DKR Drive Controllers
Planning the cabinet
5-15
DOK-DIAX03-DKR********-PR02-EN-P
Distances, drill diagram and vents
Note:
The vents in the back wall of the cabinet or mounting panel
are only required if the drive is cooled with air from outside the
unit.
11+0,2
5,2+0,2
(4x)
(4x)
460±0,5
360±0,5
264
(20)
zMalkDKR4
806
165
1050
± 0,5
11
0
360±0,5
500±0,5
40
min.
80 mm
air outlet
air inlet
min.
80 mm
min.
80 mm
Looking from outside of control enclosure onto rear wall or mounting panel.
All dimensions in mm.
control enclosure rear wall
or mounting panel
Fig. 5-14:
Distances, drill diagram and vents for DKR04