6.9 S
CHEDULED
MAINTENANCE
TABLE
The check indicated in this section can be carried out either
by the workshop or by machine user.
Check for lube oil leakage
daily
Check electrolyte in batteries (1) (2)
daily
Check for fuel oil leakage
daily
Check air cleaner for clogging (1)
200 hours
CHECKS
REGULARITY
Check oil level sump
daily
Check the fuel level and refill
daily
The routine maintenance operations, must be carried out by
qualified personnel who have the appropiate equipment and
protections.
Adjust valve clearance (2)
400 hours
Calibrate injectro and possible nozzles replacement (2)
400 hours
Change the air filter (2)
400 hours
Change oil filter (2 - 4)
400 hours
Change fuel filter (2)
400 hours (3)
ROUTINE MAINTENANCE
#
REGULARITY
Change engine oil (4 - 5 - 6)
300 hours
(1) = The regularity of these operations can vary depending
on engine use and the ambient conditions in which
it operates.
(2) = These operations must be carried out every 6 months
even when the specified operating hours have not
been reached.
(3) = Maximum period, with high-quality fuel; it may vary
depending on fuel .
(4) = Change after the first 50 hours of service (running-in)
(5) = If fuel with a sulphur content of more than 0.5% in
used, the engine oil change intervals must be halved.
(6) = These operations must be carried out every 6 months
even when the specified operating hours have not
been reached.
6.10 P
ERIOD
OF
INACTIVITY
If the generator is not to be used for a long period of time,
the following operations must be carried out.
• Completely empty out the fuel tank.
• Change the engine oil.
• Clean the air filter.
• Disconnect the battery cables. We recommend you
recharge the battery every month in order to prevent it
from going completely flat which, sometimes,
compromises its integrity.
• Clean the outside of the generator, removing all dust
and impurities.
• Cover the generator with a nylon sheet and store it in
horizontal position in a dry and ventilated place.