![Marley MD Series Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/marley/md-series/md-series_user-manual_1729405014.webp)
14
Some trial and error adjustment of the float valve may be required to
balance the makeup water with tower operation. Ideally, the float valve
setting will be such that no water is wasted through the overflow at pump
shutdown. However, the water level after pump start-up must be deep
enough to assure positive pump suction.
6. Continue pump operation for about 15 minutes, after which it is recom-
mended that the water system be drained, flushed, and refilled.
7. While operating the condensing water pump(s) and prior to operating the
cooling tower fan, execute one of the two alternative biocidal treatment
programs described in the following:
• Resume treatment with the biocide which had been used prior to shut-
down. Utilize the services of the water treatment supplier. Maintain the
maximum recommended biocide residual (for the specific biocide) for
a sufficient period of time (residual and time will vary with the biocide)
to bring the system under good biological control
or
• Treat the system with sodium hypochlorite to a level of 4 to 5 mg/L
free chlorine residual at a pH of 7.0 to 7.6. The chlorine residual must
be held at 4 to 5 mg/L for six hours, measurable with standard com-
mercial water test kits.
If the cooling tower has been in operation and then shut down for a du-
ration of time and not drained, perform one of the two previous biocidal
treatment programs directly to the cooling water storage vessel (cooling
tower sump, drain down tank, etc.) without circulating stagnant water
over the cooling tower fill or operating the cooling tower fan.
After biocidal pretreatment has been successfully completed, cooling
water may be circulated over the tower fill with the fan off.
When biocidal treatment has been maintained at a satisfactory level for
at least six hours, the fan may be turned on and the system returned to
service. Resume the standard water treatment program, including biocidal
treatment.
installation