background image

HWA1-A

 

Air/water chillers with axial fans

 

16

 

 
 

 

 
 
 
 
 
 
 
 
 
The free-cooling demand will be activated when the outdoor temperature is lower with 

F26

 than the intake temperature. 

After activation of the free-cooling, it will stop when the outdoor temperature increases above 

T

intake

 - F26 + F27

The free-cooling control valve is active when free-cooling demand is active. 

14.1.1

 

 Ventilation in freecooling 

When the free-cooling control valve is active: 
When  compressors  are  active,  or  if  compressors  are  called,  the  ventilation  starts  as  described  in  the  condensation  control 
controller. 
If the compressors switch off for satisfied thermoregulation, the ventilation logic switches the control to free-cooling demand with 
the following modes: 

-

 

The ventilation is forced at maximum speed (100%) for the first 

F25

 minutes. 

-

 

When the time defined by 

F25

 is terminated, the regulation becomes PI type with band given by 

b01

, the setpoint is that 

of the current plant water regulation. 

-

 

In case of turning back to the zone of compressors thermoregulation call, the ventilation returns under the condensation 
control. 

14.2

 

Enablement of domestic hot water production (DHW) 

In  sanitary  mode,  the  maximum  power  is  employed  (like  when  the  thermoregulator  is  asking  always  for  100%).  However,  the 
various limitations of the maximum frequency associated with the envelope and the limitation for maximum electrical absorption 
are active. 
To activate this function, it is necessary to connect to  the 

ST2E 

 ST2E

 terminals (enabled as analog input) a temperature sensor 

which should be placed inside the water tank. Once connecting and placing the sensor, then it is necessary to enable the domestic 
hot water function. 
To  enable  this  function,  enter  at  the  parameters  PRG

PSS

PRG

(introduce  the  maintainer  password)

  PRG

PAr

 

PRG

CnF

 

I/O port 

 Parameter 

Value 

Function 

H10 

0 (default) 

Deactivated function 

1  

Active function in 

heating and cooling 

mode. 

The remote on-off function 

doesn’t deactiv

ate

 the domestic hot water production (DHW). 

Active function in 

heating and cooling 

mode. 

The remote on-off function 

deactivates

 the domestic hot water production (DHW) 

Active function in 

heating

 mode. 

The remote on-off function 

doesn’t deactiv

ate

 the domestic hot water production (DHW). 

Active function in 

heating

 mode. 

The remote on-off function 

deactivates

 the domestic hot water production (DHW) 

Active function in 

cooling

 mode. 

The remote on-off function 

doesn’t deactiv

ate

 the domestic hot water production (DHW). 

Active function in 

cooling

 mode. 

The remote on-off function 

deactivates

 the domestic hot water production (DHW). 

H29 

Activation of domestic hot water temperature sensor DHW (ST7E terminals) 

H90

 

DHW valve command (D05E/D05EN terminals) 

If the DHW temperature is below the set point value (

PRG->Set->SAN

), the unit activates the sanitary valve and the compressor 

will be placed at the maximum frequency starting the modulation at 1°C before (setpoint-1°C) the set value and it stops at 1°C 
after  the  set  value  (s1°C).  Once  achieved  the  set  point  value,  the  valve  switches  to  the  stand-by  mode  and  the 
compressor works normally. 

While shifting  from user’s to  domestic hot  water, the operating sensor changes from “

outlet  water temp. sensor

” to “

sanitary 

tank temp. sensor

”. While shifting from the winter operating mode to the sanitary operating mode, the compressor does not stop 

operation, and will be placed at the maximum established frequency which can be controlled; however, when shifting from the 
summer operating mode to the sanitary operating mode, the compressor will stop operation for waiting for the safe period. 

The defrost cycle during winter operation mode is always performed on the user side, never on the sanitary water tank. 

ON 

OFF 

Temperatura esterna

 

Freecooling demand

 

Temperatura di ripresa

 

F27

 

F26

 

Содержание HWA1-A 0140

Страница 1: ...WA1 H 0285 This manual has been created for informative purpose The company declines any responsibility for the results of any projecting or any installation based on the explanations and or on the te...

Страница 2: ...ONTROL 9 7 1 SET POINT ADJUSTMENT FROM 0 10V INPUT 9 7 2 CALCULATION OF THE CORRECTION WITH 0 10V INPUT 10 7 3 CALCULATION OF THE CORRECTION WITH RATIOMETRIC INPUT 10 7 3 1 Settings for standard clima...

Страница 3: ...20 17 4 SETTING PARAMETERS 21 17 5 CONDENSATION PARAMETERS 21 17 6 COMPRESSOR PARAMETERS CONFIGURATION 21 18 USER AND INSTALLER ALLOWED CONFIGURATION TABLES 21 18 1 SET POINT S CONFIGURATION PARAMETE...

Страница 4: ...and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectly knowledg...

Страница 5: ...er voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a possi...

Страница 6: ...e UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In the setting mode this button all...

Страница 7: ...greater privilege Once you exit completely from the menus you lose the password privilege and need to re enter it 5 3 1 Setpoint menu You can display and change the various setpoints SETPOINT DESCRIP...

Страница 8: ...ou can display the number of operating hours of the compressors and of the pumps Press the ESC button for 3 seconds to resets the actual number of operating hours Note that you can get access to the m...

Страница 9: ...aged by the controller which calculates the compressor on and off events according to the setpoint based on heat within a differential If several compressors are configured the controller selects the...

Страница 10: ...delay time between a compressor shutdown and shutdown of the next one 6 5 Deactivation of compressors for outdoor temperature If the outdoor temperature sensor is configured and is not in trouble so t...

Страница 11: ...0 10V analogue input if enabled To enable the function you must set the H21 parameter to be 40 and change the values of the parameter b15 range 0 10 taking into account that if the input is at 0 volt...

Страница 12: ...ulation of the circulator is linear type 8 1 Air purging of the system This function allows the air purging of the system to achieve this function the circulator will run at its maximum speed To enabl...

Страница 13: ...draulic pump in anti freezing operation If the setting temperature is too low and the pump is off the pump will be activated automatically Pa P04 set antifreeze pump activation Pa P05 hysteresis pump...

Страница 14: ...fan motor The condensation control is a function of the condensing pressure in chiller mode and the evaporation pressure in heat pump mode The fan speed can be independently controlled from the compre...

Страница 15: ...nt the frost formation on the surface of the air air coil The frost formation on the evaporator which occurs more frequently at very low ambient temperatures in addition to greatly decreasing the ther...

Страница 16: ...utput is active in COOLING operation The output is not active in heating operation The output is not active when the unit s OFF During the DHW production and defrosting cycle the output keeps the sett...

Страница 17: ...ort Parameter Value Function H10 0 default Deactivated function 1 Active function in heating and cooling mode The remote on off function doesn t deactivate the domestic hot water production DHW 2 Acti...

Страница 18: ...ction when the digital input is open Note If a temperature sensor is installed and configured this management will be ignored and the thermoregulation will be done on the basis of the detected tempera...

Страница 19: ...below is reported an illustrating table regarding the operation of the system Mode of operation Active call of the heat pump Heating Temperature detected by the outlet sensor of the heat pump setpoin...

Страница 20: ...ppropriately configured NC state connected on the terminals DI3E DI3E Thermostat contact normally open the secondary circulator will be activated Thermostat contact normally closed the secondary circu...

Страница 21: ...SER AND INSTALLER The parameters can be activated and or edited by user or when using the installer password to get access in the CB Control menu which is located on the front panel of the unit DESCRI...

Страница 22: ...6 COMPRESSOR PARAMETERS CONFIGURATION COMPRESSOR PARAMETERS CONFIGURATION Parameter Description Unit Default Range Visibility Allowed Configurations Notes n01 Output power from PC1 100 0 100 INSTALLER...

Страница 23: ...output in heating sec 45 0 255 INSTALLER b08 Enabling dynamic set 0 0 1 INSTALLER b09 Max Offset in cooling dynamic set C 3 0 50 0 80 0 INSTALLER b10 Max Offset in heating dynamic set C 3 0 50 0 80 0...

Страница 24: ...peration time of compressor with minimum frequency sec 60 0 255 INSTALLER 18 9 CONFIGURATION PARAMETERS OF GI Module PLANT MANAGEMENT Optional Parameter Description Unit Default Range Visibility Allow...

Страница 25: ...peration If the discharge temperature drops below Pa C65 the alarm disappears and the compressors are again ready to operate 19 10E016 USAGE PUMP 1 THERMAL PROTECTION The alarm will be activated when...

Страница 26: ...Antifreeze alarm Unit E006 Flow switch alarm Unit E009 High compressor s discharge temperature Unit E016 Usage pump 1 thermal overload protection Pump 1 E018 High temperature alarm in cooling operati...

Страница 27: ...3 7208 7203 C 10 R W 5 0 23 0 Cooling 7204 C 10 R W 25 0 55 0 Heating 7205 C 10 R W 25 0 55 0 Sanitary 7206 C 10 R W 5 0 23 0 Second cooling 7207 C 10 R W 25 0 55 0 Second heating 7208 C 10 R W 0 0 80...

Страница 28: ...C 10 R Compressors inhalation circuit 2 20433 C 10 R Compressor 1 discharge circuit 2 20434 C 10 R Compressor 2 discharge circuit 2 20435 C 10 R Compressor 3 discharge circuit 2 406 bar 100 R Pression...

Страница 29: ...re fault inverter 1 E851 5 Hardware fault inverter 2 E852 6 Hardware fault inverter 3 E853 7 Overcurrent inverter 1 E861 8 Overcurrent inverter 2 E862 9 Overcurrent inverter 3 E863 10 High temperature...

Страница 30: ...lla performed correctly E060 13 Anti legionella failed or stopped E061 if enabled the cycle is activated only if the DHW 4 5 6 status is terminated by the machine if the read value is equal to 32766 t...

Страница 31: ......

Страница 32: ...r Supervisor Notes Catalogo Catalogue Katalog Catalogue MCO14110G7720 06 Serie Series Serie Serie S rie HWA1 A H 0140 0285 AIR WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS Possible wasted electrical...

Отзывы: