Model: LC5296-AT /LC5248E-AT/LC5296V-AT
masibus
Doc. Ref. no. : - m61C/om/301
Issue no. 13
User’s Manual
Page 23 of 44
2
TC K
-200 to 1372 °C
3
TC T
-200 to 400 °C
4
TC B
450 to 1800 °C
5
TC R
0 to 1768 °C
6
TC S
0 to 1768 °C
7
RTD.1
-199.9 to 850.0 °C
8
RTD
-200 to 850 °C
9
0-5 V / 0-20 mA*
-1999 to 9999
10
1-5 V / 4-20 mA*
11
0-10 V
*
Use external 250ohms,0.1% for current input
ZERO
(
zero
)
Zero
Automatically change to the Input Lower Range with
changing of Input Type
(Refer Above Table)
Can be set to any value within the Input Range & less
the SPAN Value.
-200
(If TC E)
SPAN
(
span
)
Span
Automatically change to the Input Higher Range with
changing of Input Type
(Refer Above Table)
Can be set to any value within the Input Range &
greater the ZERO Value.
1000
(If TC E)
OFST
(
ofst
)
offset
Offset Value
Input type
range
RTD/ Thermocouple
-100.0°C to +100.0°C
Linear
-1000 to +1000
0.0
FLTR
(
fltr
)
Filter
Enable or Disable Filter for PV Input
yes
/
no
0 : NO
1 : YES
1
(YES)
TSP1
(
tsp1
)
Type of Set Point
Set Type of Set Point
l-on
/
H-on
0 : L-ON (Lower ON)
1 : H-ON (Higher ON)
Refer ON-OFF Control on Page:32
0
(L -O N)
Control Type
(COP) is ON-OFF.
OPES
(
opes
)
OPEN Sensor
Status
Set Control O/P & Retransmission state when Input
OPEN condition.
down
/
up
0 : DOWN
1 : UP
Refer Page:44
1
(UP )
RD1
(
rd1
)
Relay Delay
(For Relay-1)
Relay Delay is amount of time (in sec), that Relay will
wait before getting ON after the ON condition occurs.
1 to 99 sec
1 sec
Control Type
(COP) is ON-OFF.
HY-1
(
Hy-1
)
Hysteresis
–
1
(For Relay-1)
Hysteresis Value (in °C) for Relay-1 during ON-OFF
type Control.
1 to 100
TC & RTD Input
0.1 to 100.0
RTD.1 Input
1 to 100
Linear Input with DP=0
0.1 to 100.0
Linear Input with DP=1
0.01 to 10.00
Linear Input with DP=2
0.001 to 1.000
Linear Input with DP=3
1
Control Type
(COP) is ON-OFF.