1-Jun-2018
Page 13
002000MAN-01
Wiring
IMPORTANT NOTE: A properly qualified
electrician should be retained for all
connections to the heat pump and associat-
ed controls. The connections to the unit
MUST CONFORM TO LOCAL CODES.
TABLE 3 - Power Supply Connections
Line
Description
Voltages
L1
Line 1
All
L2
Line 2
All
L3
Line 3
3-phase only
GND
Ground
All (connect to ground lug)
** Only required if connecting 115VAC circulators.
N**
Neutral
208/230-1-60, 208-3-60
Indoor Unit Power Supply Connections
Power supply for the heat pump from the breaker panel is
supplied to the indoor unit. The unit has a concentric 1.093” /
0.875” knockout for main power supply connection to the electri-
cal box. There are also two 7/8” knockouts and a 1/2” opening
with plastic grommet (grommet hole is 3/8”) for connections to
the air thermostat, optional aquastat, and power and signal con-
nections to the outdoor unit.
A schematic diagram (SCH) and electrical box layout
diagram (ELB) can be found on the electrical box cover of the
unit as well as in the
Model Specific Information
section of this
manual.
The Electrical Tables in the
Model Specific Information
section
contain information about the wire and breaker size.
Indoor Loop Circulator Pump Wiring
The indoor unit has provisions for connecting the indoor
circulator pump (between the heat pump and buffer tank) so that
it will be turned on whenever the compressor operates. Con-
nect the circulator pump module to the appropriate two terminals
(
115V & 115/230
or
230V & 115/230
) of the terminal strip
marked
Indoor Circulator Pumps
, as per the voltage of the circu-
lator pump module. Ground wires should be connected to the
ground lug in the electrical box. Ensure that the total current
draw does not exceed the value indicated on the label in the
heat pump electrical box.
For
460VAC models
, only 277VAC circulators may be
powered directly from the heat pump. If other voltage circulators
are used, they must be powered using an external contactor
actuated by the ICR terminal on the left side of the control board
and the C (24V ground) terminal.
TABLE 6 - Indoor Loop Circulator Connections
Signal
Description
115V
230V
Use a 2-conductor 14ga cable.
Connection for 115V circulator
Connection for 230V circulator
115/230
Connection for 115V or 230V circulator
TABLE 4 - Outdoor Unit Power Supply Connections
Line
Description
L1
Supply line
L2
Supply line
GND
Ground
Use a two conductor outdoor rated 14ga minimum cable.
IMPORTANT NOTE: According to most
codes, a disconnect switch visible and/or
reachable from the outdoor unit must be in-
stalled in the power supply cable. If the
switch has fuses or breakers they must be
no more than 10A.
Outdoor Unit: Power Connections
The ACE outdoor unit is powered from the indoor unit.
The power supply for the ACE unit is 208 to 277VAC, 50/60Hz.
The ATF and ACE units have matching terminal strips for these
connections. Use a two conductor, minimum 14ga
outdoor rat-
ed cable
for this connection. Refer to diagram.
the size of wire for the connections, as well as the recommend-
ed breaker size.
Auxiliary Plenum Heater:
Signal Connections
The ATF unit has two dry contacts to control the 2 stages
of the plenum heater. These dry contacts can also be used to
control other types of auxiliary air heat. Note that dry contacts
are intended to activate equipment that has its own 24VAC
transformer; if equipment does not have its own transformer,
one will need to be installed in an external electrical box.
Connect the terminals on the ATF’s terminal strip to the
matching terminals on the plenum heater’s control board using
an 18-3 cable.
TABLE 5 - Plenum Heater Signal Connections
Signal
Description
C
P
Common
1
2
Use a 3-conductor 18ga cable.
Dry contact for auxiliary heat stage 1
Dry contact for auxiliary heat stage 2
Auxiliary Plenum Heater:
Power Supply Connections
Auxiliary air heat will usually be provided by an electric
duct heater (plenum heater). These are available as accesso-
ries in 5, 7, 10, 15, and 20 kW sizes, and are installed as previ-
ously noted in this manual. The plenum heater will have its own
breaker and power supply wire. The Electrical Tables in the
Model Specific Information
section
contain information about
Control Transformer
The rest of the low voltage controls, including the control
board, are powered by a 100VA class II transformer. 208/230-1
-60 and 208-3-60 models have a resettable breaker on the sec-
ondary side for circuit protection. Should the breaker trip, locate
and correct the problem and then reset the breaker by pressing
in on it.
All other voltage models have primary and secondary fus-
es for circuit protection.
Содержание ATF-45
Страница 11: ...1 Jun 2018 Page 11 002000MAN 01 Average Maximum Snow Depth Canada 1979 1997 Source Natural Resources Canada...
Страница 12: ...Page 12 002000MAN 01 1 Jun 2018...
Страница 15: ...1 Jun 2018 Page 15 002000MAN 01...
Страница 16: ...Page 16 002000MAN 01 1 Jun 2018...
Страница 17: ...1 Jun 2018 Page 17 002000MAN 01...
Страница 18: ...Page 18 002000MAN 01 1 Jun 2018...
Страница 20: ...Page 20 002000MAN 01 1 Jun 2018...
Страница 21: ...1 Jun 2018 Page 21 002000MAN 01...
Страница 22: ...Page 22 002000MAN 01 1 Jun 2018...
Страница 23: ...1 Jun 2018 Page 23 002000MAN 01...
Страница 24: ...Page 24 002000MAN 01 1 Jun 2018...
Страница 25: ...1 Jun 2018 Page 25 002000MAN 01...
Страница 27: ...1 Jun 2018 Page 27 002000MAN 01...
Страница 31: ...1 Jun 2018 Page 31 002000MAN 01...
Страница 84: ...Page 84 002000MAN 01 1 Jun 2018 Wiring Diagram 208 230 1 60...
Страница 85: ...1 Jun 2018 Page 85 002000MAN 01 Electrical Box Layout 208 230 1 60...
Страница 86: ...Page 86 002000MAN 01 1 Jun 2018 Wiring Diagram 208 3 60...
Страница 87: ...1 Jun 2018 Page 87 002000MAN 01 Electrical Box Layout 208 3 60...
Страница 88: ...Page 88 002000MAN 01 1 Jun 2018 Wiring Diagram 460 3 60...
Страница 89: ...1 Jun 2018 Page 89 002000MAN 01 Electrical Box Layout 460 3 60...
Страница 90: ...Page 90 002000MAN 01 1 Jun 2018 ACE 45 55 Wiring Diagram ACE 65 75 Wiring Diagram...
Страница 91: ...1 Jun 2018 Page 91 002000MAN 01...
Страница 92: ...Page 92 002000MAN 01 1 Jun 2018...
Страница 93: ...1 Jun 2018 Page 93 002000MAN 01...
Страница 94: ...Page 94 002000MAN 01 1 Jun 2018 Dimensions ATF 45 Left Return INDOOR UNIT OUTDOOR UNIT ACE 45...
Страница 95: ...1 Jun 2018 Page 95 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 45 Dimensions ATF 45 Right Return...
Страница 96: ...Page 96 002000MAN 01 1 Jun 2018 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Left Return...
Страница 97: ...1 Jun 2018 Page 97 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Right Return...
Страница 100: ...Page 100 002000MAN 01 1 Jun 2018 ACE 65 75 ACE 45 55...