Page 26
002000MAN-01
1-Jun-2018
Ductwork
Duct Systems - General
Ductwork layout for a heat pump will differ from traditional
hot air furnace design in the number of leads and size of main
trunks required. Air temperature leaving the heat pump is
normally
95º -105ºF (35-40ºC)
, much cooler than that of a
conventional fossil fuel furnace. To compensate for this, larger
volumes of lower temperature air must be moved and
consequently duct sizing must be able to accommodate the
greater airflow without creating a high static pressure or high
velocity at the floor diffusers.
A duct system capable of supplying the required air flow is
of utmost importance. Maritime Geothermal Ltd. recommends
that the external static pressure from the duct system be kept
below 0.2 inches of water total. In some instances the number
of floor diffusers will actually double when compared to the
number that would be used for a hot air oil-fired furnace. Refer
to
TABLE 12
and
TABLE 13
.
1. Generally allow
100 cfm
for each floor grill.
2. All leads to the grills should be 6'' in diameter (28sq.in. each).
3. The main hot air trunks should be at least 75% of the square
surface area of leads being fed at any given point.
4. Return air grills should have a minimum of the same total
square surface area as the total of the supply grills.
5. The square surface area of the return trunks should equal
the square surface area of the grills being handled at any
given point along the trunk.
It is
VERY IMPORTANT
that all turns in both the supply
trunks and the return trunks be made with
TURNING RADII
. Air
act like a fluid and, just like water, pressure drop is increased
when air is forced to change direction rapidly around a sharp or
irregular corner.
It is recommended that flexible collars be used to connect
the main trunks to the heat pump. This helps prevent any vibra-
tions from travelling down the ductwork. If a plenum heater is
installed, the collar should be at least 12” away from the heater
elements.
If desired, the first 5-10 feet of the main supply trunks can
be insulated internally with acoustical duct insulation to further
inhibit any noise from the unit from travelling down the ductwork.
If a plenum heater is installed, insulation should not be placed
within 12” of the heater elements.
DRAWING 002249PDG
shows a typical installation.
TABLE 12 - Heat Pump Size vs. Hot Air Grills
Model
Size (tons)
# of Grills (@100 cfm)
45
3
12
55
4
15
65
5
19
75
6
21
Duct Systems - Grill Layout
Most forced air heating systems in homes have the floor
grills placed around the perimeter of the room. Supply grills
should be placed under a window when possible to help prevent
condensation on the window. As mentioned in the previous sub
-section, supply grill leads should be 6'' in diameter (28 square
inches each) to allow
100 cfm
of airflow.
In a typical new construction, there should be one supply
grill for every 100 square feet of area in the room. When rooms
require more than one grill, they should be placed in a manner
that promotes even heat distribution, such as one at each end of
the room. It is always a good idea to place a damper in each
grill supply or place adjustable grills so that any imbalances in
the heat distribution can be corrected.
The total number of supply grills available is based on the
heat pump nominal airflow.
TABLE 12
shows the number of
grills recommended per heat pump size.
Return grills should be mounted on the floor. At minimum
they should be the same size as the supply grill,
it is highly rec-
ommended that they be 25% to 50% larger than the total
supply.
They should be placed opposite the supply grills
when possible to ensure distribution across the room. For
rooms requiring more than one supply grill, it may be possible to
use one larger return grill if it can be centrally positioned oppo-
site of the supply grills, however it is preferred to have one re-
turn for each supply to optimize heat distribution across the
room.
Thermostat Location
Most homes are a single zone with one thermostat. The
thermostat should be centrally located within the home, typically
on the main floor. It should be placed away from any supply
grills, and should not be positioned directly above a return grill.
Most installations have the thermostat located in a hallway, or
on the inner wall of the living room. It should be noted that most
homes do not have any supply ducts in the hallway. This can
lead to a temperature lag at the thermostat if there is very little
air movement in the hallway, causing the home to be warmer
than indicated by the thermostat.
Plenum Heater
It is required that auxiliary heat be installed for all air source
heat pumps. The easiest way to provide this is with an electric
air plenum heater. It should be controlled by the heat pump’s
stage 3 control, as outlined in the
Wiring
section.
The plenum heater will be usually installed inside the indoor
unit, as described in the
Installation Basics
section. If the blow-
er is installed in the side discharge position, the plenum heater
is installed in the discharge ductwork outside the unit, at least
12” away from any flexible duct collars. There is an accessory
plenum heater with a wider cage profile available that is more
suitable for duct installation.
Содержание ATF-45
Страница 11: ...1 Jun 2018 Page 11 002000MAN 01 Average Maximum Snow Depth Canada 1979 1997 Source Natural Resources Canada...
Страница 12: ...Page 12 002000MAN 01 1 Jun 2018...
Страница 15: ...1 Jun 2018 Page 15 002000MAN 01...
Страница 16: ...Page 16 002000MAN 01 1 Jun 2018...
Страница 17: ...1 Jun 2018 Page 17 002000MAN 01...
Страница 18: ...Page 18 002000MAN 01 1 Jun 2018...
Страница 20: ...Page 20 002000MAN 01 1 Jun 2018...
Страница 21: ...1 Jun 2018 Page 21 002000MAN 01...
Страница 22: ...Page 22 002000MAN 01 1 Jun 2018...
Страница 23: ...1 Jun 2018 Page 23 002000MAN 01...
Страница 24: ...Page 24 002000MAN 01 1 Jun 2018...
Страница 25: ...1 Jun 2018 Page 25 002000MAN 01...
Страница 27: ...1 Jun 2018 Page 27 002000MAN 01...
Страница 31: ...1 Jun 2018 Page 31 002000MAN 01...
Страница 84: ...Page 84 002000MAN 01 1 Jun 2018 Wiring Diagram 208 230 1 60...
Страница 85: ...1 Jun 2018 Page 85 002000MAN 01 Electrical Box Layout 208 230 1 60...
Страница 86: ...Page 86 002000MAN 01 1 Jun 2018 Wiring Diagram 208 3 60...
Страница 87: ...1 Jun 2018 Page 87 002000MAN 01 Electrical Box Layout 208 3 60...
Страница 88: ...Page 88 002000MAN 01 1 Jun 2018 Wiring Diagram 460 3 60...
Страница 89: ...1 Jun 2018 Page 89 002000MAN 01 Electrical Box Layout 460 3 60...
Страница 90: ...Page 90 002000MAN 01 1 Jun 2018 ACE 45 55 Wiring Diagram ACE 65 75 Wiring Diagram...
Страница 91: ...1 Jun 2018 Page 91 002000MAN 01...
Страница 92: ...Page 92 002000MAN 01 1 Jun 2018...
Страница 93: ...1 Jun 2018 Page 93 002000MAN 01...
Страница 94: ...Page 94 002000MAN 01 1 Jun 2018 Dimensions ATF 45 Left Return INDOOR UNIT OUTDOOR UNIT ACE 45...
Страница 95: ...1 Jun 2018 Page 95 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 45 Dimensions ATF 45 Right Return...
Страница 96: ...Page 96 002000MAN 01 1 Jun 2018 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Left Return...
Страница 97: ...1 Jun 2018 Page 97 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Right Return...
Страница 100: ...Page 100 002000MAN 01 1 Jun 2018 ACE 65 75 ACE 45 55...