146
Part Number 000014797 Rev02 05/18
Suction Temperature Low Checklist
Improper Installation
• Refer to “Installation/Visual Inspection Checklist” on
Discharge Pressure
• Discharge temperature is too low, and is affecting
suction temperature, refer to “Freeze Cycle Discharge
Temperature Low Checklist” on page 143.
Improper Refrigerant Charge
• Undercharged
• Wrong type of refrigerant
Other
• Non-Manitowoc components in system
• Improper water supply over evaporator refer to
”Water System Checklist” on page 137.
• Loss of heat transfer from tubing on back side of
evaporator
• Restricted/plugged liquid line drier
• Restricted/plugged tubing in suction side of
refrigeration system
• TXV starving
NOTE: Do not limit your diagnosis to only the items listed
in the checklists.
Содержание NEO UD0140A
Страница 2: ......
Страница 20: ...20 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 182: ...182 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 215: ...Part Number 000014797 Rev02 05 18 215 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING Using Pinch Off Tool ...
Страница 252: ...252 Part Number 000014797 Rev02 05 18 ELECTRONIC CONTROL BOARD UDE065 1 2 3 4 5 6 ...
Страница 254: ...254 Part Number 000014797 Rev02 05 18 ELECTRONIC CONTROL BOARD UDE080 1 2 3 4 5 6 7 8 9 10 ...
Страница 258: ...258 Part Number 000014797 Rev02 05 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 259: ......