110
Fan Cycle Control
Function
Cycles the fan motor on and off to maintain proper
operating discharge pressure.
The fan cycle control closes on an increase, and opens on
a decrease in discharge pressure.
Specifications
Model
Cut-n (Close)
Cut-Out (Open)
U140
U190
250 psig ±5
200 psig ±5
U240
U310
275 psig ±5
225 psig ±5
Check Procedure
Disconnect electrical power to the ice machine at the
electrical service disconnect.
Verify fan motor windings are not open or grounded, and
fan spins freely.
Connect manifold gauge to ice machine.
Hook voltmeter in parallel across the fan cycle control,
leaving wires attached.
Reconnect electrical power to the ice machine and press
the power button to ON.
Wait until water flows over the evaporator then refer to
chart below.
System Pressure:
Reading
Should Be:
Fan Should Be:
above cut-in
0 volts
running
below cut-out
line voltage
off
Содержание STH042 4/16
Страница 2: ......
Страница 14: ...14 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...42 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 56: ...56 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ...98 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...124 Part Number STH042 4 16 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING SV1406 Using Pinch Off Tool ...
Страница 126: ...126 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 136: ...136 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Страница 137: ...Part Number STH042 4 16 137 U310 WIRING DIAGRAM WITHOUT J4 THERMISTOR TERMINAL ...
Страница 138: ...138 Part Number STH042 4 16 U140 U190 U240 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Страница 139: ...Part Number STH042 4 16 139 U310 WIRING DIAGRAM WITH J4 THERMISTOR TERMINAL ...
Страница 144: ...144 Part Number STH042 4 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 145: ......