Belt Tensioning:
Always shut off electrical power to the tower fan motor prior to
performing any inspections that may involve physical contact with
the mechanical or electrical equipment in or on the tower. Lock out
and tag out any electrical switches to prevent others from turning
the power back on. Service personnel must wear proper personal
protective clothing and equipment.
On the MD5006 thru MD5010, the fan motor and belt adjustment mechanism
is located outside the tower. Remove the motor protection hood by loosening
the two thumbscrews on top and hinge the hood up and out of the way. Also,
remove the motor sheave safety bracket and set aside. See the following images.
On the MD5016 thru MD5018 the motor is located inside the tower plenum.
Open the access door (see Access Door Opening Procedure) and hinge out
of the way.
Any bolts removed functioning as mechanical or structural hardware
should be replaced with the torques specified below.
Belt tension on all models is adjusted by turning a large threaded rod(s) that
drives the motor mounting plate away from (or toward) the fan centerline.
Warning
Caution
maintenance
Fastener Torque Values
Machine Bolt
Size
Galvanized
Stainless
ft·lb
ƒ
N·m
ft·lb
ƒ
N·m
8mm
8
10
15
20
10mm
15
20
30
40
12mm
25
35
50
65
16mm
65
85
120
160
20mm
125
170
230
315