6. Non Trip Earth Loop Impedance Test (Ra15mA) @1

Ω 

resolution with PFC

calculation

1)

Connect the red, black and green test leads to P, N+E terminals
respectively.

2)

Turn the dial to the Ra 15 mA        position. Display shows 'RCD' at the top 
centre.

3)

Connect the mains plug to a 230V 50HZ socket outlet, or to the appropriate
conductors on which the test is to be carried out using the croc clips.

4)

Press the

key to select the limit values for contact voltage 50V

(default) or 25V.

5)

Press the yellow             key to start the test.

6

At the end of the test, the instrument beeps twice indicating a positive out
come of the test.  The relevant results are displayed.

PFC is displayed on lower RHS of Display in Amps
Readings below 1

Ω 

are displayed as 1

Ω

Formula for the prospective short circuit current:

I

cc

= U

N

R

a

When U

= phase to earth voltage  

127V if 100V < V

meas  

150V

230V if 150V < V

meas  

265V

This test is carried out at 15mA

10

UL

M

GO

7. PHASE ROTATION/ SEQUENCE

1)

Connect red, black and green test leads to P, N and E (L1, L2, and L3)
terminals respectively.

2)

Turn dial to

position.

3)

Connect the test leads to the conductors on which the test is to be carried
out by using the croc clips.

4)

The following screen is displayed:

5)

Press the 'FUNC' key repeatedly to display the three differential voltages,
L1-2, L2-3, and L3-1 individually.

6)

Press the yellow           key to start the measurement of phase sequence. 
The display must read '123' for correct phase sequence.  This means that
the red test lead (connected to L1 ) is phase no 1.  The black
test lead (connected to L2 ) is phase no 2, and the green test
lead (connected to L3 ) is phase no 3.

If '213' or '132' are displayed, then the phase sequence is incorrect.

11

386V

386V

386V

voltage between
P2+ P3

voltage between
P1+ P2

voltage between
P3+ P1

GO

Содержание VERITEST 2240

Страница 1: ...G Motor Maintenance Equipment G Non trip loop testers G Pat testers Accessories G Phase rotation G Proving units G Socket Testers G Thermometers Probes G Test Leads G Voltage Indicators G Specialist...

Страница 2: ......

Страница 3: ...ads 3 2 LOW continuity test 4 3 M insulation test 5 4 RCD test 6 5 Loop Zs IK 9 6 Non Trip Earth Loop Impedance Test Ra15mA 10 1 resolution with PFC calculation 7 Phase Rotation Sequence 11 8 Instrume...

Страница 4: ...rrent Equipment protected by Double Insulation Class II Caution refer to accompanying documents Caution risk of electric shock 10 OPTIONAL ACCESSORIES Infra red data lead VRTL1 Download software VRSOF...

Страница 5: ...219mA the instrument has a stored value for the resistance of the test leads current supplied by instrument during calibration procedure function selected FUNC GO NON TRIP EARTH LOOP TEST RA15MA Meas...

Страница 6: ...ds Use to adjust time up and down respectively At the end of the test if the resistance value is lower than 5 the instrument beeps twice indicating low resistance The resistance value is displayed on...

Страница 7: ...be adjusted from 10 999 seconds Adjust values using or This test can be used if a minimum measuring time is required UN I n FUNC L S UL M GO 100V 250V 500V 1000V Low resistance 5 seconds 10 seconds 10...

Страница 8: ...on display by O B Press the yellow key twice The instrument injects a current in phase with negative half wave of the voltage indicated on display by 180 FUNC UN I n L S S UL M GO GO 9 SPECIFICATION...

Страница 9: ...ct to the voltage Readings below 1 are displayed as 1 PLEASE NOTE MAN x5 and auto test modes are not available for RCD type A 500mA 8 INSTRUMENT CONNECTION TO PC OR A PRINTER The connection from the V...

Страница 10: ...st passed Please refer to the full user manual for tripping times Press to scroll through the test results RAMP The instrument generates a leakage current growing step by step in a given time interval...

Страница 11: ...Connect the mains plug to a 230V 50HZ socket outlet or to the appropriate conductor by means of the croc clips 4 Press key repeatedly to select P PE P PE is shown 5 Press the yellow key once The inst...

Страница 12: ...nt Icc UN Ra When UN phase to earth voltage 127V if 100V Vmeas 150V 230V if 150V Vmeas 265V This test is carried out at 15mA 10 UL M GO 7 PHASE ROTATION SEQUENCE 1 Connect red black and green test lea...

Отзывы: