WATER LEVEL CHECK
The float valve is factory-set for the proper water level.
If adjustments are necessary:
1. Verify the ice machine is level.
2. Remove the siphon cap from the standpipe.
3. Place the main ON/OFF/WASH toggle switch to the
ON position, and wait until the float valve stops
adding water.
4. Adjust the water level to [1/4” to 3/8” (6.3 to 9.5 mm)
below the standpipe] the line in the water trough:
A. Loosen the two screws on the float valve bracket.
B. Raise or lower the float valve assembly as
necessary, then tighten the screws.
C. Move the main ON/OFF/WASH toggle switch to
the OFF position. The water level in the trough
will rise above the standpipe and run down the
drain.
5. Replace the siphon cap on the standpipe, and verify
water level and siphon action by repeating steps 3
through 5.
Содержание NEO UD0140A
Страница 2: ......
Страница 20: ...20 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 182: ...182 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 215: ...Part Number 000014797 Rev02 05 18 215 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING Using Pinch Off Tool ...
Страница 252: ...252 Part Number 000014797 Rev02 05 18 ELECTRONIC CONTROL BOARD UDE065 1 2 3 4 5 6 ...
Страница 254: ...254 Part Number 000014797 Rev02 05 18 ELECTRONIC CONTROL BOARD UDE080 1 2 3 4 5 6 7 8 9 10 ...
Страница 258: ...258 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 259: ......