6
P: 1800 281 282
|
F: 1300 281 282
|
|
W: www.matelecaustralia.com.au
5.9 - 3 Function
The functional setup for the system.
RUNNING
MENU
Level Control
Low level protection
High level protection
Sleep delay
Tank top up valve control
Top up valve open level
Top up valve closed level
Setup: 3 Function
Lower/empty/cool
Lockout
Alarm
10 Secs
1.60m
2.00m
RUNNING
MENU
Jacking pump
Low pressure protection
High pressure protection
Sleep delay
Mains bypass valve enable
Setup: 3 Function
Lockout
Lockout
10 Secs
RUNNING
MENU
Temperature control
Low temperature protection
High temperature protection
Sleep mode
Sleep delay
Setup: 3 Function
Lower/empty/cool
Lockout
Lockout
Setpoint base
10 Secs
Level Control
Pressure Control
Temperature Control
Level
Pressure
Temperature
Jacking pump
If enabled jacking pump 1 will always be the first to wake from sleep. When it can't keep up with demand,
one of the main pumps will start and the jacking pump will switch off after 10 seconds.
Low pressure
protection
Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down
the pumps only and waits 60 seconds before auto restart. 5 failed restarts will active a lockout.
High pressure
protection
Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down
the pumps only. All modes will auto reset when condition clears.
Sleep delay
The delay once the pump speed falls below the
No demand speed
before the system will go to sleep.
Mains bypass valve
enable
If enabled, the valve output will be used for a normally open mains bypass valve, energising it shut during
normal operation and de-energising the valve open on digital low level, system off, disabled or lockout.
Note -
This feature is available upon request.
Temperature control
Sets the control direction for the corresponding
System type.
Temperature = cool/heat
Low temperature
protection
Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down
the pumps only. All modes will auto reset when condition clears.
High temperature
protection
Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down
the pumps only. All modes will auto reset when condition clears.
Sleep mode
None = System won't sleep, always at least 1 pump running, Setpoint based = System will go to sleep after
the
sleep delay
when the analog
Setpoint
has been reached and/or all digital start inputs are open.
Speed based = Not applicable in temperature operation.
Sleep delay
If
Sleep mode
= Setpoint based, this is the delay once the analog
Setpoint
is reached before the pumps
will go to sleep.
Level control
Sets the control direction for the corresponding
System type.
Level = empty/fill
Low level protection
Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down
the pumps only. All modes will auto reset when condition clears.
High level protection
Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down
the pumps only. All modes will auto reset when condition clears.
Sleep delay
The delay once the analog
Setpoint
is reached before the pumps will go to sleep.
Tank top up valve
enable
If enabled the valve output will be used for a normally closed tank top up valve using the
Tank top up
valve open level
and
Tank top up valve closed level
.
Note -
This feature is available upon request.
Top up valve open
level
The analog level at which the valve output will be energised to open the valve. Must be below the
Tank
top up valve closed level
.
Top up valve closed
level
The analog level at which the valve output will be deenergised to close the valve. Must be above the
Tank
top up valve open level
.
Step 5 - Setup (Continued)