Page 56
002000MAN-01
1-Jun-2018
Air Heating Mode:
1.
Set the thermostat to heating mode and adjust the setpoint to activate stage 1 and stage 2. The fan should slowly ramp up
to speed after the time delay of the thermostat expires (if applicable) and the compressor will start.
2.
Check the PC App or LCD Display. The suction and discharge pressures will vary based on the outdoor temperature and indoor
air
temperature, but they should be
90-110PSIG
and
260-360PSIG
respectively for a typical start-up.
3.
Monitoring the refrigeration gauges while the unit runs. Record the following after 10 minutes of runtime:
1. Suction pressure
2. Discharge pressure
3. Duct Return temperature (poke a small hole in the flex collar and insert probe in airstream)
4. Duct Supply temperature (poke a small hole in the flex collar and insert probe in airstream)
5. Duct Delta T (should be between
22-32°F, 12-18°C
)
6. Outdoor air temperature
7. Compressor L1(C) current (black wire, place meter between electrical box and compressor)
4.
Adjust the thermostat setpoint to the desired room temperature and let the unit run through a cycle.
5.
For units with a desuperheater, turn the power off to the unit. Connect the brown wire with the blue insulated terminal to the
compressor contactor as shown in the electrical box diagram. Turn the DHW Switch in the unit post on. Turn the power to the
unit on.
6.
Verify the DHW IN and DHW OUT temperatures (if applicable) by hand
(caution: pipes get hot).
If the DHW OUT line does not
become hotter than the DHW IN line the circulator is air locked. Bleed the air from the system and check the temperature differ-
ential again to ensure there is flow from the circulator.
7.
Remove the electrical cover from the plenum heater.
Place a current clamp meter around one of the supply wires. Turn on
the power to the plenum heater. Adjust the thermostat setpoint to
85°F (29°C)
. Verify that the current draw increase as
each electric heat stage is activated. (10kW has 2 stages, 15kW has 3 stages and 20kW has 4 stages).
Air Cooling Mode:
1.
Set the thermostat to cooling mode and adjust the setpoint to activate stage 1 and stage 2.
2.
Monitoring the refrigeration gauges while the unit runs. Record the following after 10 minutes of runtime:
1. Suction pressure
2. Discharge pressure
3. Duct Return temperature
4. Duct Supply Out temperature
5. Duct Delta T
6. Outdoor air temperature
3.
Adjust the thermostat setpoint to the desired room temperature if possible, otherwise set it just low enough to allow the unit t(e.g.
1°F / 0.5°C less than room temperature) and let the unit run through a cycle.
Water Heating Mode:
1.
Set air thermostat to “off”. Adjust the Setpoint Control settings via the the PC App or LCD (or adjust aquastat if used) to activate
stage 1 and stage 2. The EEV will begin to open and the compressor will start, as will the circulator pumps.
2.
Check the PC App or LCD Display. The suction and discharge pressures will vary based on the outdoor temperature and the
indoor loop
temperature, but they should be
90-110PSIG
and
260-360PSIG
respectively for a typical start-up.
3.
Monitor the unit via the PC APP or LCD Display while the unit runs, and record the following after 10 minutes of run time:
1. Suction pressure
2. Discharge pressure
3. Indoor Loop In (Hot In) temperature
4. Indoor Loop Out (Hot Out) temperature
5. Indoor Delta T (should be between
8-12°F, 4-6°C
)
6. Outdoor air temperature
7. Compressor L1(C) current (black wire, place meter between electrical box and compressor)
4.
Adjust the control setpoints to the desired buffer tank temperature and let the unit run through a cycle.
Final Inspection:
1.
Turn the power off to the unit (and plenum heater if installed) and remove all test equipment.
2.
Install the electrical box cover and the access panel on the heat pump. Install the service port caps securely to prevent
refrigerant loss. Install the electrical cover on the plenum heater if applicable.
3.
Do a final check for leaks/spills and ensure the area is clean.
4.
Turn the power on to the unit and the plenum heater if installed. Set the thermostat and water heat to the final settings.
Startup Record:
1.
Sign and date the Startup Record and have the homeowner sign as well. Leave the Startup Record with the homeowner, retain
a copy for filing and send a copy to Maritime Geothermal Ltd. for warranty registration.
Содержание ATF-45
Страница 11: ...1 Jun 2018 Page 11 002000MAN 01 Average Maximum Snow Depth Canada 1979 1997 Source Natural Resources Canada...
Страница 12: ...Page 12 002000MAN 01 1 Jun 2018...
Страница 15: ...1 Jun 2018 Page 15 002000MAN 01...
Страница 16: ...Page 16 002000MAN 01 1 Jun 2018...
Страница 17: ...1 Jun 2018 Page 17 002000MAN 01...
Страница 18: ...Page 18 002000MAN 01 1 Jun 2018...
Страница 20: ...Page 20 002000MAN 01 1 Jun 2018...
Страница 21: ...1 Jun 2018 Page 21 002000MAN 01...
Страница 22: ...Page 22 002000MAN 01 1 Jun 2018...
Страница 23: ...1 Jun 2018 Page 23 002000MAN 01...
Страница 24: ...Page 24 002000MAN 01 1 Jun 2018...
Страница 25: ...1 Jun 2018 Page 25 002000MAN 01...
Страница 27: ...1 Jun 2018 Page 27 002000MAN 01...
Страница 31: ...1 Jun 2018 Page 31 002000MAN 01...
Страница 84: ...Page 84 002000MAN 01 1 Jun 2018 Wiring Diagram 208 230 1 60...
Страница 85: ...1 Jun 2018 Page 85 002000MAN 01 Electrical Box Layout 208 230 1 60...
Страница 86: ...Page 86 002000MAN 01 1 Jun 2018 Wiring Diagram 208 3 60...
Страница 87: ...1 Jun 2018 Page 87 002000MAN 01 Electrical Box Layout 208 3 60...
Страница 88: ...Page 88 002000MAN 01 1 Jun 2018 Wiring Diagram 460 3 60...
Страница 89: ...1 Jun 2018 Page 89 002000MAN 01 Electrical Box Layout 460 3 60...
Страница 90: ...Page 90 002000MAN 01 1 Jun 2018 ACE 45 55 Wiring Diagram ACE 65 75 Wiring Diagram...
Страница 91: ...1 Jun 2018 Page 91 002000MAN 01...
Страница 92: ...Page 92 002000MAN 01 1 Jun 2018...
Страница 93: ...1 Jun 2018 Page 93 002000MAN 01...
Страница 94: ...Page 94 002000MAN 01 1 Jun 2018 Dimensions ATF 45 Left Return INDOOR UNIT OUTDOOR UNIT ACE 45...
Страница 95: ...1 Jun 2018 Page 95 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 45 Dimensions ATF 45 Right Return...
Страница 96: ...Page 96 002000MAN 01 1 Jun 2018 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Left Return...
Страница 97: ...1 Jun 2018 Page 97 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Right Return...
Страница 100: ...Page 100 002000MAN 01 1 Jun 2018 ACE 65 75 ACE 45 55...