Maruson | Tacoma 1KVA-3KVA User Manual
22
1)
The Fault / Warning icon
“ ” will appear on-screen and alarm will beep
continuously if there must a fatal error detected by the UPS and is operating
abnormally.
2)
If fault happens, please notes and record what the display shows, the display
information is very important for troubleshooting. Check the Troubleshooting
table in this manual to find a solution or further instructions.
3)
Please check your equipment, wiring, ventilation, mains, battery and so on
after the fault happens. Don’t try to turn on the UPS again before find out the
reason. If the trouble can’t be shooting, please contact the distributor or
service people.
4)
In case of an emergency, pull the EPO Tab to cut off the connection from
mains / external battery / output immediately to avoid more risk or danger.
4.12.
CONTROLLED OUTLET GROUPS (2KVA/3KVA)
2KVA and 3KVA models have controlled outlet group function to prioritize battery
power for mission-critical equipment. If enabled, Segment 1 outlets are always
on while Segment 2 outlets can be set to automatic on / off functions based on
your settings during Battery Mode. This function is set via software and using the
RS232 communication method.
Send command
“PET” enables this function and send command “PDT” disables
this function. The default setting is set to disable.
If this function is enabled, Segment 2 outlets will be automatically shut off after
10 seconds of the UPS switching to Battery Mode and switch back to supplying
power after 1 minute when the UPS returns to Line Mode or Bypass Mode. By
cutting off power to Segment 2, Segment 1 has the maximum battery backup
time available. Connect mission-critical equipment to sockets in Segment 1 and
non-mission critical equipment to sockets in Segment 2.
4.13.
CHANGE SETTINGS BY LCD CONTROL PANEL
The UPS must be in Standby Mode or Bypass Mode to make any setting
changes. While in Standby Mode or Bypass Mode, hold the Select button for 2
seconds for a tool icon
“ ” to appear. Release the Select button. Press Select
for the different setting options to start cycling through on screen. When the
setting you want to change appears, release the Select button and press the
Enter button to save.
Settings that can be changed include the output voltage (100Vac, 110Vac,
115Vac, 120Vac, or 127Vac), frequency in Battery Mode (50Hz or 60Hz), bypass
state (bypass enabled or bypass disabled), UPS mode (ECO or UPS Mode).
The LCD screen will cycle through these setting options as long the Select
button is pressed. Press Enter for 2 seconds to save a setting. The UPS will exit
Settings after 30 seconds of inactivity.