104
Part Number STH042 3/14
Fan Cycle Control
Function
Cycles the fan motor on and off to maintain proper
operating discharge pressure.
The fan cycle control closes on an increase, and
opens on a decrease in discharge pressure.
Specifications
Check Procedure
Disconnect electrical power to the ice machine at the
electrical service disconnect.
Verify fan motor windings are not open or grounded,
and fan spins freely.
Connect manifold gauge to ice machine.
Hook voltmeter in parallel across the fan cycle control,
leaving wires attached.
Reconnect electrical power to the ice machine and
press the power button to ON.
Wait until water flows over the evaporator then refer to
chart below.
Model
Cut-In
(Close)
Cut-Out
(Open)
U140
U190
250 psig
±
5
200 psig
±
5
U240
U310
275 psig
±
5
225 psig
±
5
System
Pressure:
Reading
Should Be:
Fan Should
Be:
above cut-in
0 volts
running
below cut-out
line voltage
off
Содержание NEO
Страница 2: ......
Страница 20: ...20 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 30: ...30 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 46: ...46 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 94: ...94 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 107: ...Part Number STH042 3 14 107 This Page Intentionally Left Blank ...
Страница 119: ...Part Number STH042 3 14 119 Using Pinch Off Tool SV1406 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING ...
Страница 130: ...130 Part Number STH042 3 14 WIRING DIAGRAM ALL MODELS ...
Страница 134: ...134 Part Number STH042 3 14 This Page Intentionally Left Blank ...
Страница 135: ......