6. BAT END VOLT
7. BAT WAKE-UP
Battery wake up enable
Bat Wake Time
This function is used to set the discharge cut-off voltage.
When select the battery type as LFP, the default value is
43.0V and the setting range is between 40.0V to 48.0V.
Interface
Description
-BAT END VOLT-
INPUT:
43.2
UNIT:
V
Enter the option 1 to enable or disable the Function.
Enter the option 2 to adjust the value of the time.
Interface
Description
-BAT WAKE-UP-
1: ENABLE
2: TIME
Battery wake-up enable setting.
The default option is ENABLE.
Interface
Description
-BAT WAKE-UP-
1: ENABLE
2: DISABLE
Press UP/DOWN button to increase or decrease the input
figure.
Press Enter button to move cursor backward, confirm input
and return to battery parameters interface.
Interface
Description
-Bat Wake Time-
INPUT:
060min
User Manual
55
4.3.3 Grid standard
4.3.4 Operation parameters
1. Reactive mode
Press UP/DOWN button to move corresponding options.
Here are eleven countries for selection, including China,
Germany, Australia, Italy, Spain and U.K. (for detail, refers
to table 9.1).
Press ENTER button to confirm the selection and enter
restart interface.
Press ESC button to cancel the selection and return to
setting interface.
Interface
Description
-GRID STD-
1: CHN
2: GER
3: AUS
4: ITA
…
21: CHILE
22: Local 23:60Hz
Press UP/DOWN button to move corresponding options.
Press Enter to enter the selected menu.
Press ESC button to return to setting interface.
Options include reactive compensation mode, grid power,
discharge/charge power, low/high grid power, low/high
grid voltage, low/high grid frequency, VoltOverStart and
FreqOverStart (see from
❶
to
❾
)
Interface
Description
-RUN SETTING-
1: REACT POWER
2: GRID POWER
3: VOLT MAX
5: VOLT MIN
6: FREQ MAX
7: OVER VOLT
8: UNDER VOLT
9: OVER FREQ
10: UNDER FREQ
11: REACT RESP
12: VRT_ENABLE
13: POW SI RATE
Press UP/DOWN button to move corresponding options;
Press Enter to confirm the input and enter power factor
setting interface.
(select 2, press Enter to confirm input and enter reactive
power interface; Select 3, 4, the corresponding mode will
be selected and return to the parameter setting interface.)
Press ESC button to cancel the input and return to
operation parameters interface.
Interface
Description
-REACT MODE-
1: POWER FACTOR
2: REACT POWER
3: QU CURVE
4: QP CURVE
User Manual