HWA1-A

 

Air/water chillers with axial fans

 

4

 

 

WARNING: 

Before proceeding, you should read 

the user’s

-installer manual accompanying the appliance. 

All the operations described below must be carried out only by QUALIFIED PERSONNEL. 
The wiring to the terminal block must be performed by qualified personnel. 
Any routine and/or not-routine maintenance operation shall be carried out when the equipment has been shut 

down, disconnected from electric power supply. 

Do  not  put  neither  your  hands  nor  insert  screwdrivers,  spanners  or  other  tools  into  moving  parts  of  the 

equipment. 

The equipment supervisor and the maintenance man have to receive suitable training for the performance of 

their tasks in safety. 

The access to the electric panel is limited only for authorized personnel. 
Operators  have  to  know  how  to  use  personal  protective  devices  and  have  to  know  the  accident-prevention 

guidelines contained in national and international laws and norms. 

The operator’s workplace has to be kept clean, tidy and free from objects that may prevent free movements. 

Appropriate lighting of the work place shall be provided so as to allow the operator to carry out the required 
operations safely. Poor or too strong lighting can cause risks. 

Ensure  that  the  work  places  are  always  adequately  ventilated  and  that  aspirators  are  working,  in  good 

condition and in compliance with the requirements of the laws in force. 

Not all the configurations can be simultaneously enabled and/or changed. 
Other values different than those of default can ensure the proper operation of the unit, in case of doubt about 

the value to be set contact please our office. 

The company excludes any contractual and extra contractual liabilities for damages caused to persons, animals 

or objects, by incorrect installation, setting and maintenance, improper use of the equipment, and the partial 
or superficial reading of the information contained in this guide. 

 

The access to the electric panel is limited for authorized personnel only. 

It’s forbidder t

o carry out any work on the equipment under voltage. 

To touch the equipment if you are not allowed. 

 

If the lightning risk is high, the unit must be protected, the risk assessment must comply with the CEI EN 62305-2 
regulation. 
If  there  is  a  possibility  that  a  lightning  can  strike  the  area  around  the  appliance,  shut  down  the  unit  and 
disconnect the system upstream switch. 
Make sure to ground the unit. 
Do not ground the unit with pipes or lightning rods. 
A poor grounding of the unit can result in electrocution. 
Warning: Electrostatic discharges can damage the electronic components, before performing any work; ground 
the electrostatic charge by touching objects such as water or heating pipes. 
Requirements before performing electrical work on the control board: 

Turn off the unit from the control panel ("OFF" displayed). 

Put the switch “QF” general differential on OFF position

 

Wait for 15 seconds before getting access to the electric board 
Check the ground connection before beginning any operation. 
Be sure that you are well insulated from the ground, with dry hands and feet, or by using insulating platforms 

and gloves. 

Check that there is no foreign material near the system. 

4

 

PURPOSES AND CONTENTS OF THE MANUAL 

This manual collects the basic information concerning the configuration of the onboard control panel of the unit. 
It is addressed to the installer/user of the unit: it allows you to operate the machine efficiently, even without any previous specific 
knowledge of it. 
Not  all  the  described  functions  can  be  individually  and/or  simultaneously  selected.  Please  contact  the  technical  office  for  any 
information. 
This manual describes the characteristics of the equipment when it was being put in marketing; therefore, it may not capture later 
technological improvements introduced by the company as part of its constant  endeavors in order to enhance the performance, 
ergonomics, safety and functionality. 
The company introduces also technological improvements and is not constrained to update the manuals for previous versions of 
appliances that could not be compatible. So make sure to use the provided manual for the installed unit. 

It’s recommended that, the user must follow the instructions contained in this booklet, especially those concerning the safet

y and 

routine maintenance. 

Содержание HWA1-A 0140

Страница 1: ...WA1 H 0285 This manual has been created for informative purpose The company declines any responsibility for the results of any projecting or any installation based on the explanations and or on the te...

Страница 2: ...ONTROL 9 7 1 SET POINT ADJUSTMENT FROM 0 10V INPUT 9 7 2 CALCULATION OF THE CORRECTION WITH 0 10V INPUT 10 7 3 CALCULATION OF THE CORRECTION WITH RATIOMETRIC INPUT 10 7 3 1 Settings for standard clima...

Страница 3: ...20 17 4 SETTING PARAMETERS 21 17 5 CONDENSATION PARAMETERS 21 17 6 COMPRESSOR PARAMETERS CONFIGURATION 21 18 USER AND INSTALLER ALLOWED CONFIGURATION TABLES 21 18 1 SET POINT S CONFIGURATION PARAMETE...

Страница 4: ...and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectly knowledg...

Страница 5: ...er voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a possi...

Страница 6: ...e UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In the setting mode this button all...

Страница 7: ...greater privilege Once you exit completely from the menus you lose the password privilege and need to re enter it 5 3 1 Setpoint menu You can display and change the various setpoints SETPOINT DESCRIP...

Страница 8: ...ou can display the number of operating hours of the compressors and of the pumps Press the ESC button for 3 seconds to resets the actual number of operating hours Note that you can get access to the m...

Страница 9: ...aged by the controller which calculates the compressor on and off events according to the setpoint based on heat within a differential If several compressors are configured the controller selects the...

Страница 10: ...delay time between a compressor shutdown and shutdown of the next one 6 5 Deactivation of compressors for outdoor temperature If the outdoor temperature sensor is configured and is not in trouble so t...

Страница 11: ...0 10V analogue input if enabled To enable the function you must set the H21 parameter to be 40 and change the values of the parameter b15 range 0 10 taking into account that if the input is at 0 volt...

Страница 12: ...ulation of the circulator is linear type 8 1 Air purging of the system This function allows the air purging of the system to achieve this function the circulator will run at its maximum speed To enabl...

Страница 13: ...draulic pump in anti freezing operation If the setting temperature is too low and the pump is off the pump will be activated automatically Pa P04 set antifreeze pump activation Pa P05 hysteresis pump...

Страница 14: ...fan motor The condensation control is a function of the condensing pressure in chiller mode and the evaporation pressure in heat pump mode The fan speed can be independently controlled from the compre...

Страница 15: ...nt the frost formation on the surface of the air air coil The frost formation on the evaporator which occurs more frequently at very low ambient temperatures in addition to greatly decreasing the ther...

Страница 16: ...utput is active in COOLING operation The output is not active in heating operation The output is not active when the unit s OFF During the DHW production and defrosting cycle the output keeps the sett...

Страница 17: ...ort Parameter Value Function H10 0 default Deactivated function 1 Active function in heating and cooling mode The remote on off function doesn t deactivate the domestic hot water production DHW 2 Acti...

Страница 18: ...ction when the digital input is open Note If a temperature sensor is installed and configured this management will be ignored and the thermoregulation will be done on the basis of the detected tempera...

Страница 19: ...below is reported an illustrating table regarding the operation of the system Mode of operation Active call of the heat pump Heating Temperature detected by the outlet sensor of the heat pump setpoin...

Страница 20: ...ppropriately configured NC state connected on the terminals DI3E DI3E Thermostat contact normally open the secondary circulator will be activated Thermostat contact normally closed the secondary circu...

Страница 21: ...SER AND INSTALLER The parameters can be activated and or edited by user or when using the installer password to get access in the CB Control menu which is located on the front panel of the unit DESCRI...

Страница 22: ...6 COMPRESSOR PARAMETERS CONFIGURATION COMPRESSOR PARAMETERS CONFIGURATION Parameter Description Unit Default Range Visibility Allowed Configurations Notes n01 Output power from PC1 100 0 100 INSTALLER...

Страница 23: ...output in heating sec 45 0 255 INSTALLER b08 Enabling dynamic set 0 0 1 INSTALLER b09 Max Offset in cooling dynamic set C 3 0 50 0 80 0 INSTALLER b10 Max Offset in heating dynamic set C 3 0 50 0 80 0...

Страница 24: ...peration time of compressor with minimum frequency sec 60 0 255 INSTALLER 18 9 CONFIGURATION PARAMETERS OF GI Module PLANT MANAGEMENT Optional Parameter Description Unit Default Range Visibility Allow...

Страница 25: ...peration If the discharge temperature drops below Pa C65 the alarm disappears and the compressors are again ready to operate 19 10E016 USAGE PUMP 1 THERMAL PROTECTION The alarm will be activated when...

Страница 26: ...Antifreeze alarm Unit E006 Flow switch alarm Unit E009 High compressor s discharge temperature Unit E016 Usage pump 1 thermal overload protection Pump 1 E018 High temperature alarm in cooling operati...

Страница 27: ...3 7208 7203 C 10 R W 5 0 23 0 Cooling 7204 C 10 R W 25 0 55 0 Heating 7205 C 10 R W 25 0 55 0 Sanitary 7206 C 10 R W 5 0 23 0 Second cooling 7207 C 10 R W 25 0 55 0 Second heating 7208 C 10 R W 0 0 80...

Страница 28: ...C 10 R Compressors inhalation circuit 2 20433 C 10 R Compressor 1 discharge circuit 2 20434 C 10 R Compressor 2 discharge circuit 2 20435 C 10 R Compressor 3 discharge circuit 2 406 bar 100 R Pression...

Страница 29: ...re fault inverter 1 E851 5 Hardware fault inverter 2 E852 6 Hardware fault inverter 3 E853 7 Overcurrent inverter 1 E861 8 Overcurrent inverter 2 E862 9 Overcurrent inverter 3 E863 10 High temperature...

Страница 30: ...lla performed correctly E060 13 Anti legionella failed or stopped E061 if enabled the cycle is activated only if the DHW 4 5 6 status is terminated by the machine if the read value is equal to 32766 t...

Страница 31: ......

Страница 32: ...r Supervisor Notes Catalogo Catalogue Katalog Catalogue MCO14110G7720 06 Serie Series Serie Serie S rie HWA1 A H 0140 0285 AIR WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS Possible wasted electrical...

Отзывы: