![Marley MD Series Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/marley/md-series/md-series_user-manual_1729405034.webp)
34
Seasonal Shutdown Instructions
When the system is to be shut down for an extended period of time, it is
recommended that the entire system—cooling tower, system piping, heat
exchangers, etc.—be drained. Leave the basin drains open.
During shutdown, follow recommendations in the
Cooling Tower Inspec-
tion and Maintenance
section of this manual before attempting repairs. Pay
particular attention to mechanical equipment supports.
Following each year’s shutdown and cleaning, inspect the tower’s metal surfaces
for evidence of the need to apply a protective coating. Do not misinterpret
grime and transient rust from the piping system as a need to have the tower
painted. If relatively bright metal can be exposed by cleaning, consider that
the galvanizing has remained effective. Unless there is evidence of a general-
ized failure of the galvanizing, localized touch-up should be all that is required.
To the extent that the galvanizing (zinc coating) still exists, paint
will not adhere to it readily. Contact the manufacturer of the coating
you intend to use for instructions.
Tower framework Check casing and structural bolted connections and
tighten as required.
Fan Check fan assembly bolting and tighten as required. Use torque values
prescribed in the Fan User Manual.
Fan shaft bearings Lubricate fan shaft bearings at close of each operating
season—see page 33.
Clean and lubricate motor at close of each operating season (refer to motor
manufacturer’s recommendations.) Check motor anchor bolts and tighten as
required.
Do not start motor before determining that there will be no interfer-
ence with free rotation of the fan drive.
The motor should be operated for three hours at least once a month. This
serves to dry out windings and lubricate bearing surfaces (refer to Marley
“Fan Motor” User Manual User Manual
Z0239042
.
At start of new operating season, make sure bearings are adequately lubricated
before returning motor to service. Does not apply to motors with sealed bearings.
Note
Warning
maintenance