OPERATION TROUBLESHOOTING -
WATER HEATING MODE
Fault
Possible Cause
Verification
Recommended Action
High or low suc-
tion or discharge
pressure
Faulty sensor
Compare pressure sensor reading
against a known reference such as a
new refrigeration manifold set.
Check wiring, replace sensor. If
problem persists, replace control
board.
High discharge
pressure
Low indoor loop flow rate. Verify that indoor delta T is 8-12°F
(4-7°C)
Increase flow rate if new installa-
tion, check for fouled heat ex-
changer if existing installation.
Temperature setpoint(s)
too high (if using external
aquastat or BACnet con-
trol)
Use PC APP to verify that Indoor
OUT does not exceed 120°F (49°C)
Reduce setpoint(s).
EEV stuck almost closed
or partially blocked by for-
eign object.
Manually adjusting the EEV does not
affect the superheat or the suction
pressure. Low superheat and dis-
charge pressure.
Go to EEV troubleshooting sec-
tion.
Filter-dryer plugged
Feel each end of the filter-dryer; they
should be the same temperature. If
there is a temperature difference then
it is plugged. Also causes low suc-
tion pressure.
Replace filter-dryer.
Unit is overcharged.
High subcooling, low Indoor Loop
delta T.
Remove 1/2 lb of refrigerant at a
time and verify that the discharge
pressure reduces.
Low suction
pressure
Indoor OUT temperature
too cold (on startup or if
unit has been off for ex-
tended period)
Ensure Indoor OUT temperature is
above the low limit indicated in the
Model Specific Information
sec-
tion.
Reduce flow temporarily until In-
door Out temperature has risen
sufficiently.
Low or no outdoor unit
airflow
Visually check fan to see if it is oper-
ating.
Go to Outdoor Fan Troubleshoot-
ing section.
TS1 temperature sensor
not reading properly.
If the sensor is reading low it will
cause the superheat to appear high,
which causes the EEV to continually
close.
Verify EEV position is low com-
pared to normal. Check tempera-
ture sensor, replace if necessary.
Filter-dryer plugged
Feel each end of the filter-dryer; they
should be the same temperature. If
there is a temperature difference then
it is plugged. Also causes low suc-
tion pressure.
Replace filter-dryer.
EEV stuck almost closed
or partially blocked by for-
eign object.
Manually adjusting the EEV does not
affect the superheat or the suction
pressure. Low superheat and dis-
charge pressure.
Go to EEV troubleshooting sec-
tion.
Low refrigerant charge.
Superheat is high, EEV position is
high.
Locate the leak and repair it.
Spray Nine, a sniffer, and/or dye
are common methods of locating
a leak.
Содержание ATF-45
Страница 11: ...1 Jun 2018 Page 11 002000MAN 01 Average Maximum Snow Depth Canada 1979 1997 Source Natural Resources Canada...
Страница 12: ...Page 12 002000MAN 01 1 Jun 2018...
Страница 15: ...1 Jun 2018 Page 15 002000MAN 01...
Страница 16: ...Page 16 002000MAN 01 1 Jun 2018...
Страница 17: ...1 Jun 2018 Page 17 002000MAN 01...
Страница 18: ...Page 18 002000MAN 01 1 Jun 2018...
Страница 20: ...Page 20 002000MAN 01 1 Jun 2018...
Страница 21: ...1 Jun 2018 Page 21 002000MAN 01...
Страница 22: ...Page 22 002000MAN 01 1 Jun 2018...
Страница 23: ...1 Jun 2018 Page 23 002000MAN 01...
Страница 24: ...Page 24 002000MAN 01 1 Jun 2018...
Страница 25: ...1 Jun 2018 Page 25 002000MAN 01...
Страница 27: ...1 Jun 2018 Page 27 002000MAN 01...
Страница 31: ...1 Jun 2018 Page 31 002000MAN 01...
Страница 84: ...Page 84 002000MAN 01 1 Jun 2018 Wiring Diagram 208 230 1 60...
Страница 85: ...1 Jun 2018 Page 85 002000MAN 01 Electrical Box Layout 208 230 1 60...
Страница 86: ...Page 86 002000MAN 01 1 Jun 2018 Wiring Diagram 208 3 60...
Страница 87: ...1 Jun 2018 Page 87 002000MAN 01 Electrical Box Layout 208 3 60...
Страница 88: ...Page 88 002000MAN 01 1 Jun 2018 Wiring Diagram 460 3 60...
Страница 89: ...1 Jun 2018 Page 89 002000MAN 01 Electrical Box Layout 460 3 60...
Страница 90: ...Page 90 002000MAN 01 1 Jun 2018 ACE 45 55 Wiring Diagram ACE 65 75 Wiring Diagram...
Страница 91: ...1 Jun 2018 Page 91 002000MAN 01...
Страница 92: ...Page 92 002000MAN 01 1 Jun 2018...
Страница 93: ...1 Jun 2018 Page 93 002000MAN 01...
Страница 94: ...Page 94 002000MAN 01 1 Jun 2018 Dimensions ATF 45 Left Return INDOOR UNIT OUTDOOR UNIT ACE 45...
Страница 95: ...1 Jun 2018 Page 95 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 45 Dimensions ATF 45 Right Return...
Страница 96: ...Page 96 002000MAN 01 1 Jun 2018 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Left Return...
Страница 97: ...1 Jun 2018 Page 97 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Right Return...
Страница 100: ...Page 100 002000MAN 01 1 Jun 2018 ACE 65 75 ACE 45 55...