51
Safety Limit 3
If the freeze time reaches 4 minutes and water is not
sensed (float remains down for 10 continuous seconds)
the ice machine stops.
• Safety Limit 3 is bypassed on the initial cycle (manual
start or after a full bin/safety limit condition). For
all subsequent cycles if the freeze time reaches 4
minutes and water is not sensed, the ice machine
stops and initiates a 30 minute delay period. Control
board lights SL#1 and SL#2 along with the touch pad
Service (wrench) light will flash on/off at 1 second
intervals.
• The ice machine automatically restarts at the end of
the 30 minute delay period and stops flashing the
control board and Service (wrench) lights.
• If 100 consecutive failures occur the ice machine
stops and the touch pad Service (wrench) light
remains energized.
Содержание STH042 4/16
Страница 2: ......
Страница 14: ...14 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...42 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 56: ...56 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ...98 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...124 Part Number STH042 4 16 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING SV1406 Using Pinch Off Tool ...
Страница 126: ...126 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 136: ...136 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Страница 137: ...Part Number STH042 4 16 137 U310 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Страница 138: ...138 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Страница 139: ...Part Number STH042 4 16 139 U310 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Страница 144: ...144 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 145: ......