4

2. LOW 

Ω

CONTINUITY TEST

1)

Connect red & black test leads to P + N terminals respectively.

2)

Turn dial to low 

Ω

(continuity setting). Display shows 'LOW 

Ω

' at top left.

3)

Select: 'Auto', 'R+', 'R-', 'R+TIMER', 'R-TIMER'.  By repeated pressing of
the              key. See below for details of individual tests.

If using the timer function, set time using

+               keys

4)

Connect the test leads to the conductors on which the continuity test is to
be carried out.

5)

Press yellow         key – The instrument performs the test

Auto:

The instrument carries out 2 measurements. 1x positive polarity and
1 x negative polarity. The instrument displays an average reading of 
the two measurements performed.

R+: 

The instrument carries out 1 measurement with a positive polarity. I.E.
Red test lead positive.

R-:

The instrument carries out 1 measurement with a negative polarity. 
I.E. Black test lead positive

R+TIMER: The instrument carries out 1 measurement with a positive polarity and

an adjustable duration of test. Min 3 seconds, Max 15 seconds. Use

+               to set test duration.

R-TIMER: The instrument carries out 1 measurement with a negative polarity and

an adjustable duration of test.  Minimum of 3 seconds, Maximum of
15 seconds.
Use 

+

to adjust time up and down respectively.

At the end of the test, if the resistance value is lower than 5

Ω

, the instrument

beeps twice, indicating low resistance. The resistance value is displayed on the
screen.

NB

Cal & Low 

Ω

is displayed in the top left of the screen if a lead compensation 

value is stored; this value will be applied to any measurement made.

L

S

U

L

M

L

S

U

L

M

L

S

U

L

M

FUNC

GO

AC VOLTAGE:
Electrical Syst Range (V)

Resolution(V)

Accuracy

Single-phase  0 - 265

1

±(2% rdg + 2 dgt)

2 or 3 - phase  0 - 460

1

±(5% rdg + 2 dgt)

FREQUENCY:
Range (V)

Resolution HZ

Accuracy

15.3 - 99.9 Hz 

0.1 HZ

±(0.1% rdg + 1 dgt)

LINE IMPEDANCE 
(LOOP ZS/IK PHASE TO PHASE OR PHASE TO NEUTRAL)

Test mode

Range

Resolution

Accuracy

(P-P & P-N)

0.03-19.99

Ω

(0.01

Ω

Res)

±(5% rdg + 2 dgt)

20.0-199.9

Ω

(0.1

Ω

Res)

±(5% rdg + 2 dgt)

PSC

1-999A 
1.0-20.0KA

Test voltage: V

PN

100V - 265V 50Hz + 0.5 Hz

V

PP

100V - 460V 50Hz + 0.5 Hz

Max peak test current:

100V 3.17A test duration: 80ms
230V 6.64A test duration: 40ms
400V 11.5A test duration: 40ms

Accuracy current measurement: ±10% I

max

Pk

PHASE EARTH IMPEDANCE (LOOP ZS/IK)
Range

Resolution

Accuracy

0.03-19.99

Ω

(0.01

Ω

Res)

±(5%rdg+2dgt)

20.0-199.9

Ω

(0.1

Ω

Res)

±(5%rdg+2dgt)

200-1999

Ω

(1

Ω

Res)

±(5%rdg+2dgt)

PFC

1-999A, 1.0-20.0KA

Max peak test current:

100V 3.17A test duration: 80ms 
230V 6.64A test duration: 40ms

Accuracy current measurement: ±10% Imax Pk
Test frequency: VPE

100V - 265V 50Hz +0.5 Hz

17

Содержание VERITEST 2240

Страница 1: ...G Motor Maintenance Equipment G Non trip loop testers G Pat testers Accessories G Phase rotation G Proving units G Socket Testers G Thermometers Probes G Test Leads G Voltage Indicators G Specialist...

Страница 2: ......

Страница 3: ...ads 3 2 LOW continuity test 4 3 M insulation test 5 4 RCD test 6 5 Loop Zs IK 9 6 Non Trip Earth Loop Impedance Test Ra15mA 10 1 resolution with PFC calculation 7 Phase Rotation Sequence 11 8 Instrume...

Страница 4: ...rrent Equipment protected by Double Insulation Class II Caution refer to accompanying documents Caution risk of electric shock 10 OPTIONAL ACCESSORIES Infra red data lead VRTL1 Download software VRSOF...

Страница 5: ...219mA the instrument has a stored value for the resistance of the test leads current supplied by instrument during calibration procedure function selected FUNC GO NON TRIP EARTH LOOP TEST RA15MA Meas...

Страница 6: ...ds Use to adjust time up and down respectively At the end of the test if the resistance value is lower than 5 the instrument beeps twice indicating low resistance The resistance value is displayed on...

Страница 7: ...be adjusted from 10 999 seconds Adjust values using or This test can be used if a minimum measuring time is required UN I n FUNC L S UL M GO 100V 250V 500V 1000V Low resistance 5 seconds 10 seconds 10...

Страница 8: ...on display by O B Press the yellow key twice The instrument injects a current in phase with negative half wave of the voltage indicated on display by 180 FUNC UN I n L S S UL M GO GO 9 SPECIFICATION...

Страница 9: ...ct to the voltage Readings below 1 are displayed as 1 PLEASE NOTE MAN x5 and auto test modes are not available for RCD type A 500mA 8 INSTRUMENT CONNECTION TO PC OR A PRINTER The connection from the V...

Страница 10: ...st passed Please refer to the full user manual for tripping times Press to scroll through the test results RAMP The instrument generates a leakage current growing step by step in a given time interval...

Страница 11: ...Connect the mains plug to a 230V 50HZ socket outlet or to the appropriate conductor by means of the croc clips 4 Press key repeatedly to select P PE P PE is shown 5 Press the yellow key once The inst...

Страница 12: ...nt Icc UN Ra When UN phase to earth voltage 127V if 100V Vmeas 150V 230V if 150V Vmeas 265V This test is carried out at 15mA 10 UL M GO 7 PHASE ROTATION SEQUENCE 1 Connect red black and green test lea...

Отзывы: