ALARMS MANAGEMENT 

When getting access to 

ERR

 alarm’s menu, you can display the active alarms collected in two directories 

ALL C1

 for circuit 1 and 

ALL C2

 for circuit 2, under the alarm list. 

13.1

 

E000 – REMOTE ON/OFF 

The E000 code will appear when the unit is controlled from a remote digital input. 

13.2

 

E001 – HIGH PRESSURE 

If the on board pressure transductor detects a pressure higher than 39,5bar, the alarm will be activated. 

In this case the compressor will stop immediately via software. The alarm will reset when the pressure decreases under 33,5bar. 

If the number of alarm interventions in one-hour is equal to 3 times, it will become manual reset. 

13.3

 

E002 – LOW PRESSURE 

If the on board pressure transducer detects a pressure lower than value set from the controller (

A16=5 

bar by default in cooling 

mode, 1.5 bar in heating mode) the alarm will be activated. In this case the compressor will stop immediately. The alarm will reset 

when the pressure goes over a hysteresis of 2.0bar. 

If the alarm occurs more than 3 times per hour, the alarm becomes a manual reset. 

13.4

 

E003 – THERMAL PROTECTION OF FIRST ON/OFF COMPRESSOR IN BOTH CIRCUITS 

When the thermal protection of compressor C3/circuit 1 or of compressor C4/circuit 2 is activated, the alarm will raise. 

13.5

 

E004 – FAN MOTOR ALARM 

When the fan driver is broken, the corresponding alarm will be immediately activated, therefore please check the manual of the 

driver for further information. 

13.6

 

E005 – ANTIFREEZE ALARM 

The alarm will be activated when the outlet water temperature sensor is less than 4°C. It turns off when the temperature becomes 

higher than +7°C. 

13.7

 

E006 – FLOW SWITCH ALARM 

The water side flow switch is already installed inside the unit and must NOT be tampered or bypassed in any way. The flow switch 

is bypassed for 10 seconds from the start-up of the machine. The alarm signalization occurs after 5 seconds of error persistence 

(lack of water flow, air in the circuit, etc.). The alarm is automatically reset for the first 2 times and goes off after 5 seconds. If the 

alarm occurs more than 3 times per hour, the manual reset of the alarm is required. 

The alarm is not active for 10 seconds after activating the circulator. 

13.8

 

[E008] DRIVER LIMITATION 

If the compressor does not achieve the speed to ramp value which is expected within 30 minutes, the alarm becomes active and 

the compressor will stop for its safety. 

If the alarm occurs more than 3 times per hour, the alarm becomes a manual reset. 

13.9

 

[E013] THERMAL PROTECTION OF SECOND ON/OFF COMPRESSOR IN BOTH CIRCUITS 

When the thermal protection of compressor C5/circuit 1 or of compressor C6/circuit 2 is activated, the alarm will raise. 

13.10

 

 [E018] HIGH TEMPERATURE WATER SIDE 

The alarm will be activated when the outlet water temperature sensor becomes higher than 65°C for at least 50 seconds. It turns 

off when the water outlet temperature decreases below 62°C. 

13.11

 

[E016] USAGE PUMP 1 THERMAL PROTECTION 

When the driver of the AC circulator is broken, the corresponding alarm will be immediately activated, see the manual of the 

driver for further information. 

13.12

 

[E641] HIGH PRESSURE ALARM SWITCH (IN SERIES TO THE COMPRESSOR DISCHARGE TEMP. SENSOR)

 

When the built-in pressure switch of circuit 1 or of that of circuit 2 detects a value higher which is than 41,4bar, the alarm will 

raise. In this case the compressors and the fan motors will immediately stop operation by the electromechanical devices and the 

E641

 error code will be shown on the display. The alarm goes off when the pressure decreases below 30bar. After resolving the 

problem, you need to switch off the unit and then to switch on it from the disconnecting switch (please wait at least 1 minute 

between each consecutive shutdown and start-up). 

13.13

 

[E611÷E682] SENSORS’ ALARMS 

The alarm will be activated in the case of short or open circuit of any connected and enabled sensor. 

The alarm will be activated also when the temperature becomes higher than the sensors’ upper limit of 100°C or less than the 

lower limit which is -50°C. 

A configured temperature sensor for DHW production mode does give any alarm if the DHW production mode is not enabled. 

 

Temperature sensor characterization: NTC-

10kΏ a 25°C β3435

 

Содержание i-MAX 0466

Страница 1: ......

Страница 2: ...e Series Serie Serie S rie i MAX SSL 0466 06115 Industrial inverter air water heat pump with axial fans Possible wasted electrical or electronic devices products should not be located together with no...

Страница 3: ...12 7 2 3 OPERATION WITH ACTIVE ELECTRIC HEATER 12 7 2 4 CONTINUOUS OPERATION 12 7 2 5 LINEAR REGULATION OF THE CIRCULATOR DOUBLE TWater 12 7 2 6 AIR PURGING OF THE SYSTEM 13 7 3 COMPRESSORS CONTROL 1...

Страница 4: ...9 10 6 AUXILIARY SYSTEMS OFFSET MANAGEMENT 26 9 11 DOUBLE SET POINT MANAGEMENT 26 9 11 1 SETTINGS 26 9 11 2 ADJUSTABLE SETPOINTS 27 9 11 3 COMMUTATIONS 27 9 12 SECONDARY CIRCULATOR MANAGEMENT RELAUNC...

Страница 5: ...personnel and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectl...

Страница 6: ...nt under voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a...

Страница 7: ...djust the summer set point value UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In t...

Страница 8: ...cond setpoint in the summer C 18 0 Coo H03 He2 Second setpoint in the winter C 35 0 H02 Hea 5 2 2 Password menu Enter the password for the desired access level The controller will automatically open t...

Страница 9: ...sequence 6 Once the update is completed the board returns to normal operation and the appliance is ready to start operation 7 Turn off the unit by placing the main switch in OFF position 8 Remove the...

Страница 10: ...tion 24 Alarm signalization 31 Plant season signalization 47 Lockout signalization DO3 phase DO3N neutral Under voltage output 230Vac 50Hz 2A AC1 For the sizes of 0466 0475 and 0485 Wherever the GI op...

Страница 11: ...n Continuous operation The circulator will immediately switch off if You have a pump circulator locking alarm including the manual reset flow switch alarm The unit is in stand by mode or when it s swi...

Страница 12: ...it will be activated periodically for a duration given by the parameter P17 in seconds after a counting time set by the parameter P16 in minutes activated when the thermoregulation is fulfilled and th...

Страница 13: ...the expansion valve the reversing valve is commutated in the opposite direction to that required by the actual mode for 5 seconds in order to allow the equilibrium of the optimal pressures for startin...

Страница 14: ...15 b05 C 0 5 0 5 0 5 0 5 0 5 0 5 b25 C 2 5 2 5 2 5 2 0 2 0 2 0 7 3 5 INVERTER COMPRESSORS CONTROL IN HEATING MODE The compressors are active in heating mode if the heat pump is enabled H09 Configurati...

Страница 15: ...ee the paragraph related to auxiliary electric heaters 7 5 HEAT DISSIPATION FAN MOTOR CONTROL The control of the dissipation is as a function of the condensing pressure in chiller mode operation where...

Страница 16: ...rtant decreasing of the thermal efficiency of the unit it can lead also to the risk of damaging the unit itself The adjustable parameter d01 enables the defrost operation 1 enabled defrosting Please s...

Страница 17: ...ated above on the DO3 DO3N terminals Parameter H81 it s possible to configure a 230Vac signal output voltage by setting the following user parameters introducing the installer password in the control...

Страница 18: ...water production DHW 3 The function is active in heating mode The remote switching on off function doesn t deactivate the domestic hot water production DHW 4 The function is active in heating mode Th...

Страница 19: ...hole system Note It is possible to invert the polarity of the digital input to do that please contact our technical office 9 5 3 HEATING MODE ON DOMESTIC HOT WATER TANK If the following setting H83 1...

Страница 20: ...eater r24 Num 1 o 3 Type of utilization of the electric heaters 9 8 2 AUXILIARY ELECTRIC HEATER OF THE PLANT IN DEFROST CYCLE During defrost cycle see Paragraph 7 6 by setting r21 1 in addition to r10...

Страница 21: ...h DHW and plant sides no priority intervention for electric heaters Settings of the parameter r32 when the boiler is being installed r32 0 boiler without a circulating pump with thermoregulation to be...

Страница 22: ...his remote sensor is less than the setpoint Hea the boiler will be activated and then will be deactivated when the measured temperature by the remote sensor is greater than setpoint Hea The boiler wil...

Страница 23: ...0 1 0 1 2 2 3 5 6 0 1 7 1 Auxiliary electric heater of sanitary 2 After r15 minutes boiler HEAT SAN SANITARY 0 1 1 Set up of minutes 2 3 2 3 8 1 Boiler 2 After r15 minutes auxiliary electric heater o...

Страница 24: ...ter r12 minutes later heat pump HEAT HEAT SAN HEAT 1 0 1 2 Set up of minutes 1 3 1 3 3 1 Boiler 2 After r12 minutes heat pump 3 After r12 minutes later auxiliary electric heater of plant HEAT HEAT SAN...

Страница 25: ...AN HEAT 0 1 0 1 2 Set up of minutes 1 3 4 6 0 2 8 1 Auxiliary electric heater of plant HEAT HEAT SAN HEAT 0 1 0 1 2 Set up of minutes 0 2 5 1 3 9 1 Boiler HEAT SAN SANITARY 0 1 0 1 2 Set up of minutes...

Страница 26: ...to the open state the auxiliary electric heater of the plant will turned off It works as indicated in the TABLE 1 2 3 and 4 3 COOL SAN SANITARY Not available It works as indicated in the TABLE 5 4 COO...

Страница 27: ...ng pump for the plant circuit utilizations An ambient thermostat must be appropriately configured NC state connected on the terminals DI3E DI3E by the installer Thermostat contact normally open Active...

Страница 28: ...eeze alarm activation setting C 2 127 127 INSTALLER A09 Antifreeze alarm hysteresis C 3 0 0 0 25 5 INSTALLER A16 Low pressure set in cooling operation Bar Based on the model 4 0 80 0 INSTALLER A27 Low...

Страница 29: ...periodic mode min 20 0 600 INSTALLER P17 Time of operation of the pump in periodic mode sec 90 0 255 INSTALLER 0 deactivation of periodic mode P18 Enabling of unique pump operation in network 0 0 1 I...

Страница 30: ...activated function 1 enabled function 2 Operation of auxiliary plant side electric only if H83 1 r16 DHW auxiliary heater heat pump activation delay min 15 0 255 INSTALLER r19 Activation time of drain...

Страница 31: ...matically reset for the first 2 times and goes off after 5 seconds If the alarm occurs more than 3 times per hour the manual reset of the alarm is required The alarm is not active for 10 seconds after...

Страница 32: ...pump E041 Misfitted temperature alarm Heat pump E101 Communication Timeout GI module error Heat pump E611 Inlet water temp sensor error Heat pump E682 Plant water plant temperature remote sensor if e...

Страница 33: ...1 E913 Automatic All compressors are off for at least 180 sec E921 E923 Automatic All compressors are off for at least 180 sec E931 E933 Automatic All compressors are off for at least 180 sec E941 E94...

Страница 34: ...i MAX Industrial inverter air water heat pump with axial fans 34...

Страница 35: ......

Страница 36: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: