5.7 - 1 System Setup

RUNNING

MENU

System type
Control output type
Number of pumps
Pump limit
Duty change period

Setup: 1 System Setup

Level
VSD
4
6
60 Mins

The main setup for the system and pump control method.

System type

Sets default system settings for the pressure, level or temperature system types.

Control output type

Sets default system settings for the DOL, Soft Start or VSD controlled pumps. This setting is factory set and 

does not require adjustment.

Number of pumps

Total number of pumps connected which configures the display and pump selection. This setting is 

factory set and does not require adjustment.

Pump limit

Maximum number pumps to be running at the same time. Used to limit max flow or max power 

requirements.

Duty change period

Duty pump running time before initiating a duty change to the next pump.

Step 5 - Setup (Continued)

RUNNING

MENU

System type
Control output type
Number of pumps
Pump limit
Duty change period

Setup: 1 System Setup

Level
VSD
4
6
60 Mins

RUNNING

Current:

MENU

3

2

1

6

5

4

9

8

7

0

CANCEL

OK

60 Mins

Duty change period

.

-

RUNNING

MENU

System type

Pressure
Level
Temperature

CANCEL

The Setup Screen is where the controller is configured for operation. 

The pages following the System Setup page will change depending on whether the ‘Level’, ‘Pressure’ or ‘Temperature’ 

system type

 is 

selected, allowing users to adjust settings that are specific to that application. 

All user adjusted settings can be recorded on the last page of this guide.

Setup Screen Operation

Setting Adjustment - Value

Setting Adjustment - Selection

If a value setting, such as 

Duty change period

, is pressed on, 

the keyboard screen will appear and the desired value can be 

entered or the process cancelled.

If a selection setting, such as 

System type

, is pressed on, a 

drop down list of all the available options for the setting will 

appear and the desired option can be selected or the process 

cancelled.

Touch to return to 

Menu

Setting value, touch to adjust 

(see below)

Touch to scroll forward 

through setup pages

Setting name

Touch to scroll backwards 

through setup pages

 

 

Содержание Hydrowhiz FPC-63X20

Страница 1: ...the control panel is to be used in Domestic Residential applications where specific Wiring Rules in respect of electrical supply protection may apply it is the responsibility of the installing electri...

Страница 2: ...have internal filters to reduce the amount of distortion however in some applications additional filtering may be required If additional harmonic filtering is required to meet site specifications this...

Страница 3: ...een RUNNING Enter PIN LOGIN REQUIRED 10 06 2020 17 50 58 OK 3 2 1 6 5 4 9 8 7 0 CANCEL 2020 5 6 Warning If the system mode is in auto tapping on a setting will bring up a Warning screen Press OK to tu...

Страница 4: ...ype Number of pumps Pump limit Duty change period Setup 1 System Setup Level VSD 4 6 60 Mins RUNNING Current MENU 3 2 1 6 5 4 9 8 7 0 CANCEL OK 60 Mins Duty change period RUNNING MENU System type Pres...

Страница 5: ...w level threshold When the analog goes below this threshold for 3 seconds the Low level protection will be activated High level threshold When the analog goes above this threshold for 3 seconds the Hi...

Страница 6: ...uest Temperature control Sets the control direction for the corresponding System type Temperature cool heat Low temperature protection Alarm Triggers alarm only Lockout Triggers an alarm and shuts dow...

Страница 7: ...e Sleep delay the system will go to sleep See Step 5 12 on the next page for more information on setting the No demand speed Manual speed This is the speed a VSD controlled pump will run in manual If...

Страница 8: ...and destaging functions The no demand is to be set at the speed Hz at which one pump achieves the setpoint against a dead head shut discharge valve If the system is operating as a mains boosting syste...

Страница 9: ...pump has not run for 7 days the pump run for 5 seconds to prevent seizing as long as the system mode is in sleep disabled or inhibit Max run fault protection Alarm Alarm only if a pump runs at the max...

Страница 10: ...Main screen icon where the System Mode will need to be changed after completing Step 6 VSD commissioning Main Screen Alarms Logged Data Trend Plot Setup All Parameters Date Time Diagnostics RUNNING 10...

Страница 11: ...50 50000 rpm Device for 60 Hz mains 50 1750 50000 rpm General motor data Carry out settings as specified by motor nameplate data Note When you enter the motor nameplate data take into account the phas...

Страница 12: ...nominal motor voltage Hz 9908 MOTOR NOM SPEED Defines the nominal motor speed Must be equal to the value on the motor rating plate rpm 9909 MOTOR NOM POWER Defines the nominal motor power Must equal...

Страница 13: ...level step DOL Standby start pressure step Standby start temp step Low level threshold Low pressure threshold Low temperature threshold High level threshold High pressure threshold High temperature t...

Страница 14: ...ns bypass valve enable Sleep delay Top up valve open level Top up valve closed level 4 VSD Level Pressure Temperature VSD full speed level PID Proportional VSD full speed temperature VSD speed at stop...

Отзывы: