Matelec Hydrowhiz FPC-63X20 Скачать руководство пользователя страница 3

3

MATelec Australia reserves the right to alter technical data without notice

Step 5 - Setup

PUMP 1

RUNNING

MENU

Standby Run

PUMP 2

Fault

PUMP 3

Disabled

PUMP 4

Duty Run

SYSTEM MODE:

AUTO

OFF 

MANUAL

5 4 6 k P a

View Faults

3 2 . 5 H z

5.1 - Main Screen

The Main screen is the default screen on the HydroWHIZ HMI. 

Tap on the Menu button to access the Menu screen.

5.2 - Menu Screen

The Menu screen provides access to other screens within the 

HydroWHIZ HMI. Tap on the Date & Time icon to configure the 

controller’s current date and time.

Main Screen

Alarms

Logged Data

Trend Plot

Setup

All Parameters

Date & Time

Diagnostics

RUNNING

10/06/2020 17:50:58

5.5 - Login

Login is required to access the Setup screen. Enter the default 

PIN (2020) then press OK to login in and continue to the Setup 

screen.

RUNNING

Enter PIN:

LOGIN REQUIRED !

10/06/2020 17:50:58

OK

3

2

1

6

5

4

9

8

7

0

CANCEL

2020

5.6 - Warning

If the system mode is in auto, tapping on a setting will bring 

up a Warning screen. Press OK to turn the system off for 

configuration.

RUNNING

MENU

System type
Control output type
Number of pumps
Pump limit
Duty change period

Setup: 1 System Setup

Level
DOL
4
6
60 Mins

Warning

Changing this parameter could result in 

unexpected behaviour.

Switch system to off?

Cancel

OK

5.3 - Set Date & Time

Tap on the date and time to configure them, then press save 

to apply to the controller. This will automatically return to menu.

RUNNING

MENU

Set Time and Date:

Current Time:

10/06/2020 17:52:08

Current Date:

17

   :   

52

   :   

08

10

   :   

06

   :   20

20

Save

5.4 - Menu Screen

Tap on the Setup icon on the Menu screen to access begin 

the controller Setup process. This will bring up the Login screen.

Main Screen

Alarms

Logged Data

Trend Plot

Setup

All Parameters

Date & Time

Diagnostics

RUNNING

10/06/2020 17:50:58

 

 

Содержание Hydrowhiz FPC-63X20

Страница 1: ...the control panel is to be used in Domestic Residential applications where specific Wiring Rules in respect of electrical supply protection may apply it is the responsibility of the installing electri...

Страница 2: ...have internal filters to reduce the amount of distortion however in some applications additional filtering may be required If additional harmonic filtering is required to meet site specifications this...

Страница 3: ...een RUNNING Enter PIN LOGIN REQUIRED 10 06 2020 17 50 58 OK 3 2 1 6 5 4 9 8 7 0 CANCEL 2020 5 6 Warning If the system mode is in auto tapping on a setting will bring up a Warning screen Press OK to tu...

Страница 4: ...ype Number of pumps Pump limit Duty change period Setup 1 System Setup Level VSD 4 6 60 Mins RUNNING Current MENU 3 2 1 6 5 4 9 8 7 0 CANCEL OK 60 Mins Duty change period RUNNING MENU System type Pres...

Страница 5: ...w level threshold When the analog goes below this threshold for 3 seconds the Low level protection will be activated High level threshold When the analog goes above this threshold for 3 seconds the Hi...

Страница 6: ...uest Temperature control Sets the control direction for the corresponding System type Temperature cool heat Low temperature protection Alarm Triggers alarm only Lockout Triggers an alarm and shuts dow...

Страница 7: ...e Sleep delay the system will go to sleep See Step 5 12 on the next page for more information on setting the No demand speed Manual speed This is the speed a VSD controlled pump will run in manual If...

Страница 8: ...and destaging functions The no demand is to be set at the speed Hz at which one pump achieves the setpoint against a dead head shut discharge valve If the system is operating as a mains boosting syste...

Страница 9: ...pump has not run for 7 days the pump run for 5 seconds to prevent seizing as long as the system mode is in sleep disabled or inhibit Max run fault protection Alarm Alarm only if a pump runs at the max...

Страница 10: ...Main screen icon where the System Mode will need to be changed after completing Step 6 VSD commissioning Main Screen Alarms Logged Data Trend Plot Setup All Parameters Date Time Diagnostics RUNNING 10...

Страница 11: ...50 50000 rpm Device for 60 Hz mains 50 1750 50000 rpm General motor data Carry out settings as specified by motor nameplate data Note When you enter the motor nameplate data take into account the phas...

Страница 12: ...nominal motor voltage Hz 9908 MOTOR NOM SPEED Defines the nominal motor speed Must be equal to the value on the motor rating plate rpm 9909 MOTOR NOM POWER Defines the nominal motor power Must equal...

Страница 13: ...level step DOL Standby start pressure step Standby start temp step Low level threshold Low pressure threshold Low temperature threshold High level threshold High pressure threshold High temperature t...

Страница 14: ...ns bypass valve enable Sleep delay Top up valve open level Top up valve closed level 4 VSD Level Pressure Temperature VSD full speed level PID Proportional VSD full speed temperature VSD speed at stop...

Отзывы: