Maruson | Tacoma 1KVA-3KVA User Manual 

 

19 

4.

 

OPERATION 

4.1.

 

TURN ON THE UPS WITH MAINS (AC SOURCE) 

1)

 

Plug the UPS to an AC power source. The LCD will display either Standby 
Mode or Bypass Mode.   

Note:

 If the UPS has been set to Bypass Output Enabled, the output socket 

will receive the voltage directly from mains after you turn on the input 
breaker, and the LCD display “bYPA”, or else the output socket will not have 
the voltage and the LCD will indicate 

“STbY”.   

Note:

 In Bypass Mode, the connected equipment is not protected. You 

should set the UPS to Line Mode to protect connected equipment. 

2)

 

Press the ON Button for 2 seconds to change to Line Mode. The UPS will 
take up to 15 seconds to test the UPS first before switching over to Line 
Mode and start supplying power to connected equipment.   

Note:

 In the event of an outage, the UPS will switch over to Battery Mode 

automatically if it was in Line Mode. Once power returns, the UPS will 
automatically switch back to Line Mode. If the battery runs out and UPS 
automatically shuts off, the UPS will automatically restart once AC input 
power returns. 

4.2.

 

START THE UPS WITH BATTERY POWER (DC COLD START) 

This UPS has cold start function to supply power from the DC source (battery) 
without AC source as long as battery levels and battery voltage levels are 
sufficient. 

1)

 

Press the ON button for 2 seconds. After a few seconds, the UPS will power 
on in Battery Mode and supply power to the outlets.   
2)

 

While the UPS is in Battery Mode, an audible alert will beep according to 

the battery level. Audible alerts can be temporarily muted by pressing the ON 
button once. Once the AC power source returns, audible alerts will be 
enabled again for the next time the UPS is in Battery Mode.   

4.3.

 

CONNECT EQUIPMENT TO UPS 

Turn on connected equipment after the UPS has powered on for a soft start.   

1)

 

Turn on each connected equipment at a time instead of all at once. The Load 
Level grids will indicate the load capacity in Line Mode. 

2)

 

If it is necessary to connect the inductance load such as a printer to the UPS, 
the start-up power should be considered for calculating the capacity of the 
UPS, because the power consumption is too big when this kind of load is 
started. 

3)

 

If the UPS is overloaded, all Load Level grids will display, LCD will switch 
between 

“OVLd” and “LINE” every 2 seconds, and the audible alert will beep 

twice per second.   

4)

 

If the UPS is overloaded, some equipment must be turned off or offloaded 
immediately. It is recommended that the total load connected to the UPS be 

Содержание TAC-LV1K

Страница 1: ...ion All rights reserved Any mention of third party names and trademarks the property of their respective holders Use of them does not imply any affiliation with or endorsement by them The information...

Страница 2: ...de 12 3 2 8 Fault Mode 12 3 3 DISPLAY INTERFACE 13 3 3 1 Control Panel 13 3 3 2 LCD Module 13 3 4 CONTROL PANEL 14 3 5 REAR PANEL RENDERING 15 3 6 OUTPUT HARDWIRE 2KVA 3KVA MODELS 17 3 7 COMMUNICATION...

Страница 3: ...LCD WARNING CODE 25 5 2 LCD FAULT CODE 26 5 3 ADDITIONAL TROUBLESHOOTING CONDITIONS 26 6 MAINTENANCE 27 6 1 BATTERY MAINTENANCE 27 6 2 BATTERY REPLACEMENT 28 6 2 1 UPS External Battery Banks EBB Batte...

Страница 4: ...uctive contaminants Keep away from direct sunlight heat corrosive gasses dust and water For UPS with hardwired input the connection to the branch circuit mains must be performed by a licensed electric...

Страница 5: ...VA 15A 240V 16A 2 pole 12AWG 3 3 2000VA 20A 240V 30A 2 pole 12AWG 3 3 3000VA 30A 240V 40A 2 pole 10AWG 5 3 CAUTION Risk of electric shock Do not hardwire equipment to the 2KVA 3KVA output terminal whi...

Страница 6: ...MAINTENANCE CAUTION Risk of electric shock The UPS operates with hazardous voltages Maintenance repair or battery replacement should be carried out only by qualified maintenance personnel only CAUTIO...

Страница 7: ...part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote...

Страница 8: ...avoid risk of electric shock and fire hazards Note Any equipment with motors must take into consideration the in rush current as part of the overall UPS capacity WARNING It is recommended to use a 10A...

Страница 9: ...t specifically made for your UPS will void all warranties If there isn t any specified external battery cable please prepare the external battery cable that should be able to carry the current of 42A...

Страница 10: ...ife help charge the battery based on battery capacity conditions and sends a helpful warning before the end of battery lifecycle so you know when it is time to replace 3 1 OPERATION FLOW 1 The UPS rec...

Страница 11: ...ay again STRING CODE DESCRIPTION LINE Line Mode Normal UPS is operating normally and supplying power to connected equipment STbY Standby No Output Mode UPS is powered but not supplying power to the so...

Страница 12: ...ility power battery level UPS output and the load level The LINE status indicates the UPS is working in Line Mode This is the recommended mode to operate the UPS in Figure 2 Line Mode 3 2 2 Standby Mo...

Страница 13: ...ill be displayed Note If mains power fails while in Bypass Mode the UPS will not switch over to Battery Mode Connected equipment will not have battery backup protection in this mode or be protected fr...

Страница 14: ...an Figure 5 Battery Mode 3 2 5 Battery Test Mode In this mode the UPS will stop the AC DC section and discharge the battery briefly while mains input is normal If the UPS detects a battery error it wi...

Страница 15: ...e to operate the UPS normally or completely shut off the UPS from the control panel until the EPO status is deactivated by reinserting the EPO Tab To restart the UPS after triggering EPO Mode 1 Ensure...

Страница 16: ...Indicates input voltage frequency values which are displayed alternately Output Measurements Indicates output voltage frequency values which are displayed alternately Mains Power Indicates input powe...

Страница 17: ...n for 1 second to temporarily disable audible alerts Once mains power is restored audible alerts will be reset to enabled Cold start To start the UPS in Battery Mode during a power failure press and h...

Страница 18: ...the output voltage frequency bypass disable enable and ECO or Normal Mode Confirm your selection by pressing Enter Enter If the UPS system is Standby No Output or Bypass Mode confirm settings selecti...

Страница 19: ...Maruson Tacoma 1KVA 3KVA User Manual 16 Figure 9 TAC LV2K 2KVA Figure 10 TAC LV3K 3KVA...

Страница 20: ...emotely monitor control and communicate with the UPS Battery Connector Add an optional external battery bank EBB for additional battery runtime during power outages Connect up to 3 EBBs Fuse 3KVA mode...

Страница 21: ...2 Plug one end to the computer and other end to the UPS Pin assignment and description of DB 9 connector Pin Definition 2 TXD output Transmits data 3 RXD input Receives data 5 GND Ground 3 10 REMOTE N...

Страница 22: ...cold start function to supply power from the DC source battery without AC source as long as battery levels and battery voltage levels are sufficient 1 Press the ON button for 2 seconds After a few sec...

Страница 23: ...extended time make sure to recharge the batteries every 3 months to maintain battery lifespan 4 5 DISCHARGE THE BATTERIES 1 When the UPS is in Battery Mode the alarm will beep based on the battery cap...

Страница 24: ...t before you shut down the UPS system to prolong the lifespan of connected equipment 4 8 TURN OFF THE UPS IN BATTERY MODE DC SOURCE 1 To turn off the UPS in Battery Mode press the OFF button for 2 sec...

Страница 25: ...nd command PET enables this function and send command PDT disables this function The default setting is set to disable If this function is enabled Segment 2 outlets will be automatically shut off afte...

Страница 26: ...Hertz Hz or cycles per second of the UPS output power while in Battery Mode Select either 50Hz or 60Hz NOTE In Line Mode and ECO Mode the UPS frequency is synchronized to the input frequency it cannot...

Страница 27: ...F button is pressed for 2 seconds In Standby Mode the UPS will not supply power to connected equipment 4 13 4 Example of Settings Change Here is an example how to change the output voltage from 110Vac...

Страница 28: ...n CHGF Charger failed UPS charger board will not charge the batteries anymore Contact your local authorized dealer or Maruson to replace the charger board TEPH Internal temperature too high Check the...

Страница 29: ...high Contact your local authorized dealer or Maruson ISFT Inverter failed Internal fault Contact your local authorized dealer or Maruson OVLd Overload Remove non critical loads until total capacity i...

Страница 30: ...d Check the LCD for any additional status information Check the battery connections Start a battery test Contact your local authorized dealer or Maruson support if above solutions do not resolve issue...

Страница 31: ...y voltage rating marked on the rear panel before replacing any batteries Using the wrong battery voltage may cause permanent damage of the UPS EBB Note Never connect or disconnect EBBs when the UPS is...

Страница 32: ...13 F 5 C to 45 C 7 3 DISPOSAL Contact your local recycling or hazardous waste center for information on proper disposal of spent batteries and waste electric or electronic equipment WEEE This product...

Страница 33: ...1 Efficiency Line Mode 89 Battery Mode 86 86 86 ECO Mode 95 full load with batteries fully charged Transfer Time Line Battery 0ms Inverter Bypass 4ms ECO Battery 10ms Battery Charger 77 F 25 Total Ba...

Страница 34: ...EBB SPECIFICATIONS TAC LV1KBB TAC LV2KBB TAC LV3KBB For Power Ratings 1000VA 2000VA 3000VA Battery Quantity Size 6 12V 7Ah 12 12V 9Ah 12 12V 9Ah Battery Voltage 36Vdc 72Vdc 72Vdc Configuration Tower...

Страница 35: ...ARNING Lead acid batteries battery posts terminals and related accessories can expose you to chemicals including lead and lead compounds which are known to the State of California to cause cancer and...

Страница 36: ...alesperson employee or agent of Maruson is authorized to add to or vary the terms of the warranties By using the Product you agree to the terms of the Limited Warranty The duration of warranty coverag...

Страница 37: ...God leakage or breakage of plumbing harsh chemical action intentional misconduct on the part of the consumer accident dropping the device abuse or other abnormal conditions or unauthorized modificati...

Страница 38: ...ANY DUTY INCLUDING OF GOOD FAITH OR REASONABLE CARE NEGLIGENCE OR LOSS OF DATA ARISING OUT OF THE SALE USE OR INABILITY TO USE OF ANY MARUSON UPS EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES IN...

Отзывы: