COMPRESSOR TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Compressor will
not start
Faulty control board.
No 24vac output on STAGE1 when
compressor should be operating.
Replace control board.
Faulty run capacitor.
(Single phase only)
Check value with capacitance meter.
Should match label on capacitor.
Compressor will hum while trying to
start and then trip its overload.
Replace if faulty.
Loose or faulty wiring.
Check all compressor wiring, includ-
ing inside compressor electrical box.
Fix any loose connections. Re-
place any damaged wires.
Faulty compressor
contactor.
Voltage on line side with contactor
held closed, but no voltage on one
or both terminals on the load side.
Points pitted or burned.
Or, 24VAC across coil but contactor
will not engage.
Replace contactor.
Thermal overload on
compressor tripped.
Ohmmeter shows reading when
placed across R and S terminals
and infinity between C & R or C & S.
A valid resistance reading is present
again after the compressor has
cooled down.
Proceed to Operation Trouble-
shooting to determine the cause
of the thermal overload trip.
Burned out motor
(open winding)
Remove wires from compressor.
Ohmmeter shows infinite resistance
between any two terminals. Note:
Be sure compressor overload has
had a chance to reset. If compressor
is hot this may take several hours.
Replace the compressor.
Burned out motor
(shorted windings)
Remove wires from compressor.
Resistance between any two termi-
nals is below the specified value.
Replace the compressor.
Motor shorted to ground.
Remove wires from compressor.
Check for infinite resistance be-
tween each terminal and ground.
If any terminal to ground is not
infinite replace the compressor.
Seized compressor due to
locked or damaged
mechanism.
Compressor attempts to start but
trips its internal overload after a few
seconds. (Run capacitor already
verified)
Attempt to “rock” compressor free.
If normal operation cannot be
established, replace compressor.
Compressor
starts hard
Start capacitor faulty.
(Single phase only)
Check with capacitance meter.
Check for black residue around
blowout hole on top of capacitor.
Replace if faulty.
Remove black residue in electrical
box if any.
Potential relay faulty.
(Single phase only)
Replace with new one and verify
compressor starts properly.
Replace if faulty.
Compressor is “tight” due
to damaged mechanism
Compressor attempts to start but
trips its internal overload after a few
seconds. Run capacitor has been
verified already.
Attempt to “rock” compressor free.
If normal operation cannot be es-
tablished, replace compressor.
Compressor
stage 2 will not
activate
Faulty stage 2 module
Verify if 24VAC is present across
Y2 and C of the terminal strip.
Replace module if signal is pre-
sent. Check wiring if signal is not
present.
Содержание ATF-45
Страница 11: ...1 Jun 2018 Page 11 002000MAN 01 Average Maximum Snow Depth Canada 1979 1997 Source Natural Resources Canada...
Страница 12: ...Page 12 002000MAN 01 1 Jun 2018...
Страница 15: ...1 Jun 2018 Page 15 002000MAN 01...
Страница 16: ...Page 16 002000MAN 01 1 Jun 2018...
Страница 17: ...1 Jun 2018 Page 17 002000MAN 01...
Страница 18: ...Page 18 002000MAN 01 1 Jun 2018...
Страница 20: ...Page 20 002000MAN 01 1 Jun 2018...
Страница 21: ...1 Jun 2018 Page 21 002000MAN 01...
Страница 22: ...Page 22 002000MAN 01 1 Jun 2018...
Страница 23: ...1 Jun 2018 Page 23 002000MAN 01...
Страница 24: ...Page 24 002000MAN 01 1 Jun 2018...
Страница 25: ...1 Jun 2018 Page 25 002000MAN 01...
Страница 27: ...1 Jun 2018 Page 27 002000MAN 01...
Страница 31: ...1 Jun 2018 Page 31 002000MAN 01...
Страница 84: ...Page 84 002000MAN 01 1 Jun 2018 Wiring Diagram 208 230 1 60...
Страница 85: ...1 Jun 2018 Page 85 002000MAN 01 Electrical Box Layout 208 230 1 60...
Страница 86: ...Page 86 002000MAN 01 1 Jun 2018 Wiring Diagram 208 3 60...
Страница 87: ...1 Jun 2018 Page 87 002000MAN 01 Electrical Box Layout 208 3 60...
Страница 88: ...Page 88 002000MAN 01 1 Jun 2018 Wiring Diagram 460 3 60...
Страница 89: ...1 Jun 2018 Page 89 002000MAN 01 Electrical Box Layout 460 3 60...
Страница 90: ...Page 90 002000MAN 01 1 Jun 2018 ACE 45 55 Wiring Diagram ACE 65 75 Wiring Diagram...
Страница 91: ...1 Jun 2018 Page 91 002000MAN 01...
Страница 92: ...Page 92 002000MAN 01 1 Jun 2018...
Страница 93: ...1 Jun 2018 Page 93 002000MAN 01...
Страница 94: ...Page 94 002000MAN 01 1 Jun 2018 Dimensions ATF 45 Left Return INDOOR UNIT OUTDOOR UNIT ACE 45...
Страница 95: ...1 Jun 2018 Page 95 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 45 Dimensions ATF 45 Right Return...
Страница 96: ...Page 96 002000MAN 01 1 Jun 2018 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Left Return...
Страница 97: ...1 Jun 2018 Page 97 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Right Return...
Страница 100: ...Page 100 002000MAN 01 1 Jun 2018 ACE 65 75 ACE 45 55...