HWA1-A 

Air/water chillers with axial fans

 

25 

19.15

 

 [E611÷E682] TEMPERATURE SENSORS ALARMS 

The  sensor  alarms  are  all  auto-reset  type.  The  alarm  of  a  given  sensor  inhibits  the  functions  which  need  its  value.  For  each 
encoding, see the table below. 
Conditions of alarm sensor: 

 

- Disconnected sensor. 

 

- Short-circuit sensor. 

 

- Sensor records a wrong range of temperature. 

 

Temperature sensor characterization: NTC-

10kΏ a 25°C β3435

 

19.16

 

POWER FAILURE 

After power supply reset: 

 

The system comes back to the previous state before the power failure. 

 

If the system is in defrosting period, this mode will be cancelled after power supply reset. 

 

All the running timings will be cleared and reset again. 

19.17

 

 ALARMS

 LIST 

In case of alarm, an error code will appear on the 

controller

’s 

display

Code 

Description 

Lockout 

E000 

Remote switch Off of the unit 

Unit 

E001 

High pressure alarm 

Unit 

E002 

Low pressure alarm 

Unit 

E003 

Compressor 1 thermal overload protection 

Compressor 1 (C1) 

E013 

Compressor 2 thermal overload protection 

Compressor 2 (C2) 

E004 

Fan motor 1 thermal overload protection 

Unit 

E005 

Antifreeze alarm 

Unit 

E006 

Flow switch alarm 

Unit 

E009 

High compressor’s discharge

 temperature 

Unit 

E016 

Usage pump 1 thermal overload protection 

Pump 1 

E018 

High temperature alarm in cooling operation 

Unit 

E026 

Usage pump 2 thermal overload protection 

Pump  

E040 

Compressor termic 

Compressor 

E042 

Poor heat exchange alarm 

Unit/Sanitary 

E611 

Inlet water temp. sensor error 

Unit 

E621 

Outlet water temp. sensor error 

Unit 

E631 

Compressor intake temperature sensor 

Unit 

E641 

Compressor discharge temperature sensor 

Unit 

E651 

Outdoor air temp. sensor for climatic regulation 

Unit 

(1)

E652 

Desuperheater gas temperature sensor (if present) 

Unit 

(1)

E662 

Total recovery temperature (if present) 

-- 

(1)

E672 

Sanitary temperature sensor (if present) 

-- 

(1)

E682 

Plant water plant temperature remote sensor (if present) 

 

E691 

Low pressure transducer 

Unit 

E701 

High pressure transducer 

Unit 

(1)

 

Only if the optional “GI” module is prese

nt and active function. 

20

 

MODBUS VARIABLES 

The control introduces default the next configuration: 

BAUD RATE 

9600 

PARITY 

EVEN 

DATA BIT 

STOP BIT 

DEVICE ID 

The control introduces default the next configuration 

To configure the Modbus communication depending on your needs, it is necessary to modify the next registers: 

H124 : BAUD RATE 

4800 

9600 

19200 

38400 

Содержание HWA1-A 0140

Страница 1: ...WA1 H 0285 This manual has been created for informative purpose The company declines any responsibility for the results of any projecting or any installation based on the explanations and or on the te...

Страница 2: ...ONTROL 9 7 1 SET POINT ADJUSTMENT FROM 0 10V INPUT 9 7 2 CALCULATION OF THE CORRECTION WITH 0 10V INPUT 10 7 3 CALCULATION OF THE CORRECTION WITH RATIOMETRIC INPUT 10 7 3 1 Settings for standard clima...

Страница 3: ...20 17 4 SETTING PARAMETERS 21 17 5 CONDENSATION PARAMETERS 21 17 6 COMPRESSOR PARAMETERS CONFIGURATION 21 18 USER AND INSTALLER ALLOWED CONFIGURATION TABLES 21 18 1 SET POINT S CONFIGURATION PARAMETE...

Страница 4: ...and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectly knowledg...

Страница 5: ...er voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a possi...

Страница 6: ...e UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In the setting mode this button all...

Страница 7: ...greater privilege Once you exit completely from the menus you lose the password privilege and need to re enter it 5 3 1 Setpoint menu You can display and change the various setpoints SETPOINT DESCRIP...

Страница 8: ...ou can display the number of operating hours of the compressors and of the pumps Press the ESC button for 3 seconds to resets the actual number of operating hours Note that you can get access to the m...

Страница 9: ...aged by the controller which calculates the compressor on and off events according to the setpoint based on heat within a differential If several compressors are configured the controller selects the...

Страница 10: ...delay time between a compressor shutdown and shutdown of the next one 6 5 Deactivation of compressors for outdoor temperature If the outdoor temperature sensor is configured and is not in trouble so t...

Страница 11: ...0 10V analogue input if enabled To enable the function you must set the H21 parameter to be 40 and change the values of the parameter b15 range 0 10 taking into account that if the input is at 0 volt...

Страница 12: ...ulation of the circulator is linear type 8 1 Air purging of the system This function allows the air purging of the system to achieve this function the circulator will run at its maximum speed To enabl...

Страница 13: ...draulic pump in anti freezing operation If the setting temperature is too low and the pump is off the pump will be activated automatically Pa P04 set antifreeze pump activation Pa P05 hysteresis pump...

Страница 14: ...fan motor The condensation control is a function of the condensing pressure in chiller mode and the evaporation pressure in heat pump mode The fan speed can be independently controlled from the compre...

Страница 15: ...nt the frost formation on the surface of the air air coil The frost formation on the evaporator which occurs more frequently at very low ambient temperatures in addition to greatly decreasing the ther...

Страница 16: ...utput is active in COOLING operation The output is not active in heating operation The output is not active when the unit s OFF During the DHW production and defrosting cycle the output keeps the sett...

Страница 17: ...ort Parameter Value Function H10 0 default Deactivated function 1 Active function in heating and cooling mode The remote on off function doesn t deactivate the domestic hot water production DHW 2 Acti...

Страница 18: ...ction when the digital input is open Note If a temperature sensor is installed and configured this management will be ignored and the thermoregulation will be done on the basis of the detected tempera...

Страница 19: ...below is reported an illustrating table regarding the operation of the system Mode of operation Active call of the heat pump Heating Temperature detected by the outlet sensor of the heat pump setpoin...

Страница 20: ...ppropriately configured NC state connected on the terminals DI3E DI3E Thermostat contact normally open the secondary circulator will be activated Thermostat contact normally closed the secondary circu...

Страница 21: ...SER AND INSTALLER The parameters can be activated and or edited by user or when using the installer password to get access in the CB Control menu which is located on the front panel of the unit DESCRI...

Страница 22: ...6 COMPRESSOR PARAMETERS CONFIGURATION COMPRESSOR PARAMETERS CONFIGURATION Parameter Description Unit Default Range Visibility Allowed Configurations Notes n01 Output power from PC1 100 0 100 INSTALLER...

Страница 23: ...output in heating sec 45 0 255 INSTALLER b08 Enabling dynamic set 0 0 1 INSTALLER b09 Max Offset in cooling dynamic set C 3 0 50 0 80 0 INSTALLER b10 Max Offset in heating dynamic set C 3 0 50 0 80 0...

Страница 24: ...peration time of compressor with minimum frequency sec 60 0 255 INSTALLER 18 9 CONFIGURATION PARAMETERS OF GI Module PLANT MANAGEMENT Optional Parameter Description Unit Default Range Visibility Allow...

Страница 25: ...peration If the discharge temperature drops below Pa C65 the alarm disappears and the compressors are again ready to operate 19 10E016 USAGE PUMP 1 THERMAL PROTECTION The alarm will be activated when...

Страница 26: ...Antifreeze alarm Unit E006 Flow switch alarm Unit E009 High compressor s discharge temperature Unit E016 Usage pump 1 thermal overload protection Pump 1 E018 High temperature alarm in cooling operati...

Страница 27: ...3 7208 7203 C 10 R W 5 0 23 0 Cooling 7204 C 10 R W 25 0 55 0 Heating 7205 C 10 R W 25 0 55 0 Sanitary 7206 C 10 R W 5 0 23 0 Second cooling 7207 C 10 R W 25 0 55 0 Second heating 7208 C 10 R W 0 0 80...

Страница 28: ...C 10 R Compressors inhalation circuit 2 20433 C 10 R Compressor 1 discharge circuit 2 20434 C 10 R Compressor 2 discharge circuit 2 20435 C 10 R Compressor 3 discharge circuit 2 406 bar 100 R Pression...

Страница 29: ...re fault inverter 1 E851 5 Hardware fault inverter 2 E852 6 Hardware fault inverter 3 E853 7 Overcurrent inverter 1 E861 8 Overcurrent inverter 2 E862 9 Overcurrent inverter 3 E863 10 High temperature...

Страница 30: ...lla performed correctly E060 13 Anti legionella failed or stopped E061 if enabled the cycle is activated only if the DHW 4 5 6 status is terminated by the machine if the read value is equal to 32766 t...

Страница 31: ......

Страница 32: ...r Supervisor Notes Catalogo Catalogue Katalog Catalogue MCO14110G7720 06 Serie Series Serie Serie S rie HWA1 A H 0140 0285 AIR WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS Possible wasted electrical...

Отзывы: