Section 2
Installation Instructions
Part Number 000001196 3/08
2-15
Refrigeration System Installation
Traditional Remote Ice Machines Only
.
Factory Equipment Refrigeration Amounts
ICE MACHINE HEAD SECTION
Each ice machine head section ships from the factory
with a R-404A refrigerant charge appropriate for line
sets up to 50’ in length. The serial tag on the ice
machine indicates the refrigerant charge. The ice
machine may need additional refrigerant for line set
lengths between 50’ and 100’ see chart below.
Traditional
Remote
Ice Machine
Remote Single
Circuit
Condenser
Line Set*
SF600
SN650
JC0495
RM-20
RM-35
RM-50
*Lineset
Liquid Line
Discharge Line
RM20/35/50
1/4”
5/16”
Air Temperature Around the Condenser
Minimum
Maximum
-20°F (-29°C)
120°F (49°C)
!
Warning
Installation of a Remote Condenser may require the use
of special equipment for placement. Trained and
qualified personnel are required for proper rigging and
lifting.
!
Caution
The 60-month compressor warranty (including the
24-month labor replacement warranty) will not apply if
the Manitowoc Ice Machine and remote condenser
are not installed according to specifications. This
warranty also will not apply if the refrigeration system
is modified with a condenser, heat reclaim device, or
other parts or assemblies not manufactured by
Manitowoc Ice, Inc.
Important
Manitowoc remote systems are only approved and
warranted as a complete new package. Warranty on
the refrigeration system will be void if a new ice
machine head section is connected to pre-existing
(used) tubing or remote condensers.
Ice Machine
Additional Refrigerant Required
SF0600
None
SN0650
None
!
Caution
Never add more than nameplate charge to the
refrigeration system for any application.
!
Caution
Manitowoc SN Model ice machines are not approved
for use with non-Manitowoc traditional condensers or
remote condensing units. The 60-month compressor
warranty (including the 24-month labor replacement
warranty) will not apply if Manitowoc SN Model Ice
Machines are installed with a non-Manitowoc
traditional condenser or remote condensing unit.
Содержание RFC0985
Страница 12: ...General Information Section 1 1 6 Part Number 000001196 3 08 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...Installation Instructions Section 2 2 30 Part Number 000001196 3 08 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 60: ...Maintenance Section 4 4 14 Part Number 000001196 3 08 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 65: ...Section 5 Before Calling for Service Part Number 000001196 3 08 5 5 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 66: ...Before Calling for Service Section 5 5 6 Part Number 000001196 3 08 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 67: ......