPERATION WITH ACTIVE ELECTRIC HEATER 12 7 2 4 CONTINUOUS OPERATION 12 7 2 5 LINEAR REGULATION OF THE CIRCULATOR DOUBLE TWater 12 7 2 6 AIR PURGING OF THE SYSTEM 13 7 3 COMPRESSORS CONTROL 1...

Страница 4: ...9 10 6 AUXILIARY SYSTEMS OFFSET MANAGEMENT 26 9 11 DOUBLE SET POINT MANAGEMENT 26 9 11 1 SETTINGS 26 9 11 2 ADJUSTABLE SETPOINTS 27 9 11 3 COMMUTATIONS 27 9 12 SECONDARY CIRCULATOR MANAGEMENT RELAUNC...

Страница 5: ...personnel and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectl...

Страница 6: ...nt under voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a...

Страница 7: ...djust the summer set point value UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In t...

Страница 8: ...cond setpoint in the summer C 18 0 Coo H03 He2 Second setpoint in the winter C 35 0 H02 Hea 5 2 2 Password menu Enter the password for the desired access level The controller will automatically open t...

Страница 9: ...sequence 6 Once the update is completed the board returns to normal operation and the appliance is ready to start operation 7 Turn off the unit by placing the main switch in OFF position 8 Remove the...

Страница 10: ...tion 24 Alarm signalization 31 Plant season signalization 47 Lockout signalization DO3 phase DO3N neutral Under voltage output 230Vac 50Hz 2A AC1 For the sizes of 0466 0475 and 0485 Wherever the GI op...

Страница 11: ...n Continuous operation The circulator will immediately switch off if You have a pump circulator locking alarm including the manual reset flow switch alarm The unit is in stand by mode or when it s swi...

Страница 12: ...it will be activated periodically for a duration given by the parameter P17 in seconds after a counting time set by the parameter P16 in minutes activated when the thermoregulation is fulfilled and th...

Страница 13: ...the expansion valve the reversing valve is commutated in the opposite direction to that required by the actual mode for 5 seconds in order to allow the equilibrium of the optimal pressures for startin...

Страница 14: ...15 b05 C 0 5 0 5 0 5 0 5 0 5 0 5 b25 C 2 5 2 5 2 5 2 0 2 0 2 0 7 3 5 INVERTER COMPRESSORS CONTROL IN HEATING MODE The compressors are active in heating mode if the heat pump is enabled H09 Configurati...

Страница 15: ...ee the paragraph related to auxiliary electric heaters 7 5 HEAT DISSIPATION FAN MOTOR CONTROL The control of the dissipation is as a function of the condensing pressure in chiller mode operation where...

Страница 16: ...rtant decreasing of the thermal efficiency of the unit it can lead also to the risk of damaging the unit itself The adjustable parameter d01 enables the defrost operation 1 enabled defrosting Please s...

Страница 17: ...ated above on the DO3 DO3N terminals Parameter H81 it s possible to configure a 230Vac signal output voltage by setting the following user parameters introducing the installer password in the control...

Страница 18: ...water production DHW 3 The function is active in heating mode The remote switching on off function doesn t deactivate the domestic hot water production DHW 4 The function is active in heating mode Th...

Страница 19: ...hole system Note It is possible to invert the polarity of the digital input to do that please contact our technical office 9 5 3 HEATING MODE ON DOMESTIC HOT WATER TANK If the following setting H83 1...

Страница 20: ...eater r24 Num 1 o 3 Type of utilization of the electric heaters 9 8 2 AUXILIARY ELECTRIC HEATER OF THE PLANT IN DEFROST CYCLE During defrost cycle see Paragraph 7 6 by setting r21 1 in addition to r10...

Страница 21: ...h DHW and plant sides no priority intervention for electric heaters Settings of the parameter r32 when the boiler is being installed r32 0 boiler without a circulating pump with thermoregulation to be...

Страница 22: ...his remote sensor is less than the setpoint Hea the boiler will be activated and then will be deactivated when the measured temperature by the remote sensor is greater than setpoint Hea The boiler wil...

Страница 23: ...0 1 0 1 2 2 3 5 6 0 1 7 1 Auxiliary electric heater of sanitary 2 After r15 minutes boiler HEAT SAN SANITARY 0 1 1 Set up of minutes 2 3 2 3 8 1 Boiler 2 After r15 minutes auxiliary electric heater o...

Страница 24: ...ter r12 minutes later heat pump HEAT HEAT SAN HEAT 1 0 1 2 Set up of minutes 1 3 1 3 3 1 Boiler 2 After r12 minutes heat pump 3 After r12 minutes later auxiliary electric heater of plant HEAT HEAT SAN...

Страница 25: ...AN HEAT 0 1 0 1 2 Set up of minutes 1 3 4 6 0 2 8 1 Auxiliary electric heater of plant HEAT HEAT SAN HEAT 0 1 0 1 2 Set up of minutes 0 2 5 1 3 9 1 Boiler HEAT SAN SANITARY 0 1 0 1 2 Set up of minutes...

Страница 26: ...to the open state the auxiliary electric heater of the plant will turned off It works as indicated in the TABLE 1 2 3 and 4 3 COOL SAN SANITARY Not available It works as indicated in the TABLE 5 4 COO...

Страница 27: ...ng pump for the plant circuit utilizations An ambient thermostat must be appropriately configured NC state connected on the terminals DI3E DI3E by the installer Thermostat contact normally open Active...

Страница 28: ...eeze alarm activation setting C 2 127 127 INSTALLER A09 Antifreeze alarm hysteresis C 3 0 0 0 25 5 INSTALLER A16 Low pressure set in cooling operation Bar Based on the model 4 0 80 0 INSTALLER A27 Low...

Страница 29: ...periodic mode min 20 0 600 INSTALLER P17 Time of operation of the pump in periodic mode sec 90 0 255 INSTALLER 0 deactivation of periodic mode P18 Enabling of unique pump operation in network 0 0 1 I...

Страница 30: ...activated function 1 enabled function 2 Operation of auxiliary plant side electric only if H83 1 r16 DHW auxiliary heater heat pump activation delay min 15 0 255 INSTALLER r19 Activation time of drain...

Страница 31: ...matically reset for the first 2 times and goes off after 5 seconds If the alarm occurs more than 3 times per hour the manual reset of the alarm is required The alarm is not active for 10 seconds after...

Страница 32: ...pump E041 Misfitted temperature alarm Heat pump E101 Communication Timeout GI module error Heat pump E611 Inlet water temp sensor error Heat pump E682 Plant water plant temperature remote sensor if e...

Страница 33: ...1 E913 Automatic All compressors are off for at least 180 sec E921 E923 Automatic All compressors are off for at least 180 sec E931 E933 Automatic All compressors are off for at least 180 sec E941 E94...

Страница 34: ...i MAX Industrial inverter air water heat pump with axial fans 34...

Страница 35: ......

Страница 36: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: