Part Number 000014797 Rev02 05/18
209
6. Let the system “settle” for 2 to 3 minutes.
7. Place the toggle switch in the ICE position.
NOTE: Manifold gauge set must be removed properly to
ensure that no refrigerant contamination or loss occurs.
8. Verify that all of the vapor in the charging hoses is
drawn into the ice machine before disconnecting the
charging hoses.
A. Run the ice machine in the freeze cycle.
B. Verify the refrigerant cylinder valve is closed.
C. Open the high and low side valves on the
manifold gauge set. Any refrigerant in the lines
will be pulled into the low side of the system.
D. Allow the pressures to equalize while the ice
machine is in the freeze cycle.
E. Close the high and low side manifold gauge set
and remove from the ice machine.
F. Remove the temporary access fittings