TROUBLE SHOOTING GUIDE 

 

Manu

Flo

 

®

TM

 

FOR BATCH CONTROLLER / ROTA PULSE FLOW METER SYSTEMS 

 

PROBLEM 

 

 

POSSIBLE CAUSE 

 

SUGGESTED SOLUTION 

No power to batch controller   

Blown fuse or holder not tightened 

Check fuse, tighten fuse holder (at rear of controller) 

 or displays not on   

 

+12vdc and O.V. shorted 

 

Check pulse cable from DCD to RPFS meter 

 

 

 

 

No main power supply 

 

Check power supply, check wiring 

Pulse fails at start of batch   

•Check calibration (K-factor) setting 

•000 calibration –pulse-fails. Make sure a calibration value is set.  

(1.5 seconds after typical) 

 

 

 

 

 

 

 

 

 

 

 

Seized paddlewheel 

 

Remove RPFS, inspect; clean with acid, check axle/bushes 

 

 

 

 

 

 

 

 

  make sure paddlewheel spins freely 

 

 

 

 

Solenoid valve not opening   

Check and service solenoid valve, check output control voltage is 

 

 

 

 

 

 

 

 

  240vac(N & C, pins 7&9) when pushing start button 

 

 

 

 

Restriction or service gate valve closed 

Open gate valve 

 

 

 

 

Empty water tank   

 

Check water level 

 

 

 

 

Pump not turning   

 

Check and service pump 

 

 

 

 

•Pump foot valve failed 

 

•Empty pipe, Install non-return valve 

 

 

 

 

 

 

Signal cable cut, bad joint at JB, 

Check signal cable for 12VDC at junction box near RPFS meter 

 

 

 

 

  oxidized cable- leakage 

 

  If no power, cable cut or oxidized- repair/replace.  

 

 

 

 

 

 

 

 

  Unwire RPFS, take up to batch-room, remove extension cable  and 

 

 

 

 

 

 

 

 

  hardwire RPFS direct into the Batch controller (P,+,-), spin wheel 

 

 

 

 

 

 

 

 

  should count on display, if so, then extension cable or connections  

 

 

 

 

 

 

 

 

  at JB faulty, if no counts & 12vdc present then RPFS faulty 

 

 

 

 

•RPFS not positioned in pipe   

•Check RPFS slots are in keyway position, lock cap secured 

 

 

 

 

 

 

 

 

  Paddlewheel not inserted into flow stream 

 

 

 

 

RPFS Flowmeter faulty 

 

Replace with new RPFS  

 

 

 

 

 

 

 

Pulse fails during batch cycle  

Flowrate too slow   

 

Open restriction gate valve, or increase minimum flowrate in  

program.   

 

 

 

 

 

 

  Pipe diameter too big for flowrate (reduce pipe dia. or increase flow)  

 

 

 

 

Pipe buildup restricting flow   

Cleanout pipelines, calcium buildup on pipe walls -recycle systems 

 

 

 

 

Paddlewheel problem 

 

Calcium buildup on wheel, soak in diluted acid. Warn bushes. 

 

 

 

 

 

Backflow alarm 

 

 

Non return valve faulty  (jammed open) 

Clean, service or replace 

  after batch complete 

 

•Solenoid valve not properly closed 

•damaged seal, faulty solenoid 

 

 

Batch target display counter   

Flowrate too fast excessive overflow 

Turn down gate valve to restrict flowrate 

  counts past batch selection    

 

 

 

 

  or set preact (overflow deduct) function to compensate 

 

 

 

 

 

 

 

 

Reduce delivery pipe diameter 

•Intermittent overflow past batch select  •Faulty solenoid valve not closing 

•service solenoid valve, check air pressure 

 or water does not stop 

 

 

 

 

 

 properly, insufficient air pressure 

Over batch alarm sounds   

 

 

 

 

  

 

Wet loads, more  water 

 

Paddlewheel bushes worn 

 

Check paddlewheel 

collected than indicated 

 

Wheel dirty, flowing over range 

 

Replace with new paddlewheel, recalibrate 

Dry loads, less water 

 

Requires recalibration test 

 

Set new calibration figure. 

 collected than indicated 

 

 

 

 

 

  

 

Controller starts counting 

 

Active and contact power 

 

Contactor fused due to excessive current draw from pump 

  when power switched on 

 

  drive short circuited 

 

 

Relay fused due to excessive current draw on solenoid coil

 

 

 

 

 

 

 

 

 

 

  - install higher current rated contactor or install contactor 

 

Interference on pulse cable input –use shielded cable only. 

 

ANY OTHER PROBLEMS REFER TO ME3000 USER MANUAL –Trouble shooting guide. 

 

Sequential fault finding and rectification 

1. 

If a another ManuFlo controller (any model) is available, simply unplug doubtful unit and plug in exchange unit. If the new unit is also not 
operating correctly, then the problem is isolated to the pulse flowmeter or wiring.

 

2. 

When  checking  flowmeter,  reset  the  ManuFlo  controller.  Remove  the  flow  sensor  and  spin  the  paddlewheel.  Check  that  the  ManuFlo 
controller has registered a number of counts on its display. If so, the  lectrical connections are probably OK. If no counts are registered, check 
that 12VDC is supplied to the flow sensor. If supplied, then switch off the ManuFlo controller and replace the RPFS flow sensor. 

 

3. 

The flow sensor paddlewheel is jammed, damaged etc. (For servicing, refer to the flow sensor brochure).

 

 
 

If in further doubt, contact your local representative, or ManuFlo on ph +61 2 9938 1425 or 9905 432

 

Содержание ManuFlo ME3000-RPFS

Страница 1: ...flowmeter as per the installation guide found on the flowmeter brochure Install the Rota Pulse paddlewheel sensor RPFS P in a straight pipe section with the same diameter pipe as the adaptor tee section with 10x diameter before and 5x diameter after the sensor with no elbows reducers valves or restrictions within this pipe run Where the sensor is housed the pipe must be full when measuring D Use s...

Страница 2: ...nd continuously if an error occurs With the ME3000 Batch Controller using the same instrument housing and the same 10 pin Weidmuller receptacle plug as other ManuFlo Batch Controller models changeover or upgrade is instant with no rewiring necessary It can be easily interfaced with PLCs through the optional computer control interface thus incorporating the controller s safety features and providin...

Страница 3: ...nfiguration value is diplayed entering a new value via the keypad causes the display value to change and flash Then pressing SET locks in the new value or pressing CANCEL reverts value to its original setting and the display digits stop flashing Use the up down arrows buttons to step through more configuration settings or press CANCEL for 2 seconds to exit to the SET RDY display CALIBRATION 1 The ...

Страница 4: ...nel Eagle etc PLCs MC 4 pin PLC Computer Command Start Stop Reset interface plug MC2 2 pin plug for scaled open collector pulse output Includes 4 pin external command Start Stop Reset interface plug e g ME3000 is the standard Batch Controller 240vac powered without any of the options whereas ME3000 MC2 is an ME3000 Batch Controller with a scaled open collector pulse o p and external Start Stop Res...

Страница 5: ...tion to larger size pipes is possible depending on pipe wall thickness alternatively the Long Stem LS versions with adaptors are then used With only one moving part and limited intrusion into the pipe and combined with its flow through design the RPFS allows accurate measurement of liquid flows with virtually no head losses Each of the 4 blades of the rotor paddlewheel extends approximately one ce...

Страница 6: ...G 6 1 Unscrew the black PVC locking cap anti clockwise 2 Hold the neck of the Tee piece in your left hand grasp the RPFS body with your right hand and turn slowly anti clockwise until the sensor hydraulically raises out of slot then pull upwards out of the socket never by the cable When returning the sensor to nipple adaptor insert so the keyway and slots line up then then push down until they loc...

Страница 7: ...e If mounted in horizontal or inclined pipe make sure insertion position of sensor is at top or 45 from top not on the underside Selection of pipe diameter For best results use the table below Pipe size Flowrange Litres min Pulses Litre mm Min Max approx 1 2 20 13 160 116 25 20 250 75 32 30 410 46 40 50 640 30 50 90 1000 20 63 132 1580 11 7 65 120 1690 12 75 180 2250 8 3 80 190 2560 7 3 90 244 324...

Страница 8: ...25 LS 140 mm SC140 LS 150 mm PVC150SC LS SCP150 LS SC160 LS 160 mm SCPE160 LS SC160 LS 200 mm PVC200SC LS SCP200 LS SC200 LS 225 mm SCPE225 LS SC225 LS 250 mm SCP250 LS SC250 LS 280 mm SC280 LS 300 mm PVC300SC LS SCPE300 LS SC315 LS Galvanised iron threaded ends BSP female 2000 kPa Note 25mm can be supplied with straight pipe sections already fitted Part GAL25 T2 PVC T piece Class 18 Cat 19 Glue i...

Страница 9: ...4 ME3000 ME995 wiring with RPFS or other powered flowmeters ...

Страница 10: ...5 ME3000 ME995 wiring with RPFS or other powered flowmeters ...

Страница 11: ...6 PLUMBING INSTALL options guide for RPFS or other ManuFlo flowmeters ...

Страница 12: ...7 ...

Страница 13: ...blem Calcium buildup on wheel soak in diluted acid Warn bushes Backflow alarm Non return valve faulty jammed open Clean service or replace after batch complete Solenoid valve not properly closed damaged seal faulty solenoid Batch target display counter Flowrate too fast excessive overflow Turn down gate valve to restrict flowrate counts past batch selection or set preact overflow deduct function t...

Отзывы: