HWA1-A

 

Air/water chillers with axial fans

 

18

 

14.2.6

 

HEATING MODE ON DOMESTIC HOT WATER TANK 

If the parameter 

Pa H130 

is set to be

 1

, the unit uses the domestic hot water tank also for heating the plant side. Under these 

conditions, therefore, the relay that controls the domestic hot water will be excited even during heating mode operation and not 
only in sanitary mode. 
During the defrosting cycle and cooling mode, the valve will stop operation. 

14.3

 

SUMMER/WINTER MODE ROMOTE COMMUTATION 

Remote possibility of controlling the heating/cooling mode of the heat pump. 
To enable this function, enter at the parameters PRG

PSS

PRG

(introduce the maintainer password)

PRG

PAr

 PRG

CnF

 

See paragraph 

Errore. L'origine riferimento non è stata trovata.

.

 

Parameter 

Unit 

Value 

Description 

Terminals 

Notes 

H57 

Num 

Digital input for operazioni mode management. 
Open contact 

 

heat pump in ”

cool

” mode

Close contact 

 unit operates in 

heat

 mode. 

ID3E- ID3E 

Voltage free digital input 

14.4

 

PLANT REMOTE CONTROL (MANAGEMENT) 

It  is  possible  to  enable  a  plant  temperature  sensor  in  order  to  allow  the  on-board  unit  controller  to  correctly  manage  the 
regulation. 
To enable this function, enter at the parameters PRG

PSS

PRG

(introduce the maintainer password)

PRG

PAr

 PRG

CnF 

Parameter 

Value 

Description 

Terminals 

H30 

41 

Enablement of the plant remote temperature sensor 

ST8E- ST8E 

The  plant  circuit  remote  sensor  adjusts  the  heat  pump  temperature  only  during  the  startup  period  of  the  compressor(s),  the 
shutdown  is  managed  by  the  outlet  temperature  sensor  of  the  heat  pump.  For  more  explanation  herein  below  is  reported  an 
illustrating table regarding the operation of the system: 

Mode of operation 

Active call of the heat pump 

 

Heating 

Temperature detected by the outlet sensor of the heat pump < setpoint 

Hea 

b05

 

and

 

Temperature detected by the plant circuit remote sensor < water setpoint 

Hea 

- (

b22 - b05)

 

 

Cooling 

Temperature detected by the outlet sensor of the heat pump > setpoint 

Coo 

b05

 

and 

Temperature detected by the plant circuit remote sensor > setpoint 

Coo 

+ (

b22 - b05)

 

NOTE:

 b05=1°C; b22=5°C. 

14.5

 

DOUBLE SET-POINT MANAGEMENT 

The double set-point function introduces a second working set-point of the plant side (in both cooling and heating mode).

 

It is possible to configure in the user terminal block a digital input allowing the transition from the first to the second set-point and 
vice versa. 

14.5.1

 

SETTINGS 

The parameter 

H129

 of double setpoint mode setting (from maintainer menu): 

H82 

OPERATION 

Classic mode 

Double setpoint active in the summer 

Double setpoint active in the winter 

Double setpoint active in the summer and winter 

To activate the function enter with maintainer password to the parameters: 

Parameter 

Unit 

Default 

Value 

Description 

Terminals 

Notes 

H57 

Num 

26 

Digital input for second setpoint 

ID3E 

 ID3E 

H90 

Num 

25 

Under-voltage output for 3 way valve 
for radiant panels 

DO5E(phase) 

DO5EN(neutral) 

Under voltage output single 
phase 230Vac, 50Hz, 5A resistive, 
1A inductive to connect relay coil 
for obtaining a free contact.

 

The  under-voltage  output  with  live  contact  for  switching  from  first  to  second  set-point  and  vice  versa.  This  can  be  used,  for 
example, for switching a hydronic valve for to divert the water flow between the radiant system and the ventilation system. If it is 
needed a relay should be used for the hydronic valve power supply. 

Содержание HWA1-A 0140

Страница 1: ...WA1 H 0285 This manual has been created for informative purpose The company declines any responsibility for the results of any projecting or any installation based on the explanations and or on the te...

Страница 2: ...ONTROL 9 7 1 SET POINT ADJUSTMENT FROM 0 10V INPUT 9 7 2 CALCULATION OF THE CORRECTION WITH 0 10V INPUT 10 7 3 CALCULATION OF THE CORRECTION WITH RATIOMETRIC INPUT 10 7 3 1 Settings for standard clima...

Страница 3: ...20 17 4 SETTING PARAMETERS 21 17 5 CONDENSATION PARAMETERS 21 17 6 COMPRESSOR PARAMETERS CONFIGURATION 21 18 USER AND INSTALLER ALLOWED CONFIGURATION TABLES 21 18 1 SET POINT S CONFIGURATION PARAMETE...

Страница 4: ...and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectly knowledg...

Страница 5: ...er voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a possi...

Страница 6: ...e UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In the setting mode this button all...

Страница 7: ...greater privilege Once you exit completely from the menus you lose the password privilege and need to re enter it 5 3 1 Setpoint menu You can display and change the various setpoints SETPOINT DESCRIP...

Страница 8: ...ou can display the number of operating hours of the compressors and of the pumps Press the ESC button for 3 seconds to resets the actual number of operating hours Note that you can get access to the m...

Страница 9: ...aged by the controller which calculates the compressor on and off events according to the setpoint based on heat within a differential If several compressors are configured the controller selects the...

Страница 10: ...delay time between a compressor shutdown and shutdown of the next one 6 5 Deactivation of compressors for outdoor temperature If the outdoor temperature sensor is configured and is not in trouble so t...

Страница 11: ...0 10V analogue input if enabled To enable the function you must set the H21 parameter to be 40 and change the values of the parameter b15 range 0 10 taking into account that if the input is at 0 volt...

Страница 12: ...ulation of the circulator is linear type 8 1 Air purging of the system This function allows the air purging of the system to achieve this function the circulator will run at its maximum speed To enabl...

Страница 13: ...draulic pump in anti freezing operation If the setting temperature is too low and the pump is off the pump will be activated automatically Pa P04 set antifreeze pump activation Pa P05 hysteresis pump...

Страница 14: ...fan motor The condensation control is a function of the condensing pressure in chiller mode and the evaporation pressure in heat pump mode The fan speed can be independently controlled from the compre...

Страница 15: ...nt the frost formation on the surface of the air air coil The frost formation on the evaporator which occurs more frequently at very low ambient temperatures in addition to greatly decreasing the ther...

Страница 16: ...utput is active in COOLING operation The output is not active in heating operation The output is not active when the unit s OFF During the DHW production and defrosting cycle the output keeps the sett...

Страница 17: ...ort Parameter Value Function H10 0 default Deactivated function 1 Active function in heating and cooling mode The remote on off function doesn t deactivate the domestic hot water production DHW 2 Acti...

Страница 18: ...ction when the digital input is open Note If a temperature sensor is installed and configured this management will be ignored and the thermoregulation will be done on the basis of the detected tempera...

Страница 19: ...below is reported an illustrating table regarding the operation of the system Mode of operation Active call of the heat pump Heating Temperature detected by the outlet sensor of the heat pump setpoin...

Страница 20: ...ppropriately configured NC state connected on the terminals DI3E DI3E Thermostat contact normally open the secondary circulator will be activated Thermostat contact normally closed the secondary circu...

Страница 21: ...SER AND INSTALLER The parameters can be activated and or edited by user or when using the installer password to get access in the CB Control menu which is located on the front panel of the unit DESCRI...

Страница 22: ...6 COMPRESSOR PARAMETERS CONFIGURATION COMPRESSOR PARAMETERS CONFIGURATION Parameter Description Unit Default Range Visibility Allowed Configurations Notes n01 Output power from PC1 100 0 100 INSTALLER...

Страница 23: ...output in heating sec 45 0 255 INSTALLER b08 Enabling dynamic set 0 0 1 INSTALLER b09 Max Offset in cooling dynamic set C 3 0 50 0 80 0 INSTALLER b10 Max Offset in heating dynamic set C 3 0 50 0 80 0...

Страница 24: ...peration time of compressor with minimum frequency sec 60 0 255 INSTALLER 18 9 CONFIGURATION PARAMETERS OF GI Module PLANT MANAGEMENT Optional Parameter Description Unit Default Range Visibility Allow...

Страница 25: ...peration If the discharge temperature drops below Pa C65 the alarm disappears and the compressors are again ready to operate 19 10E016 USAGE PUMP 1 THERMAL PROTECTION The alarm will be activated when...

Страница 26: ...Antifreeze alarm Unit E006 Flow switch alarm Unit E009 High compressor s discharge temperature Unit E016 Usage pump 1 thermal overload protection Pump 1 E018 High temperature alarm in cooling operati...

Страница 27: ...3 7208 7203 C 10 R W 5 0 23 0 Cooling 7204 C 10 R W 25 0 55 0 Heating 7205 C 10 R W 25 0 55 0 Sanitary 7206 C 10 R W 5 0 23 0 Second cooling 7207 C 10 R W 25 0 55 0 Second heating 7208 C 10 R W 0 0 80...

Страница 28: ...C 10 R Compressors inhalation circuit 2 20433 C 10 R Compressor 1 discharge circuit 2 20434 C 10 R Compressor 2 discharge circuit 2 20435 C 10 R Compressor 3 discharge circuit 2 406 bar 100 R Pression...

Страница 29: ...re fault inverter 1 E851 5 Hardware fault inverter 2 E852 6 Hardware fault inverter 3 E853 7 Overcurrent inverter 1 E861 8 Overcurrent inverter 2 E862 9 Overcurrent inverter 3 E863 10 High temperature...

Страница 30: ...lla performed correctly E060 13 Anti legionella failed or stopped E061 if enabled the cycle is activated only if the DHW 4 5 6 status is terminated by the machine if the read value is equal to 32766 t...

Страница 31: ......

Страница 32: ...r Supervisor Notes Catalogo Catalogue Katalog Catalogue MCO14110G7720 06 Serie Series Serie Serie S rie HWA1 A H 0140 0285 AIR WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS Possible wasted electrical...

Отзывы: