background image

8

Test results:

MAN x ½:

If the RCD does not trip, the instrument beeps twice
indicating a successful outcome. (see screen on unit)

MAN x1, x2, x5: If the RCD trips within limits, the instrument beeps twice 

suggesting a successful outcome. (see screen on unit). 
Please note that the internal values apply for RCDs
manufactured to comply with BSEN61008. RCDs which are 
manufactured to comply with BS4293 are required to operate in
0.2s at 1X I

Δ

N

. It is important that the user of this instrument is

aware of the applicable tripping time(s) for the RCD being
tested.

Please refer to the full user manual for tripping times.

AUTO:

The instrument carries out the following 6 tests with different
values of rated current.

½ x I

Δ

n @ 0°

- The RCD should not trip

½ x I

Δ

n @ 180° - The RCD should not trip

1 x I

Δ

n @ 0° 

- The RCD trips (blinking RCD) - Switch RCD on again

1 x I

Δ

n @ 180°

- The RCD trips (blinking RCD) - Switch RCD on again

5 x I

Δ

n @ 0° 

- The RCD trips (blinking RCD) - Switch RCD on again

5 x I

Δ

n @ 180°  - The RCD trips (blinking RCD) - Switch RCD on again

'OK' displayed - test passed.

Please refer to the full user manual for tripping times.

Press 

to scroll through the test results

RAMP:

The instrument generates a leakage current growing step by
step in a given time interval.  At the end of the test, if the RCD
tripping current is < I

Δ

n (type AC) or 1.4xI

Δ

n ( type A with

I

Δ

n>10mA ) the instrument beeps twice indicating a positive 

outcome of the test.
If the parameters set on the instrument are consistent with the 
RCD under test, the ramp test will cause RCD tripping with a 
current lower than or equal to the selected rated differential 
current.

U

t

Press yellow 

key once.  The instrument carries out the 

test.  If the RCD does not trip, the instrument beeps twice 
indicating a successful outcome of the test.

GO

DISP

13

CLEARING TEST RESULTS

To clear results, proceed as follows:

1)

Press the                key

2)

Navigate to the desired test using 

and

keys.

3)

Press the               key to display the selected test result.

4)

Press               once.               flashes in the display.

To cancel deletion press

5)

Press   

again to permanently delete the test result, from the one 

selected to the last one saved

WARNING

The instrument will delete the all results stored from the memory

location selected to the last full one.

CLR

L

S

UL

M

DISP

CLR

RCL

CLR

ESC

Содержание VERITEST 2240

Страница 1: ...G Motor Maintenance Equipment G Non trip loop testers G Pat testers Accessories G Phase rotation G Proving units G Socket Testers G Thermometers Probes G Test Leads G Voltage Indicators G Specialist...

Страница 2: ......

Страница 3: ...ads 3 2 LOW continuity test 4 3 M insulation test 5 4 RCD test 6 5 Loop Zs IK 9 6 Non Trip Earth Loop Impedance Test Ra15mA 10 1 resolution with PFC calculation 7 Phase Rotation Sequence 11 8 Instrume...

Страница 4: ...rrent Equipment protected by Double Insulation Class II Caution refer to accompanying documents Caution risk of electric shock 10 OPTIONAL ACCESSORIES Infra red data lead VRTL1 Download software VRSOF...

Страница 5: ...219mA the instrument has a stored value for the resistance of the test leads current supplied by instrument during calibration procedure function selected FUNC GO NON TRIP EARTH LOOP TEST RA15MA Meas...

Страница 6: ...ds Use to adjust time up and down respectively At the end of the test if the resistance value is lower than 5 the instrument beeps twice indicating low resistance The resistance value is displayed on...

Страница 7: ...be adjusted from 10 999 seconds Adjust values using or This test can be used if a minimum measuring time is required UN I n FUNC L S UL M GO 100V 250V 500V 1000V Low resistance 5 seconds 10 seconds 10...

Страница 8: ...on display by O B Press the yellow key twice The instrument injects a current in phase with negative half wave of the voltage indicated on display by 180 FUNC UN I n L S S UL M GO GO 9 SPECIFICATION...

Страница 9: ...ct to the voltage Readings below 1 are displayed as 1 PLEASE NOTE MAN x5 and auto test modes are not available for RCD type A 500mA 8 INSTRUMENT CONNECTION TO PC OR A PRINTER The connection from the V...

Страница 10: ...st passed Please refer to the full user manual for tripping times Press to scroll through the test results RAMP The instrument generates a leakage current growing step by step in a given time interval...

Страница 11: ...Connect the mains plug to a 230V 50HZ socket outlet or to the appropriate conductor by means of the croc clips 4 Press key repeatedly to select P PE P PE is shown 5 Press the yellow key once The inst...

Страница 12: ...nt Icc UN Ra When UN phase to earth voltage 127V if 100V Vmeas 150V 230V if 150V Vmeas 265V This test is carried out at 15mA 10 UL M GO 7 PHASE ROTATION SEQUENCE 1 Connect red black and green test lea...

Отзывы: