ATF Sizing
Plenum Heater Sizing
Plenum heaters are available as accessories in 5, 7, 10,
15 and 20kW sizes. Choose a size that covers 100% of the
coldest day heat load, according to the heat loss analysis men-
tioned in the last section. If that is not available, use the follow-
ing recommendation:
This is which unit size is required for a
typical
two-level
home (main level and below grade basement) with R-20 walls,
R-40 ceiling and average size and number of windows. The
Heated Area is the area of the main level. The table accounts
for a basement the same size as the heated area.
IT IS HIGHLY RECOMMENDED THAT A PROPER HEAT
LOSS/GAIN ANALYSIS BE PERFORMED BY A PROFES-
SIONAL WITH APPROVED CSA F-280 SOFTWARE BEFORE
SELECTING THE SIZE OF UNIT REQUIRED FOR THE APPLI-
CATION.
The analysis will result in a heat load for the coldest day,
which is influenced by, for example, the number of levels, the
size of the windows, the orientation of the home, attached gar-
age, bonus rooms, walk-in basement, and coldest outdoor tem-
perature for the region.
In northern climates, a heat pump model size can be se-
lected by matching the calculated heat load to a heat pump’s
standard capacity rating at an outdoor temperature of 35°F
(1.7°C), which is the AHRI H2
2
test condition. These are listed
in the
Model Specific Information
section later in this manual.
This sizing will result in a good compromise between covering
as much of the cold weather heat load as possible without utiliz-
ing backup heat, while minimizing excessive cycling (turning on
and off frequently) during moderate outdoor temperatures.
It should be noted that sizing an air source heat pump is
always a compromise between covering coldest-day heat load
and minimizing cycling due to over-capacity in warm weather.
In cooling dominant climates, the heat pump should be
similarly sized, by matching the calculated cooling load to the
standard capacity rating at an outdoor temperature that matches
the local maximum outdoor temperature. The difference here is
that it is necessary to cover all of the cooling load, since there is
no backup cooling.
Even in northern heating dominant climates, it should
be ensured that 100% of the cooling load will be covered
when sizing the heat pump.
Heat Pump Sizing
TABLE 1
contains a guideline to the size of home each
air source heat pump size can handle.
TABLE 1 - Heat Pump Size vs. Heated Area
Model
sq.ft.
m
2
45
1,400
130
55
2,000
185
65
2,600
240
75
3,100
290
TABLE 2 - Plenum Heater Sizing
Model
Plenum Heater Size (kW)
Recommended
Internally Possible
45
10
5, 7, 10
55
10
5, 7, 10, 15, 20
65
15
5, 7, 10, 15, 20
75
20
5, 7, 10, 15, 20
Two styles of plenum heater are available; the first is for
internal installation (inside the indoor unit). Note limit for size 45
in above table.
The second has a wider element profile for installation
outside the unit, in the ductwork. If field-installing the fan in the
convertible side discharge position, this type of plenum heater
will need to be used.
Содержание ATF-45
Страница 11: ...1 Jun 2018 Page 11 002000MAN 01 Average Maximum Snow Depth Canada 1979 1997 Source Natural Resources Canada...
Страница 12: ...Page 12 002000MAN 01 1 Jun 2018...
Страница 15: ...1 Jun 2018 Page 15 002000MAN 01...
Страница 16: ...Page 16 002000MAN 01 1 Jun 2018...
Страница 17: ...1 Jun 2018 Page 17 002000MAN 01...
Страница 18: ...Page 18 002000MAN 01 1 Jun 2018...
Страница 20: ...Page 20 002000MAN 01 1 Jun 2018...
Страница 21: ...1 Jun 2018 Page 21 002000MAN 01...
Страница 22: ...Page 22 002000MAN 01 1 Jun 2018...
Страница 23: ...1 Jun 2018 Page 23 002000MAN 01...
Страница 24: ...Page 24 002000MAN 01 1 Jun 2018...
Страница 25: ...1 Jun 2018 Page 25 002000MAN 01...
Страница 27: ...1 Jun 2018 Page 27 002000MAN 01...
Страница 31: ...1 Jun 2018 Page 31 002000MAN 01...
Страница 84: ...Page 84 002000MAN 01 1 Jun 2018 Wiring Diagram 208 230 1 60...
Страница 85: ...1 Jun 2018 Page 85 002000MAN 01 Electrical Box Layout 208 230 1 60...
Страница 86: ...Page 86 002000MAN 01 1 Jun 2018 Wiring Diagram 208 3 60...
Страница 87: ...1 Jun 2018 Page 87 002000MAN 01 Electrical Box Layout 208 3 60...
Страница 88: ...Page 88 002000MAN 01 1 Jun 2018 Wiring Diagram 460 3 60...
Страница 89: ...1 Jun 2018 Page 89 002000MAN 01 Electrical Box Layout 460 3 60...
Страница 90: ...Page 90 002000MAN 01 1 Jun 2018 ACE 45 55 Wiring Diagram ACE 65 75 Wiring Diagram...
Страница 91: ...1 Jun 2018 Page 91 002000MAN 01...
Страница 92: ...Page 92 002000MAN 01 1 Jun 2018...
Страница 93: ...1 Jun 2018 Page 93 002000MAN 01...
Страница 94: ...Page 94 002000MAN 01 1 Jun 2018 Dimensions ATF 45 Left Return INDOOR UNIT OUTDOOR UNIT ACE 45...
Страница 95: ...1 Jun 2018 Page 95 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 45 Dimensions ATF 45 Right Return...
Страница 96: ...Page 96 002000MAN 01 1 Jun 2018 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Left Return...
Страница 97: ...1 Jun 2018 Page 97 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Right Return...
Страница 100: ...Page 100 002000MAN 01 1 Jun 2018 ACE 65 75 ACE 45 55...