23
maintenance
To turn the rod(s), the
rod retention bracket(s)
must first be moved. On
the models with motors
located externally loosen
the thumbscrew holding
this bracket in place and
rotate the bracket away
from the assembly. On
models with the motor
located in the plenum
the rod retention is held in place with fasteners. Loosen fastener and slide
the bracket away from the adjusting rod. Turn the rod(s) clockwise to drive the
motor away from the fan (tighten belts)
or counterclockwise to drive the motor
toward the fan (loosen the belts). On
models with more than one rod, alternate
turns on the rods to prevent binding.
There is no need to loosen any other
hardware to adjust the belt tension. After
belt tension is adjusted to a satisfactory
position, install the rod retention bracket
with the thumbscrew and replace any
safety hoods.
Ideal tension is the lowest tension at
which the belt will not slip under peak load conditions. Check tension frequently
during the first 24-48 hours of run-in operation. Overtensioning shortens
belt and bearing life. Keep belts free from foreign material which may cause
slipping. Never apply belt dressing as this will damage the belt and cause