![Master Power GreenE 3.68K Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/master-power/greene-3-68k/greene-3-68k_installation-operation-and-maintenance-manual_1737618025.webp)
7. START-UP delay
8. CEI SPI CTRL
9. GFCICHK ENB
10. DISC MODE
11. DISC HG DEPTH
2. Input mode
3. ZERO EXPORT
4. DRM enable
5. Backup enable
6. Remote Control enable
48
Setup of PV Input mode.
The factory setting by default is standalone mode.
When parallel input is set to be stand-alone mode, PV
power will be imbalanced.
Interface
Description
-INPUT MODE-
1: INDEPENDANT
2: PARALLEL
3: CV
Back-flow-prevention function.
Default option is disabling.
Interface
Description
-ZERO EXPORT-
1: DISABLE
2: ENABLE
It is enabled when BACKUP load needs power.
Default option is disabling.
Interface
Description
-DRM EXPORT-
1: DISABLE
2: ENABLE
It is enabled when BACKUP load needs power.
Default option is enabling.
Interface
Description
-EPS EXPORT-
1: DISABLE
2: ENABLE
The power switch of the machine can be realized through
remote control.
Default option is disabling.
Interface
Description
-REMOTE CTRL-
1: DISABLE
2: ENABLE
User Manual
49
The input value ranges from 20 to 300, which varies with
different standards.
Interface
Description
-START-UP DELAY-
INPUT:
30
UNIT:
SEC
CEI SPI CTRL: (1. Disable 2. Enable)
When the DRM signal is enabled, this is used as a local
signal. When the DRM signal is enabled, when the CEI SPI
Ctrl is enabled, the frequency range is 50.2Hz ~ 49.8Hz.
When the CEI SPI Ctrl is disabled, the frequency range is
51.5Hz ~ 49.8Hz.
Interface
Description
-CEI SPI CTRL-
1: DISABLE
2: ENABLE
GFCICHK ENB (1. Disable 2. Enable)
PV leakage protection enable.
Interface
Description
-GFCICHK ENB-
1: DISABLE
2: ENABLE
DISC MODE (1. Rated Power, 2. Load Prio)
This is only for test.
Interface
Description
-DISC MODE-
1: RATED POWER
2: LOAD PRIO
Discharge depth enable (1. Disable 2. Enable) : enable
discharge depth. When the SOC of the battery is less than
the discharge depth set by 1 -, the battery will no longer
discharge, and alarm the low capacity of w13 battery. Set
the discharge depth in the battery parameter setting.
Interface
Description
-DISCHGDEPTH-
1: DISABLE
2: ENABLE
User Manual