8. ALARM OUTPUT
For all Alarm outputs there are five settings. (As shown in configuration mode Menu)
Set Value (in run mode)
Type
Hysteresis(Dead band)
Direction (Normal/Fail safe)
Delay
SET VALUE: Alarm set point
8.1 ALARM TYPES
Various alarm operations are shown in the reference figure.
ALARM
TYPE
NO
Display
message
ALARM TYPE
Note
0
none
None
NO operation available
1
Pv
.d
.H
Deviation High alarm
Ref figure 3
2
Pv
.d
.l
Deviation Low alarm
Ref figure 4
3
Pv
.d
.r
Deviation High & Low range alarm
Ref figure 5
4
Pv
.d
.b
Deviation High & Low Band alarm
Ref figure 6
5
Pv
.a
.H
Absolute value High alarm
Ref figure 1
6
Pv
.A
.L
Absolute value Low alarm
Ref figure 2
7
SP
.A
.H
Absolute value set point high alarm
Ref figure 7
8
SP
.A
.L
Absolute value set point low alarm
Ref figure 8
9
P
.S
.d
.H
Deviation High alarm with standby
Same as figure 3
10
P
.S
.d
.L
Deviation Low alarm with standby
Same as figure 4
11
P
.S
.d
.r
Deviation High & Low range alarm with standby Same as figure 5
12
P
.S
.d
.b
Deviation High & Low limit alarm with standby
Same as figure 6
13
P
.S
.A
.H
Absolute value High alarm with standby
Same as figure 1
14
P
.S
.A
.L
Absolute value Low alarm with standby
Same as figure 2
15
PV
.-E
.
PV error(OPEN/OVER/UNDER)
Note 1
NOTE-1:
The fault diagnosis output turns on in case of input burnout (PV) failure.