Model: LC5296-AT /LC5248E-AT/LC5296V-AT
masibus
Doc. Ref. no. : - m61C/om/301
Issue no. 13
User’s Manual
Page 11 of 44
4. TERMINAL CONNECTIONS
4.1 LC5296-AT
Fig 4.1: Terminal Connection Detail of LC5296-AT
Terminal No.
Description
2 (NC1)
3 (NO1)
4 (C1)
For Relay-1 potential free Contacts (Use 230V -2A load)
PID/ On-Off Control o/p.
Alarm-1 o/p, if output type is Linear.
Forward Relay, if output type is Motor position control
without slide wire feedback
Terminal 3,4:- SSR Pulse o/p.
5 (NC2)
6 (NO2)
7 (C2)
For Relay-2 potential free Contacts (Use 230V -2A load)
Alarm-2 o/p.
Reverse Relay, if output type is Motor position control
without slide wire feedback
8 (Earth)
Earth Connection
9 (N/-)
10 (L/+)
Power Supply Input
11 (LPS+)
24VDC Loop power supply
Terminal 14 is ground Reference.
12
For RTD Input Only
(Three wire Compensation).
13 (TC+/ V+)
14 (TC- / V- / LPS-)
For Thermocouple, RTD & Linear Input
17 (Linear /RTR1+)
18 (Linear Output-/RTR1-)
For Retransmission-1 output
Linear type Control Output
19 (D+/ RTR2+)
20 (D- / RTR2-)
For Retransmission-2 output
Modbus-RTU Communication Output