Contamination/Cleanup Chart
Symptoms/Findings
Required
Cleanup
Procedure
No symptoms or suspicion of
contamination
Normal
evacuation/
recharging
procedure
Moisture/Air Contamination symptoms
Refrigeration system open to
atmosphere for longer than 15 minutes
Refrigeration test kit and/or acid oil test
shows contamination
No burnout deposits in open
compressor lines
Mild
contamination
cleanup
procedure
Mild Compressor Burnout symptoms
Oil appears clean but smells acrid
Refrigeration test kit or acid oil test
shows harmful acid content
No burnout deposits in open
compressor lines
Mild
contamination
cleanup
procedure
Severe Compressor Burnout symptoms
Oil is discolored, acidic, and smells
acrid
Burnout deposits found in the
compressor, lines, and other
components
Severe
contamination
cleanup
procedure
Содержание NEO
Страница 2: ......
Страница 20: ...20 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 30: ...30 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 46: ...46 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 94: ...94 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 107: ...Part Number STH042 3 14 107 This Page Intentionally Left Blank ...
Страница 119: ...Part Number STH042 3 14 119 Using Pinch Off Tool SV1406 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING ...
Страница 130: ...130 Part Number STH042 3 14 WIRING DIAGRAM ALL MODELS ...
Страница 134: ...134 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 135: ......