5.9 - 3 Function

The functional setup for the system. 

RUNNING

MENU

Level Control
Low level protection
High level protection
Sleep delay
Tank top up valve control
Top up valve open level
Top up valve closed level

Setup: 3 Function

Lower/empty/cool
Lockout
Alarm
10 Secs

1.60m
2.00m

RUNNING

MENU

Jacking pump
Low pressure protection
High pressure protection
Sleep delay
Mains bypass valve enable

Setup: 3 Function

Lockout
Lockout
10 Secs

RUNNING

MENU

Temperature control
Low temperature protection
High temperature protection
Sleep mode
Sleep delay

Setup: 3 Function

Lower/empty/cool
Lockout
Lockout
Setpoint base
10 Secs

Level Control

Pressure Control

Temperature Control

Level

Pressure

Temperature

Jacking pump

If enabled jacking pump 1 will always be the first to wake from sleep. When it can't keep up with demand, 

one of the main pumps will start and the jacking pump will switch off after 10 seconds.

Low pressure 

protection

Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down 

the pumps only and waits 60 seconds before auto restart. 5 failed restarts will active a lockout.

High pressure 

protection

Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down 

the pumps only. All modes will auto reset when condition clears.

Sleep delay

The delay once the pump speed falls below the 

No demand speed

 before the system will go to sleep.

Mains bypass valve 

enable

If enabled, the valve output will be used for a normally open mains bypass valve, energising it shut during 

normal operation and de-energising the valve open on digital low level, system off, disabled or lockout. 

Note -

 This feature is available upon request.

Temperature control

Sets the control direction for the corresponding 

System type.

 Temperature = cool/heat

Low temperature 

protection

Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down 

the pumps only. All modes will auto reset when condition clears.

High temperature 

protection

Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down 

the pumps only. All modes will auto reset when condition clears.

Sleep mode

None = System won't sleep, always at least 1 pump running, Setpoint based = System will go to sleep after 

the 

sleep delay

 when the analog 

Setpoint

 has been reached and/or all digital start inputs are open. 

Speed based = Not applicable in temperature operation.

Sleep delay

If 

Sleep mode

 = Setpoint based, this is the delay once the analog 

Setpoint

 is reached before the pumps 

will go to sleep.

Level control

Sets the control direction for the corresponding 

System type.

 Level = empty/fill

Low level protection

Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down 

the pumps only. All modes will auto reset when condition clears.

High level protection

Alarm = Triggers alarm only, Lockout = Triggers an alarm and shuts down the pumps, Inhibit = Shuts down 

the pumps only. All modes will auto reset when condition clears.

Sleep delay

The delay once the analog 

Setpoint

 is reached before the pumps will go to sleep.

Tank top up valve 

enable

If enabled the valve output will be used for a normally closed tank top up valve using the 

Tank top up 

valve open level 

and 

Tank top up valve closed level

Note -

 This feature is available upon request.

Top up valve open 

level

The analog level at which the valve output will be energised to open the valve. Must be below the 

Tank 

top up valve closed level

.

Top up valve closed 

level

The analog level at which the valve output will be deenergised to close the valve. Must be above the 

Tank 

top up valve open level

.

Step 5 - Setup (Continued)

 

 

Содержание Hydrowhiz FPC-63X20

Страница 1: ...the control panel is to be used in Domestic Residential applications where specific Wiring Rules in respect of electrical supply protection may apply it is the responsibility of the installing electri...

Страница 2: ...have internal filters to reduce the amount of distortion however in some applications additional filtering may be required If additional harmonic filtering is required to meet site specifications this...

Страница 3: ...een RUNNING Enter PIN LOGIN REQUIRED 10 06 2020 17 50 58 OK 3 2 1 6 5 4 9 8 7 0 CANCEL 2020 5 6 Warning If the system mode is in auto tapping on a setting will bring up a Warning screen Press OK to tu...

Страница 4: ...ype Number of pumps Pump limit Duty change period Setup 1 System Setup Level VSD 4 6 60 Mins RUNNING Current MENU 3 2 1 6 5 4 9 8 7 0 CANCEL OK 60 Mins Duty change period RUNNING MENU System type Pres...

Страница 5: ...w level threshold When the analog goes below this threshold for 3 seconds the Low level protection will be activated High level threshold When the analog goes above this threshold for 3 seconds the Hi...

Страница 6: ...uest Temperature control Sets the control direction for the corresponding System type Temperature cool heat Low temperature protection Alarm Triggers alarm only Lockout Triggers an alarm and shuts dow...

Страница 7: ...e Sleep delay the system will go to sleep See Step 5 12 on the next page for more information on setting the No demand speed Manual speed This is the speed a VSD controlled pump will run in manual If...

Страница 8: ...and destaging functions The no demand is to be set at the speed Hz at which one pump achieves the setpoint against a dead head shut discharge valve If the system is operating as a mains boosting syste...

Страница 9: ...pump has not run for 7 days the pump run for 5 seconds to prevent seizing as long as the system mode is in sleep disabled or inhibit Max run fault protection Alarm Alarm only if a pump runs at the max...

Страница 10: ...Main screen icon where the System Mode will need to be changed after completing Step 6 VSD commissioning Main Screen Alarms Logged Data Trend Plot Setup All Parameters Date Time Diagnostics RUNNING 10...

Страница 11: ...50 50000 rpm Device for 60 Hz mains 50 1750 50000 rpm General motor data Carry out settings as specified by motor nameplate data Note When you enter the motor nameplate data take into account the phas...

Страница 12: ...nominal motor voltage Hz 9908 MOTOR NOM SPEED Defines the nominal motor speed Must be equal to the value on the motor rating plate rpm 9909 MOTOR NOM POWER Defines the nominal motor power Must equal...

Страница 13: ...level step DOL Standby start pressure step Standby start temp step Low level threshold Low pressure threshold Low temperature threshold High level threshold High pressure threshold High temperature t...

Страница 14: ...ns bypass valve enable Sleep delay Top up valve open level Top up valve closed level 4 VSD Level Pressure Temperature VSD full speed level PID Proportional VSD full speed temperature VSD speed at stop...

Отзывы: