58
Grid Volt Min
Freq Max
High INV frequency
GRID Freq Max
Freq Min
GRID Low Voltage Protection Point
Press UP/DOWN to adjust the input figure.
Press Enter to confirm the input.
Interface
Description
-GRID MIN-
INPUT:
170V
Enter option 1 to adjust the maximum frequency of the INV.
Enter option 2 to adjust the maximum frequency of the
grid.
Interface
Description
-FREQ MAX-
1: INV-MAX
2: GRID MAX
INV Over Frequency Protection Point
Press UP/DOWN to adjust the input number.
Press ENTER to confirm the input and enter restart
interface.
Press ESC to cancel the input and return to Operational
parameters interface.
The value ranges between 50.5 and 55, which varies with
different standards.
Interface
Description
-INV FREQ HIGH-
INPUT:
52.0
UNIT:
Hz
Value range
(50.5 ~ 55)
GRID Over Frequency Protection Point
Press UP/DOWN to adjust the input figure.
Press Enter to confirm the input.
Interface
Description
-GRID MAX-
INPUT:
53.5Hz
Enter option 1 to adjust the minimum frequency of the INV.
Enter option 2 to adjust the minimum frequency of the grid.
Interface
Description
-FREQ MIN-
1: INV MIN
2: GRID MIN
User Manual
59
Low INV frequency
GRID Freq Min
OVER VOLT
OVER VOLT ENABLE
OVER VOLT START
INV Low Frequency Protection Point
Press UP/DOWN to adjust the input figure.
Press Enter to confirm the input and enter restart interface;
Press ESC to cancel the input and return to peration
parameters interface.
The value ranges between 45 and 49.8, which varies with
different standards.
Interface
Description
-INV FREQ LOW-
INPUT:
UNIT:
Hz
Value range
(45 ~ 49.8)
GRID Low Frequency Protection Point
Press UP/DOWN to adjust the input figure.
Press Enter to confirm the input.
Interface
Description
-GRID MIN-
INPUT:
50.5Hz
Enter the option 1 to enable or disable the function that the
power of inverter derates when voltage is too high.
Enter the option 2 to adjust the exact value of the voltage
when power starts to derate.
Interface
Description
-OVER VOLT-
1: ENABLE
2: VOLT
Derate power when Voltage over.
The default option is enable.
Interface
Description
-OVER VOLT-
1: DISABLE
2: ENABLE
Press UP/DOWN to adjust the input figure.
Press Enter to confirm the input.
Interface
Description
-OVER START-
INPUT:
264V