QUICK START GUIDE

Introduction

The HydroWHIZ Controller has been designed with ease of use at the core of the system design. Building on the wealth of the pump 

control features in the Advanced controller, the HydroWHIZ brings these features into a new age with a color touch screen interface 

and a streamlined setup process. In a world where information is power the HydroWHIZ has extensive time and date stamped 

alarms, logged data, trend graphs and diagnostic pages to provide the user with all the information required for optimisation and 

preventative maintenance. Featuring the flexibility of level, pressure and temperature system modes with a wide range of functions 

and protections, the HydroWHIZ VSD controller is ideal for a wide range of applications including water transfer, stormwater and 

sewage pump out, constant pressure, hot water circulation and chiller supply, to name a few. 

For more information on the operation of the HydroWHIZ VSD controller see the HydroWHIZ VSD Operation Manual.

V1.7

HydroWHIZ Pump Controllers

VSD

Safety

This control panel has been designed and built for applications that are Commercial and/or Industrial in nature, operation, function 

and location. If the control panel is to be used in Domestic/Residential applications, where specific Wiring Rules in respect of ‘electrical 

supply’ protection may apply, it is the responsibility of the installing electrician to ensure compliance with relevant standards.

• 

Prior to installation, ensure power supply is isolated.

• 

Power supply must be circuit breaker protected (qualified electrician to determine appropriate amp rating).

• 

It is highly recommended that RCDs are NOT used to protect the supply to this panel. The VSDs in this panel have EMC filtering 

which can cause nuisance tripping of RCDs. It is recommended to use alternative protection for the incoming cables. If RCDs 

are required, type B RCDs must be used, taking into consideration the VSD earth leakage current to avoid nuisance tripping.

• 

Electrical connection to the panel must be carried out in accordance with the following pages.

• 

Additions or modifications to the control panel are not permitted and will void warranty.

• 

The controller is not intended for use by children or infirm persons without supervision.

• 

Repairs to the controller must only be carried out by a suitably qualified electrician.

This manual makes use of the following symbols to indicate warnings that must be paid specific attention to:

Damage to equipment or personal harm may occur if this instruction is not followed

 

 

 

 

Electrical risk (electrocution hazard) may occur if this instruction is not followed

 

 

 

 

Single Phase - FPC-63X21 (1-6 Pumps)
Three Phase - FPC-63X20 (1-6 Pumps)

Содержание Hydrowhiz FPC-63X20

Страница 1: ...the control panel is to be used in Domestic Residential applications where specific Wiring Rules in respect of electrical supply protection may apply it is the responsibility of the installing electri...

Страница 2: ...have internal filters to reduce the amount of distortion however in some applications additional filtering may be required If additional harmonic filtering is required to meet site specifications this...

Страница 3: ...een RUNNING Enter PIN LOGIN REQUIRED 10 06 2020 17 50 58 OK 3 2 1 6 5 4 9 8 7 0 CANCEL 2020 5 6 Warning If the system mode is in auto tapping on a setting will bring up a Warning screen Press OK to tu...

Страница 4: ...ype Number of pumps Pump limit Duty change period Setup 1 System Setup Level VSD 4 6 60 Mins RUNNING Current MENU 3 2 1 6 5 4 9 8 7 0 CANCEL OK 60 Mins Duty change period RUNNING MENU System type Pres...

Страница 5: ...w level threshold When the analog goes below this threshold for 3 seconds the Low level protection will be activated High level threshold When the analog goes above this threshold for 3 seconds the Hi...

Страница 6: ...uest Temperature control Sets the control direction for the corresponding System type Temperature cool heat Low temperature protection Alarm Triggers alarm only Lockout Triggers an alarm and shuts dow...

Страница 7: ...e Sleep delay the system will go to sleep See Step 5 12 on the next page for more information on setting the No demand speed Manual speed This is the speed a VSD controlled pump will run in manual If...

Страница 8: ...and destaging functions The no demand is to be set at the speed Hz at which one pump achieves the setpoint against a dead head shut discharge valve If the system is operating as a mains boosting syste...

Страница 9: ...pump has not run for 7 days the pump run for 5 seconds to prevent seizing as long as the system mode is in sleep disabled or inhibit Max run fault protection Alarm Alarm only if a pump runs at the max...

Страница 10: ...Main screen icon where the System Mode will need to be changed after completing Step 6 VSD commissioning Main Screen Alarms Logged Data Trend Plot Setup All Parameters Date Time Diagnostics RUNNING 10...

Страница 11: ...50 50000 rpm Device for 60 Hz mains 50 1750 50000 rpm General motor data Carry out settings as specified by motor nameplate data Note When you enter the motor nameplate data take into account the phas...

Страница 12: ...nominal motor voltage Hz 9908 MOTOR NOM SPEED Defines the nominal motor speed Must be equal to the value on the motor rating plate rpm 9909 MOTOR NOM POWER Defines the nominal motor power Must equal...

Страница 13: ...level step DOL Standby start pressure step Standby start temp step Low level threshold Low pressure threshold Low temperature threshold High level threshold High pressure threshold High temperature t...

Страница 14: ...ns bypass valve enable Sleep delay Top up valve open level Top up valve closed level 4 VSD Level Pressure Temperature VSD full speed level PID Proportional VSD full speed temperature VSD speed at stop...

Отзывы: