Uploading/Downloading Projects via Flash 

In addition to uploading/downloading a project through the customary method of connecting a USB cable to a computer 
that contains MAPware-7000, you can also use the USB Host port on the HMC7057A-M or HMC7035A-M model to 
upload/download projects using a USB Flash Drive.  The Flash Drive must be formatted as FAT32.  Although Maple 
Systems has not tested every Flash Drive manufactured, Flash Drives from the following manufacturers have been found 
to work with the HMC7000 units: 

 

PNY: Attaché (4-8GB) 

 

SanDisk: Cruzer Micro (2-8GB) 

 

Transcend: JF V30 (1-8GB) 

 

Kingston: Data Traveler (4-8GB) 

 

Sony: Micro Vault (2-8GB) 

When using a Flash Drive with your HMC7000 unit, make sure that all important data is backed up to a safe location on 
another storage medium.    

Before you can upload/download a project, the HMC must have a project running that contains a screen with a Set Bit 
button object.  This object is tagged to internal memory bit S00037 – the USB Host Menu trigger: 

 

 

Note: this is just an example; you can create any type of screen as long as you have a Set Bit object that is tagged to 
S00037. 

When the project is running, the operator must press the Set button to set internal coil address S00037 (make sure that a 
Flash Drive is inserted into the USB Host port of the HMC).  This displays the following screen on the HMC: 

 

Click the Yes button to display the next screen in sequence: 

Содержание HMC7030A-L

Страница 1: ...trostatic discharge by Discharging personal static by grounding yourself prior to handling the HMC Handling the HMC at a static free grounded workstation Connecting the frame ground connector of the HMC to a clean earth ground Placing the HMC in an antistatic bag during transport Unpacking the Unit Carefully unpack the HMC Please read any instructions or cautions that appear on the shipping contai...

Страница 2: ...eliable However no responsibility is assumed by Maple Systems for the use of this information or for any infringements of patents or other rights of third parties which may result from its use No license is granted by implication or otherwise under any patent or patent rights of Maple Systems Inc Maple Systems retains the right to revise or change its products and documentation at any time without...

Страница 3: ...puts three expansion slots HMC7057A M 5 7 TFT 32K color display 320x240 pixels LED backlight 6 membrane style keys touchscreen 2 serial ports 1 USB slave port 1 USB host port no local inputs outputs five expansion slots These are the currently available expansion modules for the models listed above except for the HMC7030A L Contact Maple Systems if you need a module not listed Expansion Module Des...

Страница 4: ...emperature variations or high humidity Either will cause condensation of water inside the device and eventual damage to the HMC Highly humid areas are also to be avoided High humidity causes condensation of water in the unit Do not operate the HMC7000 Series in areas subject to explosion hazards due to flammable gases vapors or dusts NEMA Rating The HMC7000 Series is rated for NEMA 4 12 indoor or ...

Страница 5: ...anel does not flex or bow more than 0 010 in to ensure a proper seal Maximum thickness should be no more than 0 26 or 6 5mm The HMC should be mounted into a panel with a depth of at least 4 in 105 mm Allow a clearance of at least 1 in 25 mm on each side for mounting hardware Consider proper clearance for cable connections when mounting NOTE Cutout dimensions for each particular HMC model are readi...

Страница 6: ...gure 3 Figure 4 Make a cutout in the panel to the required size Place the unit into the panel The sealing gasket is placed directly behind the HMC bezel Note use a sealing adhesive in installations in which the panel surface is rough or uneven On each HMC there are four mounting slots Four mounting clamps with clamp bolt and cap nut are included with each HMC Insert each clamp into the mounting sl...

Страница 7: ...e a sealing adhesive in installations in which the panel surface is rough or uneven On each HMC there are four mounting slots Four mounting clamps with clamp bolt and cap nut are included with each HMC Insert each clamp into the mounting slots Hold the unit in place while you tighten the mounting bolts evenly to about 0 5 lb ft of torque Caution Do not over tighten the screws beyond snugness or yo...

Страница 8: ...ull out the lock connectors to attach the I O Expansion module to slots on the HMC7000 NOTE you must remove the protective tab directly below the Expansion Port label so that the I O Expansion interconnect plug can attach to the HMC7000 socket Push down the lock connectors to safely secure the I O Expansion module To remove the expansion module simply pull out the lock connectors on both sides and...

Страница 9: ...nclosure Corrosion develops over time and prevents good electrical contact For this reason a separate wire braid should be installed from the hinged control panel to the rest of the enclosure For a more in depth overview of ground wiring techniques refer to Technical Note 1027 OIT Ground Wiring and Electrical Noise Reduction which you can find in the Tech Notes section on our web site Connect HMC ...

Страница 10: ...wires connecting the output of the power line filter to the power supply should be kept as short as possible to minimize any additional noise pickup The case of the power line filter should be connected to a quiet earth ground The power line filter should have a current rating of at least 3 Amps with common mode and differential mode attenuation In applications that may have high frequency noise p...

Страница 11: ...ng power to the HMC before applying power again Figure 4 HMC Power Wiring To connect the HMC to power 1 Connect the power cable to the HMC a Strip cable shield to expose 2 of the black red wires b Strip of insulation from the black red wires c Connect red wire to the 24V DC positive input d Connect black wire to the 24V DC negative input e Connect power shield wire to chassis ground input 2 Route ...

Страница 12: ...1 Pin Number Name Description 1 TX RS422 transmit 2 TXD RS232 transmit 3 RXD RS232 receive 4 RX RS422 receive 5 GND Ground 6 NC No connection 7 NC No connection 8 TX RS422 transmit 9 RX RS422 receive Note for 2 wire RS485 jumper Pins 1 TX and 4 RX Also jumper Pins 8 TX and 9 RX COM2 port HMC7057 model only The COM2 port on the HMC7000 Series supports RS232 RS422 four wire and RS485 two wire connec...

Страница 13: ...232 for your HMC Please refer to the Maple Systems website to select a download cable Ethernet Ethernet is not available on any of the HMC7000 Series models but new models are under development If an Ethernet port is a requirement for your project please contact Maple Systems for information on new models USB Client port This port is used solely for downloading uploading projects into the HMC7000 ...

Страница 14: ...quirements when installing and wiring the module Digital Modules Expansion modules that have digital inputs and or digital outputs are termed digital modules The term digital signifies that the signal is interpreted by the module to be discrete levels either an ON state 1 or OFF state 0 Each digital input contact is tagged to an internal Input Coil X in the tag database of the HMC7000 Similarly ea...

Страница 15: ...th an X followed by a number is an input contact and a contact with a Y followed by a number is an output contact The number refers to the position associated with each contact in the I O module When you create your application project in MAPware 7000 you will have to assign a bit register memory address for each contact on the expansion module MAPware 7000 provides you with the option to allow th...

Страница 16: ...puts With analog inputs the analog module writes a data value to the assigned register XW based upon the measured DC voltage at the input 0 to 10 volts Resolution varies but is typically 16 bits meaning a data value of 0 equates to a measurement of 0 volts and a data value of 65535 equates to a measurement of 10 volts Analog outputs can deliver a DC voltage of 0 to 10 volts to a load with a minimu...

Страница 17: ...nt to properly configure your MAPware 7000 project Regardless of the particular HMC7000 model you are using the steps to configure the I O modules is very similar 1 Open a new project and select which product you wish to use Click OK 2 On the Project Configuration dialog box enter the appropriate information and then click OK 3 In the Project Information Window click on the I O Allocation folder a...

Страница 18: ... manufacturers including PLCs from Allen Bradley Rockwell Automation Schneider Electric Modbus RTU Siemens Omron and GE Fanuc Finally many of the HMC7000 models have two serial ports which allow simultaneous connections to two PLCs Each serial port is individually configured so that you are not restricted to using only one PLC communications driver Connecting to a PLC As mentioned above an externa...

Страница 19: ...our external PLC For more specific information about each external PLC supported please visit our Support Center Controller Info Sheets at our website www maplesystems com 4 Click OK Please note that you can check or adjust your settings by clicking on the Network Configuration folder in the Project Information Window 5 Simply right click on the PLC driver to display the Edit Model Settings dialog...

Страница 20: ...al PLC to one of the COM ports on the HMC7000 you can read write to the internal memory of the attached PLC To do this you must first assign tags to the PLC memory using the tag database Once PLC memory addresses have been assigned to the tag database you can then read write to the PLC in your project ...

Страница 21: ...Printer Columns the total number of columns or number of characters printed before the terminating character is issued Range is 1 to 256 default is 80 Note when printing a screen the HMC7000 can only print text characters that appear on the screen no graphics You can send data to the serial printer in a number of ways Set the Screen Print Properties attribute for a screen Use a Function Key to Pri...

Страница 22: ...GB Transcend JF V30 1 8GB Kingston Data Traveler 4 8GB Sony Micro Vault 2 8GB When using a Flash Drive with your HMC7000 unit make sure that all important data is backed up to a safe location on another storage medium Before you can upload download a project the HMC must have a project running that contains a screen with a Set Bit button object This object is tagged to internal memory bit S00037 t...

Страница 23: ...following screen appears Options include Application uploads only the application project to the flash drive The project is saved as an MPL file Application Logged Data uploads the project and any data logged Fonts uploads the font files used to create all text objects The font files are saved as FONT_File BIN Firmware uploads the firmware for the HMC7000 The firmware is saved as an ABS file Appli...

Страница 24: ... upload Click OK to begin This process can take several minutes to complete When completed the following screen appears Click the OK button The HMC7000 then displays the Upload Options screen Click the Exit button Unit will reboot and display the following Press the F2 function key on the HMC to run the internal project ...

Страница 25: ... file that currently resides in the HMC7000 The following screen appears Options include Application downloads only the application project mpl to the HMC7000 Fonts downloads the font file used to create all text objects Firmware downloads the firmware to the HMC7000 Ladder downloads the ladder logic only Click one of the options above to proceed to download Click OK to begin This process can take...

Страница 26: ... screen Click the Exit button Unit will reboot and display the following Press the F2 function key on the HMC to run the internal project Now that you have a general knowledge of the hardware features for the HMC7000 Series please consult the HMC7000 Series Programming Manual for information on how to use the many software features available ...

Страница 27: ... Guide 1010 1042 Rev 00 www maplesystems com 2011 Maple Systems Inc All rights reserved Maple Systems Inc 808 134 th Street SW Suite 120 Everett WA 98204 7333 Phone 425 745 3229 Email maple maplesystems com Web www maplesystems com ...

Отзывы: