Part Number STH042 3/14
79
Suction Pressure High Checklist
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
on page 64.
Discharge Pressure
•
Discharge pressure is too high, and is affecting
suction pressure, refer to “Discharge Pressure
High Checklist” on page 76.
Improper Refrigerant Charge
•
Overcharged
•
Wrong type of refrigerant
•
Non-condensable in system
Other
•
Non-Manitowoc components in system
•
Harvest valve leaking
•
TXV flooding (check bulb mounting)
•
Defective compressor