83
Suction Pressure Low Checklist
Improper Installation
• Refer to “Installation/Visual Inspection Checklist” on
Discharge Pressure
• Discharge pressure is too low, and is affecting suction
pressure, refer to “Freeze Cycle Discharge Pressure
Low Checklist” on page 79.
Improper Refrigerant Charge
• Undercharged
• Wrong type of refrigerant
Other
• Non-Manitowoc components in system
• Improper water supply over evaporator refer to
”Water System Checklist” on page 68.
• Loss of heat transfer from tubing on back side of
evaporator
• Restricted/plugged liquid line drier
• Restricted/plugged tubing in suction side of
refrigeration system
• TXV starving
NOTE: Do not limit your diagnosis to only the items listed
in the checklists.
Содержание STH042 4/16
Страница 2: ......
Страница 14: ...14 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...42 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 56: ...56 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ...98 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...124 Part Number STH042 4 16 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING SV1406 Using Pinch Off Tool ...
Страница 126: ...126 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 136: ...136 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Страница 137: ...Part Number STH042 4 16 137 U310 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Страница 138: ...138 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Страница 139: ...Part Number STH042 4 16 139 U310 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Страница 144: ...144 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 145: ......