![Marley MD Series Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/marley/md-series/md-series_user-manual_1729405007.webp)
7
If tower purchased is one fan cell only, ignore steps 4 through 8.
5. If collection basins are to be equalized by the use of Marley standard
flumes, unbolt the coverplate from the basin of the cell just installed. The
coverplate is located in the collection basin depressed section end.
6. Unbolt temporary coverplate from the basin of the second cell and set
the bottom module of the second cell in place. Align anchor bolt holes
and flume openings in basin sides.
7. Install flume according to
“MD Field Installation Manual”.
It is important that the cells be firmly anchored before the flume is
attached to the 2nd cell.
8. Repeat steps 2 through 4 for the second top section.
9. Repeat steps 5 through 8 for any remaining cells.
10. Attach your cold water supply piping to the cold water basin outlet con-
nection in accordance with drawing instructions. Use gaskets where
recommended.
Do not support your pipe from the tower or outlet connection—sup-
port it externally.
Normally, one of the following three outlet arrangements is provided:
Side or End suction connection: This is a factory-installed, galvanized
pipe nipple, extending horizontally from the side or end of the cold water
basin. It is both beveled for welding—and grooved for a mechanical cou-
pling. If a weld connection is used, it is recommended that the weld area
be protected against corrosion. Cold galvanizing is suggested, applied
according to the manufacturer’s instructions.
Protect adjacent areas from excessive heat and sparks during weld-
ing or damage could occur.
Bottom outlet connection: This is a factory-installed, circular opening
in the cold water basin floor of one or more cells. An appropriately sized
circular opening has been drilled to 125# ANSI B16.1 flat-face flange
specifications. A full faced gasket and appropriately sized bolts (by others)
must be used for proper outlet function.
Note
Note
Caution
Caution
installation