 MASTERBUS 

FUNCTIONS 

 

EN / Digital DC 10x10A / October 2010

 15

 

5.7 

MASTERBUS LOGICAL BLOCKS 

The Digital DC features 

logical block

 configuration to 

enable installing devices that need logical 
conditions. In this case the logical blocks are used 
as source in the MasterBus event configuration. 
Four logical blocks are available with the Digital DC 
10x10A.  

 

See figure 14. A logical block has three sources and 
one result. The result of the first logical block can be 
a source for the second block, see figure 15.  
 

 

5.7.1 Logical 

functions 

The table below shows the block input (three 
sources) and the corresponding output using the 
functions Disabled, AND, OR, XOR and NAND, 
NOR, NXOR.  
AND is true when 

all

 

inputs are true; 

OR is true when 

at least

 

one

 input is true; 

XOR is true when 

an odd number 

of inputs is true. 

NAND is true when 

not all

 inputs are true; 

NOR is true when 

no

 input is true; 

NXOR is true when 

an even number 

of inputs is 

true.  
The results are True (1) or False (0). The function 

Disabled

 must be selected when the logical block is 

not used. 
 

5.7.2 

Logical truth table 

For each of the three logical block sources, one of 
next options can be chosen: 

 

True (1) and False (0) are fixed values in case 
the source is not in use, 

 

All channels 1 to 10; switched On =1, Off =0. If 
the channel is not in use, it sais “Do not use”, 

  Logical Block 1 to 4. This means the logical 

block can also be chosen as source for itself, 
which is not without risks. 

 

NOTE 
For correct logical functioning, an unused 
source must be set to True (1) or False (0). 

 

 
 

 

Sources 

 

 

 

 

Function 

 

 

B

 

C

 

Disabled 

AND 

OR 

XOR 

NAND 

NOR 

NXOR 

 

 

5.7.3 Configuration 

explanation 

Log. Block 

Function 

Source 1 

Source 2 

Source 3 

Result description 

# 1 

AND 

Channel 1 

Channel 3 

True 

Only if Channel 1 

AND

 3 are enabled, 

Logical Block 1 is TRUE. 

# 2 

OR 

Logical 
Block 1 

Channel 8 

False 

Only if Logical Block 1 is TRUE 

OR

 

channel 8 is enabled, Logical Block 2 
is TRUE. 

 

Figure 15:  
Sequential logical blocks 

1

2

2A

2B

2C

1A

1B

1C

1

1A

1B

1C

Figure 14: Logical block 

Содержание Digital DC 10x10A

Страница 1: ...tal DC 10x10A MasterBus DC Switching Device MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www Mastervolt com Copyright 2010 Mastervolt v 1 6 Octob...

Страница 2: ...atus signal MasterBus menus Monitoring menu History menu to keep track of data Configuration menu to enter Digital DC 10x10A settings Alarm menu which shows an Overload and No Load situation of a chan...

Страница 3: ...ions 12 5 4 Wire check 13 5 5 Event configuration 14 5 6 MasterBus Event data 14 5 7 MasterBus logical blocks 15 5 8 Dimming 18 5 9 Event examples Switches 18 6 INSTALLATION 19 6 1 Things you need for...

Страница 4: ...his manual at a secure place 1 2 GUARANTEE SPECIFICATIONS Mastervolt guarantees that this unit has been built according to the legally applicable standards and specifications Should work take place wh...

Страница 5: ...other than mentioned in point 2 is not considered to be consistent with the intended purpose Mastervolt is not liable for any damage resulting from the above 2 3 ORGANIZATIONAL MEASURES The user must...

Страница 6: ...Bus position MasterBus controls up to 10A of the output Manual override Always On Hardware fused Manual override Always Off WARNING Manual Override overrides light voltage settings refer to sections 5...

Страница 7: ...ntrol of the connected devices Mastervolt offers a wide range of panels which show full status information of your electrical system at a glance and a push of a button Three different panels are avail...

Страница 8: ...network Do not make ring networks The electric power for the network is supplied by the connected MasterBus devices At least one device in the network should have powering capabilities see specificat...

Страница 9: ...k has dropped below 10V 20V in a 12V 24V system for more than 30 seconds an alarm will be raised The alarm stops as soon as the battery voltage is higher than 11 22 V in a 12 24 V system for more than...

Страница 10: ...ting see section 3 2 Application navigation lights and ceiling lights 5 2 3 Light 24V See light 12V now for 24V lighting At a voltage supply of 12V the Light 24V mode is not convenient 5 2 4 Switched...

Страница 11: ...low value can be set in this mode See also section 5 3 8 5 2 10 Always On In Always On the channel does not switch off provided the hardware fuse current is not exceeded Application radio memory refri...

Страница 12: ...DC was switched Off Disabled channel is not enabled power up Last Off On Last Disabled Intensity Voltage as percentage of the maximum output voltage 100 0 100 Maximum voltage Fixed maximum channel out...

Страница 13: ...ch Convenient are the Switch Input 3 or 4 with LED buttons The Digital DC is able to illuminate a button LED when the load is switched On and it is working correctly This is possible only after config...

Страница 14: ...vice you chose The command can be a section of the device to perform a task for example Channel 1 if the Digital DC is the target Select Selectable targets are system dependent Event 1 data Data trans...

Страница 15: ...e function Disabled must be selected when the logical block is not used 5 7 2 Logical truth table For each of the three logical block sources one of next options can be chosen True 1 and False 0 are f...

Страница 16: ...ht until it reaches the end switch When the end switch is closed 1 the drive must stop Shown are three situations The roof is in open position the end switch is open 0 The roof is being closed the end...

Страница 17: ...Function Source 1 Source 2 Source 3 Result description AND Close roof End sw open True Only if the motor switch is on Close roof AND the End switch is open Roof is closed is TRUE In the next event Roo...

Страница 18: ...Off 0 5 sec Dimming till button release 5 9 EVENT EXAMPLES SWITCHES 5 9 1 Event example 1 Main switch In this example the main system switch Switch 4 disables two Digital DC s Event configuration exam...

Страница 19: ...se isolated tools Materials Digital DC 10x10A Up to ten fuses together maximum 100A per Digital DC See section 3 2 10 2 fuses 15A included see figure 1 MasterBus cable Terminator for MasterBus One tra...

Страница 20: ...n MasterBus power is needed 1 DC In positive line 2 DC In negative line 3 Hardware fuses with two positions each 4 DC Output 1 5 Positive at the left Negative at the right For connecting the cables se...

Страница 21: ...Digital DC input 6 7 MASTERCONNECT The Digital DC 10x10A belongs to the MasterConnect range These devices link to each other on the DC connectors directly by pushing them together and bolt them See f...

Страница 22: ...on is pressed The reading light can now be switched On and Off by pressing the button shortly If configured long button presses let the light grow and dim alternately 7 2 SYSTEM EXAMPLE 1 CAMPER Figur...

Страница 23: ...Off means the channels outputs are disabled except for the Always On outputs These outputs see also section 3 2 will stay active even when the Digital DC is disabled useful for a radio memory or refr...

Страница 24: ...mble MasterBus cables Delivery includes 100m 330ft UTP cable 50 pcs modular jacks and crimping tool 77050100 100m 330ft MasterBus cable 77050200 50 pcs MasterBus connectors 77030900 Digital Input 7703...

Страница 25: ...ide the 12V light voltage will change to the system voltage this can be 24V Make appropriate settings and change fuse position to Normal Position Wrong output voltage measured in one channel of Digita...

Страница 26: ...e Digital DC 10x10A Unlimited MasterBus powering capacity Yes high powering Power consumption off board situation 2 mA 12V 2 mA 24V Communication isolation Galvanic Software layer MasterBus proprietar...

Страница 27: ...7020400 Digital DC 10x10A Is in conformity with the provision of the EC EMC directive 89 336 EEC and amendments 92 31 EEC 93 68 EEC The following harmonised standards have been applied Generic emissio...

Страница 28: ...Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 Email info Mastervolt com...

Отзывы: