4
2. LOW
Ω
CONTINUITY TEST
1)
Connect red & black test leads to P + N terminals respectively.
2)
Turn dial to low
Ω
(continuity setting). Display shows 'LOW
Ω
' at top left.
3)
Select: 'Auto', 'R+', 'R-', 'R+TIMER', 'R-TIMER'. By repeated pressing of
the key. See below for details of individual tests.
If using the timer function, set time using
+ keys
4)
Connect the test leads to the conductors on which the continuity test is to
be carried out.
5)
Press yellow key – The instrument performs the test
Auto:
The instrument carries out 2 measurements. 1x positive polarity and
1 x negative polarity. The instrument displays an average reading of
the two measurements performed.
R+:
The instrument carries out 1 measurement with a positive polarity. I.E.
Red test lead positive.
R-:
The instrument carries out 1 measurement with a negative polarity.
I.E. Black test lead positive
R+TIMER: The instrument carries out 1 measurement with a positive polarity and
an adjustable duration of test. Min 3 seconds, Max 15 seconds. Use
+ to set test duration.
R-TIMER: The instrument carries out 1 measurement with a negative polarity and
an adjustable duration of test. Minimum of 3 seconds, Maximum of
15 seconds.
Use
+
to adjust time up and down respectively.
At the end of the test, if the resistance value is lower than 5
Ω
, the instrument
beeps twice, indicating low resistance. The resistance value is displayed on the
screen.
NB
Cal & Low
Ω
is displayed in the top left of the screen if a lead compensation
value is stored; this value will be applied to any measurement made.
L
S
U
L
M
L
S
U
L
M
L
S
U
L
M
FUNC
GO
AC VOLTAGE:
Electrical Syst Range (V)
Resolution(V)
Accuracy
Single-phase 0 - 265
1
±(2% rdg + 2 dgt)
2 or 3 - phase 0 - 460
1
±(5% rdg + 2 dgt)
FREQUENCY:
Range (V)
Resolution HZ
Accuracy
15.3 - 99.9 Hz
0.1 HZ
±(0.1% rdg + 1 dgt)
LINE IMPEDANCE
(LOOP ZS/IK PHASE TO PHASE OR PHASE TO NEUTRAL)
Test mode
Range
Resolution
Accuracy
(P-P & P-N)
0.03-19.99
Ω
(0.01
Ω
Res)
±(5% rdg + 2 dgt)
20.0-199.9
Ω
(0.1
Ω
Res)
±(5% rdg + 2 dgt)
PSC
1-999A
1.0-20.0KA
Test voltage: V
PN
100V - 265V 50Hz + 0.5 Hz
V
PP
100V - 460V 50Hz + 0.5 Hz
Max peak test current:
100V 3.17A test duration: 80ms
230V 6.64A test duration: 40ms
400V 11.5A test duration: 40ms
Accuracy current measurement: ±10% I
max
Pk
PHASE EARTH IMPEDANCE (LOOP ZS/IK)
Range
Resolution
Accuracy
0.03-19.99
Ω
(0.01
Ω
Res)
±(5%rdg+2dgt)
20.0-199.9
Ω
(0.1
Ω
Res)
±(5%rdg+2dgt)
200-1999
Ω
(1
Ω
Res)
±(5%rdg+2dgt)
PFC
1-999A, 1.0-20.0KA
Max peak test current:
100V 3.17A test duration: 80ms
230V 6.64A test duration: 40ms
Accuracy current measurement: ±10% Imax Pk
Test frequency: VPE
100V - 265V 50Hz +0.5 Hz
17