HWA1-A
Air/water chillers with axial fans
25
19.15
[E611÷E682] TEMPERATURE SENSORS ALARMS
The sensor alarms are all auto-reset type. The alarm of a given sensor inhibits the functions which need its value. For each
encoding, see the table below.
Conditions of alarm sensor:
- Disconnected sensor.
- Short-circuit sensor.
- Sensor records a wrong range of temperature.
Temperature sensor characterization: NTC-
10kΏ a 25°C β3435
19.16
POWER FAILURE
After power supply reset:
•
The system comes back to the previous state before the power failure.
•
If the system is in defrosting period, this mode will be cancelled after power supply reset.
•
All the running timings will be cleared and reset again.
19.17
ALARMS
’
LIST
In case of alarm, an error code will appear on the
controller
’s
display
.
Code
Description
Lockout
E000
Remote switch Off of the unit
Unit
E001
High pressure alarm
Unit
E002
Low pressure alarm
Unit
E003
Compressor 1 thermal overload protection
Compressor 1 (C1)
E013
Compressor 2 thermal overload protection
Compressor 2 (C2)
E004
Fan motor 1 thermal overload protection
Unit
E005
Antifreeze alarm
Unit
E006
Flow switch alarm
Unit
E009
High compressor’s discharge
temperature
Unit
E016
Usage pump 1 thermal overload protection
Pump 1
E018
High temperature alarm in cooling operation
Unit
E026
Usage pump 2 thermal overload protection
Pump
E040
Compressor termic
Compressor
E042
Poor heat exchange alarm
Unit/Sanitary
E611
Inlet water temp. sensor error
Unit
E621
Outlet water temp. sensor error
Unit
E631
Compressor intake temperature sensor
Unit
E641
Compressor discharge temperature sensor
Unit
E651
Outdoor air temp. sensor for climatic regulation
Unit
(1)
E652
Desuperheater gas temperature sensor (if present)
Unit
(1)
E662
Total recovery temperature (if present)
--
(1)
E672
Sanitary temperature sensor (if present)
--
(1)
E682
Plant water plant temperature remote sensor (if present)
E691
Low pressure transducer
Unit
E701
High pressure transducer
Unit
(1)
Only if the optional “GI” module is prese
nt and active function.
20
MODBUS VARIABLES
The control introduces default the next configuration:
BAUD RATE
9600
PARITY
EVEN
DATA BIT
8
STOP BIT
1
DEVICE ID
1
The control introduces default the next configuration
To configure the Modbus communication depending on your needs, it is necessary to modify the next registers:
H124 : BAUD RATE
0
4800
1
9600
2
19200
3
38400
Содержание HWA1-A 0140